TITLE 12. HEALTH
Title of Regulation: 12VAC5-590. Waterworks Regulations (amending 12VAC5-590-10, 12VAC5-590-40, 12VAC5-590-50, 12VAC5-590-70, 12VAC5-590-100 through 12VAC5-590-150, 12VAC5-590-190 through 12VAC5-590-270, 12VAC5-590-290 through 12VAC5-590-392, 12VAC5-590-405, 12VAC5-590-421, 12VAC5-590-430, 12VAC5-590-440, 12VAC5-590-450, 12VAC5-590-470 through 12VAC5-590-580, 12VAC5-590-600, 12VAC5-590-610, 12VAC5-590-630, 12VAC5-590-640, 12VAC5-590-660, 12VAC5-590-670, 12VAC5-590-680, 12VAC5-590-700, 12VAC5-590-720, 12VAC5-590-730, 12VAC5-590-760, 12VAC5-590-770, 12VAC5-590-790, 12VAC5-590-810, 12VAC5-590-820, 12VAC5-590-840, 12VAC5-590-850, 12VAC5-590-860, 12VAC5-590-880, 12VAC5-590-900 through 12VAC5-590-960, 12VAC5-590-990 through 12VAC5-590-1020, 12VAC5-590-1040, 12VAC5-590-1050, 12VAC5-590-1080, 12VAC5-590-1090, 12VAC5-590-1110 through 12VAC5-590-1180, 12VAC5-590-1210, 12VAC5-590-1220, 12VAC5-590-1230; adding 12VAC5-590-35, 12VAC5-590-45, 12VAC5-590-55, 12VAC5-590-115, 12VAC5-590-372, 12VAC5-590-373, 12VAC5-590-374, 12VAC5-590-376, 12VAC5-590-377, 12VAC5-590-378, 12VAC5-590-382, 12VAC5-590-383, 12VAC5-590-384, 12VAC5-590-388, 12VAC5-590-391, 12VAC5-590-395, 12VAC5-590-401, 12VAC5-590-411, 12VAC5-590-415, 12VAC5-590-461, 12VAC5-590-475, 12VAC5-590-476, 12VAC5-590-515, 12VAC5-590-531, 12VAC5-590-532, 12VAC5-590-546, 12VAC5-590-565, 12VAC5-590-725, 12VAC5-590-865, 12VAC5-590-871 through 12VAC5-590-875, 12VAC5-590-881, 12VAC5-590-882, 12VAC5-590-883, 12VAC5-590-895, 12VAC5-590-975, 12VAC5-590-985, 12VAC5-590-1001 through 12VAC5-590-1005, 12VAC5-590-1065, 12VAC5-590-1081, 12VAC5-590-1082, 12VAC5-590-1235; repealing 12VAC5-590-20, 12VAC5-590-30, 12VAC5-590-60, 12VAC5-590-80, 12VAC5-590-160, 12VAC5-590-170, 12VAC5-590-180, 12VAC5-590-280, 12VAC5-590-400, 12VAC5-590-410, 12VAC5-590-420, 12VAC5-590-425, 12VAC5-590-460, 12VAC5-590-590, 12VAC5-590-620, 12VAC5-590-650, 12VAC5-590-690, 12VAC5-590-710, 12VAC5-590-740, 12VAC5-590-750, 12VAC5-590-780, 12VAC5-590-800, 12VAC5-590-870, 12VAC5-590-890, 12VAC5-590-970, 12VAC5-590-980, 12VAC5-590-1030, 12VAC5-590-1060, 12VAC5-590-1070, 12VAC5-590-1100, 12VAC5-590-1190, 12VAC5-590-1200, 12VAC5-590-1240 through 12VAC5-590-1280, Appendices A through E, Appendix G, Appendix I, Appendix L through P).
Statutory Authority: §§ 32.1-12 and 32.1-170 of the Code of Virginia.
Effective Date: June 23, 2021.
Agency Contact: Dwayne Roadcap, Office Director, Office of Drinking Water, Virginia Department of Health, 109 Governor Street, Richmond, VA 23219, telephone (804) 864-7522, or email dwayne.roadcap@vdh.virginia.gov.
Summary:
The amendments reorganize provisions; add new sections to expand or clarify existing requirements or incorporate new ones; remove obsolete information and duplication; update citations; correct sentence structure, grammar, spelling, and typographical errors; and improve consistency.
In Part I (General Framework for Waterworks Regulations), amendments (i) revise, add, or delete definitions; (ii) add units of measurement; (iii) add new sections regarding the Waterworks Advisory Committee, the relationship of the Waterworks Regulations to the Uniform Statewide Building Code, and administrative proceedings and enforcement requirements; (iv) clarify and streamline the permit process, including the requirements for obtaining a construction permit; and (v) add requirements and circumstances for issuance of a temporary operation permit.
In Part II (Operation Regulations for Waterworks), amendments (i) consolidate all water quality standards, maximum contaminant levels, action levels, treatment techniques, and maximum disinfectant levels and goals; (ii) revise and clarify the procedure for determining surface water influence of groundwater sources; (iii) revise and clarify the classification of waterworks, operator requirements, and operator attendance; (iv) add new sections for abandoning and reactivating wells; (v) reorganize operation report content requirements; (vi) revise and clarify cross-connection control program requirements; and (vii) generally reorganize content into smaller sections.
In Part III (Manual of Practice for Waterworks Design), amendments (i) update design water demand and waterworks capacity requirements; (ii) revise and clarify metering, building design, layout, laboratory design, and new source development requirements for groundwater sources, including springs; (iii) clarify well construction requirements and classification; (iv) distinguish and clarify construction, testing, and capacity requirements for wells located in designated groundwater management areas; (iv) revise and clarify water treatment processes by adding new sections for membrane filtration, bag and cartridge filtration, pre-engineered package treatment units, powdered activated carbon, disinfection processes using chloramines, chlorine dioxide, ultraviolet light, and ozone; (v) clarify design requirements for pump stations and equipment; (vi) distinguish atmospheric and pressure storage tank design requirements; (vii) add a new section on water loading stations; and (viii) generally reorganize content into new, smaller sections.
In Part IV (Exceptions for Noncommunity Waterworks) and the appendices, amendments move some requirements into Part II or III of the chapter and repeal Part IV and all appendices.
Amendments, identified as substantive by the agency, to the proposed regulation (i) add special monitoring requirements for sodium in drinking water; (ii) add a requirement that an owner shall document the Cross-Connection Control Program in a plan and submit the written plan to the department for review and approval and clarify owner and department must ensure cross-connections are adequately safeguarded; (iii) update and clarify requirements in the Cross-Connection Control Program; (iv) update conditions where actual or potential cross-connection hazards can be eliminated or controlled by allowing point-of-use isolation backflow protection instead of containment; (v) update low-hazard and high-hazard examples of backflow situations; and (vi) clarify design requirements for hydrants and flushing devices.
Article 1
Definitions
12VAC5-590-10. Definitions and units of measurement.
A. Definitions. As used in this chapter, the following words and, terms, and abbreviations shall have meanings respectively set forth unless the context clearly requires a different meaning:
"Action level" or "AL" means the concentration of lead or copper in water specified in 12VAC5-590-385, which determines, in some cases, the treatment requirements contained in 12VAC5-590-405 that an owner is required to complete.
"Administrative Process Act" or "APA" means Chapter 40 (§ 2.2-4000 et seq.) of Title 2.2 of the Code of Virginia. The APA is the basic law conferring authority on agencies either to make regulations or case decisions as well as to standardize court review thereof.
"Air gap separation" means the unobstructed vertical distance through the free atmosphere between the lowest opening from any pipe or faucet supplying pure water to a tank, plumbing fixture, or other device and the rim of the receptacle point of the potable water outlet and the flood rim of the receiving vessel.
"Annual daily water demand" means the average rate of daily water usage over at least the most recent three-year period.
"ANSI" means the American National Standards Institute.
"Applied water" means water that is ready for filtration.
"Approved" means material, equipment, workmanship, process or method that has been accepted by the commissioner as suitable for the proposed use.
"ASME" means the American Society of Mechanical Engineers.
[ "ASSE" means the American Society of Sanitary Engineering. ]
"ASTM" means the American Society for Testing and Materials.
"Auxiliary water system" means any water supply or system on or available to the premises of the consumer other than the waterworks. These auxiliary waters may include water from a source such as wells, lakes, or streams; process fluids; or used water. They may be polluted or contaminated or, objectionable, or of questionable quality and constitute an unapproved water source supply or system over which the water purveyor waterworks owner does not have control.
"AWWA" means the American Water Works Association.
"Backflow" means the undesirable reversal of flow of water or mixtures of water and other liquids, mixtures gases, or other substances into the distribution piping of a waterworks from any source or sources other than its intended source.
"Backflow elimination method" means the air gap separation or physical disconnection that will eliminate the cross-connection.
"Backflow prevention assembly" means a mechanical unit, designed to [ control various cross-connections and ] stop the reversal of flow that includes an inlet and outlet shutoff valve and test cocks [ to facilitate testing of the assembly ]. Backflow prevention assemblies include the reduced pressure principle backflow prevention [ (RPZ) ] assembly, the double [ gate-double ] check valve assembly, and the pressure vacuum breaker assembly.
"Backflow prevention device" means any approved device, method, or type of construction intended to prevent backflow into a waterworks. a mechanical unit designed to [ control cross-connections and ] stop the reversal of flow that is not testable because it does not have inlet and outlet shutoff valves or test cocks. A backflow prevention device is not generally designed or constructed to withstand [ backpressure continuous pressure over 12 hours, or to control high hazards ]. A backflow prevention device generally includes the atmospheric type vacuum breakers and the dual check valve type devices.
"Backpressure backflow" means backflow caused by pressure in the downstream piping that is superior to the supply pressure at the point of consideration.
"Backsiphonage" means backflow caused by a reduction in pressure that causes a partial vacuum, creating a siphon effect.
"Bag filters" means pressure-driven separation devices that remove particulate matter larger than one micrometer using an engineered porous filtration media. They Bag filters are typically constructed of a nonrigid, fabric filtration media housed in a pressure vessel in which the direction of flow is from the inside of the bag to outside.
"Bank filtration" means a water treatment process that uses a well to recover surface water that has naturally infiltrated into groundwater through a river bed or bank(s) or bank. Infiltration is typically enhanced by the hydraulic gradient imposed by a nearby pumping water supply or other well(s) well.
"Best available technology" or "BAT" means the best practicable technology, treatment techniques, or other means that the [ commissioner department ] finds, after examination for efficacy under field conditions and not solely under laboratory conditions and in conformance with applicable EPA regulations, that are available (taking cost into consideration).
"Board" means the State Board of Health.
"Breakpoint chlorination" means the addition of chlorine to water until the chlorine demand has been satisfied and further additions result in a residual that is directly proportional to the amount added.
"Boil water advisory" and "boil water notice" mean a statement that informs consumers that drinking water is or may be contaminated and that the water should be boiled before being used for human consumption.
"BSSP" means a bacteriological sample siting plan.
"CAP" means a corrective action plan.
"Cartridge filters" means pressure-driven separation devices that remove particulate matter larger than one micrometer using an engineered porous filtration media. They Cartridge filters are typically constructed as rigid or semi-rigid, self-supporting filter elements housed in pressure vessels in which flow is from the outside of the cartridge to the inside.
"Chlorine" means dry chlorine.
"Chlorine gas" means dry chlorine in the gaseous state.
"Chlorine solution (chlorine water)" means a solution of chlorine in water.
"Chronically noncompliant waterworks" or "CNC" means a waterworks that is unable to provide pure water for any of the following reasons: (i) the waterworks' record of performance demonstrates that it can no longer be depended upon to furnish pure water to the persons served; (ii) the owner has inadequate technical, financial, or managerial capacity to furnish pure water to the people served; (iii) the owner has failed to comply with an order issued by the board or the commissioner; (iv) the owner has abandoned the waterworks and has discontinued supplying pure water to the persons served; or (v) the owner is subject to a forfeiture order pursuant to § 32.1-174.1 of the Code of Virginia.
"Case decision" means an agency determination as defined in § 2.2-4001 of the Code of Virginia.
"CCCP" means a cross-connection control program.
"CCR" means consumer confidence report.
"CDC" means the Centers for Disease Control and Prevention.
"CFE" means the combined filter effluent.
"CFR" means the Code of Federal Regulations.
"Clean compliance history" means a record of no PMCL violations for microbiological contaminants, no monitoring violations under 12VAC5-590-370, and no coliform treatment technique trigger exceedances or treatment technique violations under 12VAC5-590-392.
"Coagulation" means a process using coagulant chemicals and mixing by which colloidal and suspended materials are destabilized and agglomerated into floc.
"Coliform bacteria group" means a group of bacteria predominantly inhabiting the intestines of man or animal but also occasionally found elsewhere. It includes all aerobic and facultative anaerobic, gram-negative, non-sporeforming bacilli that ferment lactose with production of gas. Also included are all bacteria that produce a dark, purplish-green colony with metallic sheen by the membrane filter technique used for coliform identification.
"Combined distribution system" means the interconnected distribution system consisting of the distribution systems of wholesale waterworks and of the consecutive waterworks that receive finished water.
"Commissioner" means the State Health Commissioner, who is the executive officer of the board.
"Community waterworks" means a waterworks that serves at least 15 service connections used by year-round residents or regularly serves at least 25 year-round residents.
"Compliance cycle" means the nine-year calendar year cycle during which a waterworks shall monitor. Each compliance cycle consists of three three-year compliance periods. The first calendar year cycle begins began January 1, 1993, and ends ended December 31, 2001; the second begins January 1, 2002, and ends December 31, 2010; the third begins January 1, 2011, and ends December 31, 2019 with subsequent compliance cycles continuing thereafter.
"Compliance period" means a three-year calendar year period within a compliance cycle. Each compliance cycle has consists of three three-year compliance periods. Within the first compliance cycle, the first compliance period runs from January 1, 1993, to December 31, 1995; the second from January 1, 1996, to December 31, 1998; the third from January 1, 1999, to December 31, 2001 The first compliance period began January 1, 1993, and ended December 31, 1995, with subsequent compliance periods continuing thereafter.
"Comprehensive performance evaluation" or "CPE" means a thorough review and analysis of a treatment plant's performance-based capabilities and associated administrative, operational and maintenance practices. It is conducted to identify factors that may be adversely impacting a plant's capability to achieve compliance and emphasizes approaches that can be implemented without significant capital improvements. For purposes of compliance with 12VAC5-590-530 E 1 b (2), the comprehensive performance evaluation shall consist of at least the following components: assessment of plant performance, evaluation of major unit processes, identification and prioritization of performance limiting factors, assessment of the applicability of comprehensive technical assistance, and preparation of a CPE report.
"Comprehensive business plan" means a plan detailing the technical, managerial, and financial [ (TMF) ] commitments that the owner will make in order to assure that the waterworks will have the capability to provide water that complies with this chapter over the long term.
"Confirmation sample" means a sample to be collected by the owner within a specified time after the results of the initial sample are known to have exceeded a specified limit or standard in order to validate the initial result and to determine compliance.
"Confluent growth" means a continuous bacterial growth covering the entire filtration area of a membrane filter, or a portion thereof, in which bacterial colonies are not discrete.
"Consecutive waterworks" means a waterworks that has no water production or source facility of its own and that obtains all of its water from another permitted waterworks or receives some or all of its finished water from one or more wholesale waterworks. Consecutive waterworks may provide additional treatment to finished water. Delivery may be through a direct connection or through the distribution system of one or more consecutive waterworks.
"Consolidated" means rock made from sedimentary, igneous, or metamorphic materials that have been metamorphosed or cemented together forming strata or bodies of rock.
"Consumer" means any person who drinks receiving water for human consumption from a waterworks.
"Consumer's water system" means any water system located on the consumer's premises, supplied by or in any manner connected to a waterworks.
"Containment" means the safeguard against backflow into a waterworks from a consumer's water system by installing an appropriate backflow prevention assembly, backflow prevention device, or backflow elimination method at the service connection [ or downstream of the service connection but before any unprotected takeoffs ].
"Contaminant" means any objectionable or hazardous physical, chemical, biological, or radiological substance or matter in water.
"Conventional filtration treatment" means a series of processes including coagulation, flocculation, sedimentation, and filtration resulting in substantial particulate removal.
"Corrosion inhibitor" means a substance capable of reducing the corrosivity of water toward metal plumbing materials, especially lead and copper, by forming a protective film on the interior surface of those materials.
"Cross connection" "Cross-connection" means any connection or structural arrangement, direct or indirect, to the waterworks whereby actual or potential link, connection, or physical arrangement, direct or indirect, between used water, an auxiliary water system, or other source of contamination [ or pollution ] to the waterworks through which backflow can occur.
"CT" or "CTcalc" means the product of "residual disinfectant concentration" (C) in mg/L determined before or at the first customer, and the corresponding "disinfectant contact time" (T) in minutes (i.e., "C" x "T").
"Daily fluid intake" means the daily intake of water for drinking and culinary use and is defined as two liters.
"Dechlorination" means the partial or complete reduction of residual chlorine in water by any chemical or physical process at a waterworks with a treatment facility.
"Degree of hazard" means the level of health hazard, as derived from an evaluation of the potential risk to health and the adverse effect upon the waterworks.
"DBPPs" means disinfection byproduct precursors.
"DBPs" means disinfection byproducts.
"DCLS" means the Virginia Department of General Services, Division of Consolidated Laboratory Services.
"Department" means the Virginia Department of Health.
"DEQ" means the Virginia Department of Environmental Quality.
"Diatomaceous earth filtration" means a process resulting in substantial particulate removal in which (i) a precoat cake of diatomaceous earth filter media is deposited on a support membrane (septum), and (ii) while the water is filtered by passing through the cake on the septum, additional filter media known as body feed is continuously added to the feed water to maintain the permeability of the filter cake.
"Direct filtration" means a series of processes including coagulation and filtration but excluding sedimentation resulting in substantial particulate removal.
"Disinfectant" means any oxidant (including chlorine) that is chemical and physical agents, including chlorine, chlorine dioxide, chloramines, ozone, and UV light, added to water in any part of the treatment or distribution process for the purpose of killing or deactivating inactivating pathogenic organisms.
"Disinfectant contact time" ("T" in CT calculations) means the time in minutes that it takes for water to move from the point of disinfectant application to the point where residual disinfectant concentration ("C") is measured.
"Disinfection" means a process that inactivates or destroys pathogenic organisms in water by chemical oxidants or equivalent agents use of a disinfectant.
"Disinfection profile" means a summary of Giardia lamblia or virus inactivation through the water treatment plant.
"Distribution main" means a water main pipeline whose primary purpose is to provide treated convey drinking water to service connections.
"District engineer" means the employee assigned by the Commonwealth of Virginia, Department of Health, Office of Drinking Water to manage its regulatory activities in a geographical area of the state consisting of a state planning district or subunit of a state planning district.
"Domestic or other nondistribution system plumbing problem" means a coliform contamination problem in a waterworks with more than one service connection that is limited to the specific service connection from which the coliform positive sample was taken.
"Distribution system" means a network of pipelines and appurtenances by which a waterworks delivers drinking water to its consumers.
"DOC" means the dissolved organic carbon in a water sample.
"Double [ gate-double ] check valve assembly" [ or "double check detector backflow assembly" ] means [ an approved a backflow prevention ] assembly composed of two single independently acting check valves including tightly closing shutoff valves located at each end of the assembly and [ petcocks and test gauges for testing the watertightness of each check valve test cocks to facilitate testing of the assembly, used for low hazard situations ].
"DPOR" means the Virginia Department of Professional and Occupational Regulation.
"Drawdown" means the difference, measured vertically, between the static water level in the well and the water level during pumping.
"Dual sample set" means a set of two samples collected at the same time and same location, with one sample analyzed for TTHM and the other sample analyzed for HAA5. Dual sample sets are collected for the purposes of conducting an initial distribution system evaluation (IDSE) under 12VAC5-590-370 B 3 e (2) and determining compliance with the TTHM and HAA5 MCLs under 12VAC5-590-370 B 3 e (3).
"Effective corrosion inhibitor residual" means, for the purpose of 12VAC5-590-405 A 1 only, a concentration sufficient to form a passivating film on the interior walls of a pipe.
[ "EDR" means electrodialysis reversal. ]
"Enhanced coagulation" means the addition of sufficient coagulant for improved removal of disinfection byproduct precursors by conventional filtration treatment.
"Enhanced softening" means the improved removal of disinfection byproduct precursors by precipitative softening.
"Entry point" means the place where water from the source after application of any treatment is delivered to the distribution system. Where two or more sources are combined before distribution, the entry point is the location that is representative of the blended water following all treatment.
"Equivalent residential connection" means a volume of water used equal to a residential connection that is 400 gallons per day unless supportive data indicates otherwise.
"Exception" means an approved deviation from a "shall" criteria contained in Part III (12VAC5-590-640 et seq.) of this chapter.
"EPA" means the U.S. Environmental Protection Agency.
"Exemption" means a conditional waiver of allowing a waterworks that satisfies the criteria in 12VAC5-590-150 to deviate from a specific PMCL or treatment technique requirement that is granted to a specific the waterworks for a limited period of time.
"Filter profile" means a graphical representation of individual filter performance, based on continuous turbidity measurements or total particle counts versus time for an entire filter run, from startup start-up to backwash inclusively, that includes an assessment of filter performance while another filter is being backwashed.
"Filtration" means a process for removing particulate matter from water by passage through porous media.
"Finished water" means water that is introduced into the distribution system of a waterworks and is intended for distribution and consumption without further treatment, except as treatment is necessary to maintain water quality in the distribution system [ (e.g., booster disinfection). ], addition of corrosion control chemicals).
"First draw sample" means a one-liter sample of tap water, collected in accordance with 12VAC5-590-375 B 2, that has been standing in plumbing pipes at least six hours and is collected without flushing the tap.
"Flocculation" means a process to enhance agglomeration or collection of smaller floc particles into larger, more easily settleable particles through gentle stirring by hydraulic or mechanical means.
"Flowing stream" means a course of running water flowing in a definite channel.
"Free available chlorine" means that portion of the total residual chlorine residual remaining in water at the end of a specified contact period that will react chemically and biologically as hypochlorous acid or hypochlorite ion.
"GAC10" means granular activated carbon filter beds with an empty-bed contact time of 10 minutes based on average daily flow and a carbon reactivation frequency of every 180 days, except that the reactivation frequency for GAC10 used as a best available technology for compliance with 12VAC5-590-410 C 2 b (1) (b) shall be 120 days.
"GAC20" means granular activated carbon filter beds with an empty-bed contact time of 20 minutes based on average daily flow and a carbon reactivation frequency of every 240 days.
"Governmental entity" means the Commonwealth, a town, city, county, service authority, sanitary district, or any other governmental body established under the Code of Virginia, including departments, divisions, boards, or commissions.
"GAC" means granular activated carbon.
"Gross alpha particle activity" means the total radioactivity due to alpha particle emission as inferred from measurements on a dry sample.
"Gross beta particle activity" means the total radioactivity due to beta particle emission as inferred from measurements on a dry sample.
"Groundwater" means all water obtained from sources not classified as surface water (or surface water sources).
"Groundwater system" means any waterworks that uses groundwater as its source of supply; however, a waterworks that combines all its groundwater with surface water or with groundwater under the direct influence of surface water prior to before treatment is not a groundwater system. Groundwater systems include consecutive waterworks that receive finished groundwater from a wholesale waterworks potable water from another groundwater source.
"Groundwater under the direct influence of surface water" or "GUDI" means any water beneath the surface of the ground with (i) significant occurrence of insects or other macroorganisms, algae, or large-diameter pathogens such as Giardia lamblia, or Cryptosporidium. It also means or (ii) significant and relatively rapid shifts in water characteristics such as turbidity, temperature, conductivity, or pH that closely correlate to climatological or surface water conditions. The commissioner GUDI source determinations shall be made by the department in accordance with 12VAC5-590-430 will determine direct influence of surface water.
"GWMA" means the groundwater management area designation by the State Water Control Board.
"Haloacetic acids (five)" or "HAA5" means the sum of the concentrations in milligrams per liter of the haloacetic acid compounds (monochloroacetic acid, dichloroacetic acid, trichloroacetic acid, monobromoacetic acid, and dibromoacetic acid), rounded to two significant figures after addition acids, expressed in milligrams per liter (mg/L) as rounded to two significant figures. For the purpose of this chapter the HAA5 shall mean monochloroacetic acid, dichloroacetic acid, trichloroacetic acid, monobromoacetic acid, and dibromoacetic acid.
"Halogen" means one of the chemical elements chlorine, bromine, fluorine, astatine, or iodine.
"Health hazard" means any condition, device, or practice in a waterworks or its operation that creates, or may create, a danger to the health and well-being of the water consumer.
"Health regulations" means regulations that include all primary maximum contaminant levels, treatment technique requirements, and all operational regulations, the violation of which would jeopardize the public health.
"HPC" means the heterotrophic plate count of a bacterial population.
"Human consumption" means drinking, food preparation, dishwashing, bathing, showering, hand washing, teeth brushing, and maintaining oral hygiene.
"Hypochlorite" means a solution of water and some form of chlorine, usually sodium hypochlorite the ionic component from the disassociation of hypochlorous acid that performs the function of disinfection. It is the available active ingredient in liquid hypochlorite disinfectants such as sodium and calcium hypochlorite.
"Initial compliance period" means for all regulated contaminants, the initial compliance period is the first full three-year compliance period beginning at least 18 months after promulgation with the exception of waterworks with 150 or more service connections for contaminants listed at Table 2.3, VOC 19-21; Table 2.3, SOC 19-33; and antimony, beryllium, cyanide (as free cyanide), nickel, and thallium that shall begin January 1993 the compliance period in which chemical [ monitoring begins and radiological monitoring began, and it is represented by the first full three-year compliance period beginning at least 18 months after rule promulgation. It applies to inorganic, organic, and radionuclide contaminants listed in Tables 340.1, 340.2, and 340.4, respectively ].
"Interchangeable connection" means an arrangement or device that will allow alternate but not simultaneous use of two sources of water.
"Isolation" means the safeguard against backflow into a waterworks from a consumer's water system by installing an appropriate backflow prevention assembly or device or by installing a backflow elimination method at the sources of potential contamination in the consumer's water system. This is also called point-of-use isolation.
"Karst geology" means an area predominantly underlain by limestone, dolomite, or gypsum and characterized by rapid underground drainage. Such These areas often feature sinkholes, caverns, and sinking or disappearing creeks. In Virginia, this generally includes all that area west of the Blue Ridge and, in Southwest Virginia, east of the Cumberland Plateau.
"Lake/reservoir" "Lake or reservoir" means a natural or manmade man-made basin or hollow on the Earth's surface in which water collects or is stored that may or may not have a current or single direction of flow.
"Large waterworks" means, for the purposes of 12VAC5-590-375, 12VAC5-590-405, 12VAC5-590-530 F, and 12VAC5-590-550 D only, a waterworks that serves more than 50,000 persons.
"Lead free" means the following: 1. When (i) when used with respect to solders and flux, refers to solders and flux containing not more than 0.2% lead; 2. When and (ii) when used with respect to pipes, and pipe fittings, refers to pipes and pipe fittings containing not more than 8.0% lead; pipe fittings, plumbing fittings, and plumbing fixtures, refers to the weighted average of wetted surfaces of pipes, pipe fittings, plumbing fittings, and plumbing fixtures containing not more than 0.25% lead.
3. When used with respect to plumbing fittings and fixtures intended by the plumbing manufacturer to dispense water for human ingestion, refers to fittings and fixtures that are in compliance with standards established in accordance with 42 USC § 300g-6(e).
"Lead service line" means a service line pipeline made of lead that connects the water distribution main to the building inlet and any lead pigtail, gooseneck, or other fitting that is connected to such lead line the lead pipeline.
"Leakage" means the loss of potable water from the distribution system, up to the points of service connections, through breaks or defects in piping and piping appurtenances.
"Legionella" means a genus of bacteria, some species of which have caused cause a type of pneumonia called Legionnaires disease.
"Level 1 assessment" means an evaluation to identify the possible presence of sanitary defects, defects in distribution system coliform monitoring practices, and, when possible, the likely reason that the waterworks triggered the assessment.
"Level 2 assessment" means an evaluation to identify the possible presence of sanitary defects, defects in distribution system coliform monitoring practices, and, when possible, the likely reason that the waterworks triggered the assessment in a more comprehensive investigation than a Level 1 assessment.
"Liquid chlorine" means a liquefied, compressed chlorine gas as shipped in commerce.
"Locational running annual average" or "LRAA" means the average of sample analytical results for samples taken at a particular monitoring location during the previous four calendar quarters.
"Log inactivation (log removal)" means that a 99% reduction is a 2-log inactivation; a 99.9% reduction is a 3-log inactivation; a 99.99% reduction is a 4-log inactivation the inactivation of organisms expressed on a logarithmic scale. For example, a 99.9% inactivation is a 3-log inactivation; whereas a 99.99% inactivation is a 4-log inactivation.
"Manmade beta particle and photon emitters" means all radionuclides emitting beta particles and/or photons listed in the most current edition of "Maximum Permissible Body Burdens and Maximum Permissible Concentration of Radionuclides in Air or Water for Occupational Exposure," National Bureau of Standards Handbook 69, except the daughter products of thorium-232, uranium-235 and uranium-238.
"Log removal" means the removal of organisms expressed on a logarithmic scale. For example, a 99.9% is a 3-log removal; whereas a 99.99% removal is a 4-log removal.
"Maximum contaminant level" or "MCL" means the maximum permissible level of a contaminant in pure potable water that is delivered to any user consumer of a waterworks. MCLs are set as close to the MCLGs as feasible using the best available treatment technology BAT. MCLs may be either "primary" (PMCL), meaning based on health considerations, or "secondary" (SMCL), meaning based on aesthetic considerations.
"Maximum contaminant level goal" or "MCLG" means the maximum level of a contaminant in drinking water at which no known or anticipated adverse effect on the health of persons would occur [ and that allows an adequate margin of safety ]. [ Applying an adequate margin of safety to the MCLG allows the MCL to be set as the standard. ] Maximum contaminant level goals are nonenforceable health goals.
"Maximum daily water demand" means the rate of water usage during the day of maximum water use.
"Maximum residual disinfectant level" or "MRDL" means a level of a disinfectant added for water treatment that may not be exceeded at the consumer's tap without an unacceptable possibility of adverse health effects. For chlorine and chloramines, a waterworks is in compliance with the MRDL when the running annual average of monthly averages of samples taken in the distribution system, computed quarterly, is less than or equal to the MRDL. For chlorine dioxide, a waterworks is in compliance with the MRDL when daily samples are taken at the entrance to the distribution system and no two consecutive daily samples exceed the MRDL. MRDLs are enforceable in the same manner as maximum contaminant levels. There is convincing evidence that addition of a disinfectant is necessary for control of waterborne microbial contaminants. Notwithstanding the MRDLs listed in Table 2.12, operators may increase residual disinfectant levels of chlorine or chloramines (but not chlorine dioxide) in the distribution system to a level and for a time necessary to protect public health to address specific microbiological contamination problems caused by circumstances such as distribution line breaks, storm runoff events, source water contamination, or cross-connections.
"Maximum residual disinfectant level goal" or "MRDLG" means the maximum level of a disinfectant added for water treatment at which no known or anticipated adverse effect on the health of persons would occur, and that allows an adequate margin of safety. MRDLGs are nonenforceable health goals and do not reflect the benefit of the addition of the chemical for control of waterborne microbial contaminants.
"Maximum total trihalomethane potential" or "MTP" means the maximum concentration of total trihalomethanes (TTHMs) produced in a given water containing a residual disinfectant residual after seven days at a temperature of 25°C or above.
"Medium waterworks" means, for the purpose of 12VAC5-590-375 and 12VAC5-590-405 only, a waterworks that serves greater than 3,300 and less than or equal to 50,000 persons.
"Membrane filtration" means a pressure or vacuum-driven separation process in which particulate matter larger than one micrometer is rejected by an engineered barrier, primarily through a size exclusion mechanism, and that has a measurable removal efficiency of a target organism that can be verified through the application of a direct integrity test. This definition includes the common membrane technologies of microfiltration, ultrafiltration, nanofiltration, and reverse osmosis Included in this definition are the common membrane classifications of microfiltration (MF), ultrafiltration (UF), nanofiltration (NF), and reverse osmosis (RO).
"Membrane module" means the smallest component of a membrane unit in which a specific membrane surface area is housed in a device with a filtrate outlet.
"Membrane [ technologies technology ]" means [ those processes a process ] that [ use uses ] a permeable membrane to remove ions, molecules, or particles from the process stream, such as MF, UF, NF, RO, and [ EDR electrodialysis reversal (EDR) ].
"Membrane unit" means a group of membrane modules that share common valving that allows the unit to be isolated from the rest of the system for the purpose of integrity testing or other maintenance.
"Method detection limit" or "MDL" means the minimum concentration of a substance that can be measured and reported with 99% confidence that the analyte concentration is greater than zero and is determined from analysis of a sample in a given matrix containing the analyte.
"Microfiltration" or "MF" means a pressure-driven membrane technology that separates particles, based on the pore-size rating of the membrane, from a feed stream by using a sieving mechanism. Typically, MF can remove particles down to 0.1 micrometer in size.
"Most probable number" or "MPN" means that the density or number of organisms per unit volume that, in accordance with statistical theory, would be more likely than any other number to yield the observed test result or that would yield the observed test result with the greatest frequency, expressed as density of organisms per 100 milliliters. Results are computed from the number of positive findings of coliform-group organisms resulting from multiple-portion decimal-dilution plantings most likely to be present in a water sample and obtained from method-specific statistical MPN tables.
"MPA" means the microscopic particulate analysis method approved by EPA for use in the determination of whether a groundwater is under the influence of surface water.
"Nanofiltration" or "NF" means a pressure-driven membrane technology designed to remove multivalent ions ("softening") and other constituents based on the pore size, which ranges from one to 10 nanometers. Nanofiltration membranes typically operate under a pressure range of 600 to 1100 psi.
[ "Nondetected" or "ND" means a term typically used by laboratories to express the absence of an analyte in a test sample. ]
"Noncommunity waterworks" means a waterworks that is not a community waterworks, but operates at least 60 days out of the year.
"Nonpotable water" means water not classified as pure water.
"Nontransient noncommunity waterworks" or "NTNC" means a waterworks that is not a community waterworks and that regularly serves at least 25 of the same persons over six months out of the year. When used in the context of an NTNC, "regularly serves" means four or more hours per day, for four or more days per week, for 26 or more weeks per year.
"NSF" means [ NSF International, formerly known as ] the National Sanitation Foundation. [ NSF collaborates with ANSI and Canadian authorities on drinking water standards development (NSF/ANSI/CAN). ]
"Office" or "ODW" means the Commonwealth of Virginia, Department of Health, Office of Drinking Water.
"One hundred year flood level" elevation" or "100-year flood elevation" means the flood elevation that will, over a long period of time, be equaled or exceeded on the average once every 100 years that has a 1.0% probability of being equaled or exceeded in any given year.
"Operating staff" means individuals employed or appointed by an owner to work at a waterworks. Included in this definition are operators, whether or not the operator's license is appropriate for the classification and category of the waterworks, and unlicensed individuals.
"Operator" means any individual with the requisite skills, employed or appointed by any owner, and who is designated by such the owner to be the person in responsible charge, such as having full responsibility for the waterworks operations and any subordinate operating staff. The individual may be a supervisor, a shift operator, or a substitute in charge, and whose have duties include including testing or evaluation to control waterworks operations. Not included in this definition are superintendents or directors of public works, city engineers, or other municipal or industrial officials whose duties do not include the actual operation or direct supervision of waterworks.
"Optimal corrosion control treatment" means the corrosion control treatment that minimizes the lead and copper concentrations at users' consumers' taps while ensuring that the treatment does not cause the waterworks to violate any other section of this chapter.
"Optimum fluoride ion concentration" means that fluoride ion concentration recommended by the U.S. Public Health Service for protection from dental caries.
"Owner" or "water purveyor" means an individual, group of individuals, partnership, firm, association, institution, corporation, governmental entity, or the federal government that supplies or proposes to supply water to any person within this state the Commonwealth from or by means of any waterworks (see Article 2 (§ 32.1-167 et seq.) of Chapter 6 of Title 32.1 of the Code of Virginia).
"PAC" means powdered activated carbon.
"PCBs" means polychlorinated biphenyls.
"PER" means a preliminary engineering report.
"Permit" means an authorization granted by the commissioner to construct or operate a waterworks.
"Permitted capacity" means the limiting hydraulic capability of the waterworks, taking into consideration the source water capacity, treatment facilities, finished water storage, delivery, and distribution system.
"Person" means any individual, corporation, partnership, association, cooperative, limited liability company, trust, joint venture, government, political subdivision, or any other legal or commercial entity and any successor, representative, agent, or instrumentality thereof.
"pH" means the negative logarithm of the hydrogen ion concentration of an aqueous solution.
"Physical disconnection" means the removal or absence of pipes, fittings, or fixtures that connect a waterworks directly or indirectly to any other water system.
"Picocurie" or "pCi" means that quantity of radioactive material producing 2.22 nuclear transformations per minute.
"Plant intake" means the works or structures at the head of a conduit through which water is diverted from a source (e.g., river or lake) into the treatment plant.
"PMCL" means the [ same as "maximum contaminant level." primary maximum contaminant level of a contaminant based on health considerations. ]
"Point of disinfectant application" means the point where the disinfectant is applied and water downstream of that point is not subject to recontamination by surface water runoff.
"Point-of-entry treatment device" or "POE device" means a treatment device applied to the water entering a house or building for the purpose of reducing contaminants in the water distributed throughout the house or building.
"Point-of-use treatment device" or "POU device" means a treatment device applied to a single tap for the purpose of reducing contaminants in the water at that one tap.
"Pollution" means the presence of any foreign substance (chemical, physical, radiological, or biological) in water that tends to degrade its quality so as to constitute an unnecessary risk to human health or impair the usefulness of the water.
"Pollution hazard" means a condition through which an aesthetically objectionable or degrading material may enter the waterworks or a consumer's water system.
"Postchlorination" means the application of chlorine to water subsequent to treatment.
"Potable water" – see "Pure means the same as "pure water."
"Practical quantitation level" or "PQL" means the lowest level achievable by good laboratories within specified limits during routine laboratory operating conditions that can be reliably measured within specified limits of precision and accuracy during routine laboratory conditions.
"Prechlorination" means the application of chlorine to water prior to before filtration.
"Presedimentation" means a preliminary treatment process used to remove gravel, sand, and other particulate material from the source water through settling before the water enters the primary clarification and filtration processes in a water treatment plant.
"Pressure vacuum breaker assembly" means [ an a backflow prevention ] assembly designed to prevent backsiphonage and used for [ high-hazard high hazard ] or [ low-hazard low hazard ] situations, composed of an independently operating, spring-loaded check valve; an independently operating, spring-loaded air-inlet valve; and tightly closing shutoff valves located at each end of the assembly and fitted with properly located test cocks [ to facilitate testing of the assembly ].
"Primary disinfection" means disinfection to achieve a desired level of inactivation of targeted pathogenic organisms in water by chemical or physical agents as an integral part of the treatment process.
"Process fluids" means any fluid or solution that may be chemically, biologically, or otherwise contaminated or polluted that would constitute a health, pollutional environmental, or system hazard if introduced into the waterworks. This includes, but is not limited to: (i) polluted or contaminated water; (ii) used waters; (iii) cooling waters; (iv) contaminated natural waters taken from wells, lakes or reservoirs, streams, or irrigation systems; (v) chemicals in solution or suspension; or (vi) oils, gases, acids, alkalis, and other liquid and gaseous fluid used in industrial or other processes.
1. Polluted or contaminated water;
2. Process waters;
3. Used waters, originating from the waterworks that may have deteriorated in sanitary quality;
4. Cooling waters;
5. Contaminated natural waters taken from wells, lakes, streams, or irrigation systems;
6. Chemicals in solution or suspension; and
7. Oils, gases, acids, alkalis, and other liquid and gaseous fluid used in industrial or other processes, or for firefighting purposes.
"Process water" means water used for dissolving dry chemicals; diluting liquid chemicals; and operating chemical feeders, treatment facilities, or equipment.
"Project documents" means the engineer's report, design criteria, preliminary and final plans, specifications, and procurement documents for the construction of new waterworks or modifications to existing waterworks.
"Pure water" means water fit for human consumption that is (i) sanitary and normally free of minerals, organic substances, and toxic agents in excess of reasonable amounts and (ii) adequate in quantity and quality for the minimum health requirements of the persons served (see Article 2 (§ 32.1-167 et seq.) of Chapter 6 of Title 32.1 of the Code of Virginia).
"Raw water main" means a water main that conveys untreated water from a source to a treatment facility.
"QCRV" means the quality control release value used in challenge tests of microfiltration (MF) and ultrafiltration (UF) membrane filters.
"RAA" means running annual average.
"Reduced pressure principle backflow prevention device assembly" or [ "reduced pressure zone backflow prevention assembly" or ] "RPZ device assembly" means a device containing a minimum of two independently acting check valves together with an automatically operated pressure differential relief valve located between the two check valves an assembly designed to prevent backsiphonage or backpressure backflow [ and ] used for high or low hazard situations, composed of two independently operating spring-loaded check valves together with an independent, hydraulically operating pressure differential relief valve located between the two check valves. During normal flow and at the cessation of normal flow, the pressure between these two checks shall be less than the supply pressure. In case of leakage of either check valve, the differential relief valve, by discharging to the atmosphere, shall operate to maintain the pressure between the check valves at less than the supply pressure. The unit assembly shall include tightly closing shutoff valves located at each end of the device, RPZ assembly and each device shall be fitted with properly located test cocks [ to facilitate testing of the assembly ]. These devices shall be of the approved type.
"REM" means the unit of dose equivalent from ionizing radiation to the total body or any internal organ or organ system. A millirem (MREM) (mrem) is 1/1000 of a an REM.
"Repeat compliance period" means any subsequent compliance period after the initial compliance period.
"Residual disinfectant concentration" ("C" in CT Calculations) means the concentration of disinfectant measured in mg/L in a representative sample of water.
"Responsible charge" means designation by the owner of any individual to have duty and authority to operate or modify the operation of waterworks processes.
"Sanitary facilities" means piping and fixtures, such as sinks, lavatories, showers, and toilets, supplied with potable water and drained by wastewater piping.
"Reverse osmosis" or "RO" means a membrane technology designed to remove salts, low-molecular weight solutes, and all other constituents up to 0.0001 micron in size by applying a pressure in excess of osmotic pressure to force water through a semi-permeable membrane from a region of high solution concentration to a region of lower solution concentration.
"Sanitary defect" means a defect that could provide a pathway of entry for microbial contamination into the distribution system or that is indicative of a failure or imminent failure in a protective barrier that is already in place.
"Sanitary survey" means an evaluation conducted by ODW the department of a waterworks' water supply, facilities, equipment, operation, maintenance, monitoring records, and overall management of a waterworks to ensure the provision of pure potable water.
"SDWA" means the Safe Drinking Water Act (42 USC § 300f et seq.) and its amendments.
"Seasonal waterworks" means a noncommunity waterworks that is not operated as a waterworks on a year-round basis, and starts up and shuts down at the beginning and end of each operating season.
"Secondary water source" means any approved water source, other than a waterworks' primary source, connected to or available to that waterworks for emergency or other nonregular use.
"Secondary disinfection" means disinfection by chemical oxidants or equivalent agents applied at the entry point or in the distribution system to provide a residual disinfectant in water to maintain water quality and safeguard against chance contamination from permeation, leaching, intrusion, regrowth, or biofilms.
"Sedimentation" means a process for removal of solids before filtration by gravity or separation.
"Service connection" means the point of delivery of finished water to a customer's building service line as follows: from a waterworks to a consumer's water system, fire protection system, [ or ] irrigation system [ , ] and to all other points where finished water is delivered through the distribution system to a consumer. [ Generally, the service connection occurs at the water meter, or at the distribution main if no water meter is installed, or in the case of an owner of both the waterworks and the building supplied, the point of entry into the building. ] Service connections may be permanent, temporary, or emergency.
1. If a meter is installed, the service connection is the downstream side of the meter;
2. If a meter is not installed, the service connection is the point of connection to the waterworks;
3. When the water purveyor is also the building owner, the service connection is the entry point to the building.
"Service line sample" means a one-liter sample of water, collected in accordance with 12VAC5-590-375 B 2 c, that has been standing for at least six hours in a service line.
[ "Service line" means the pipeline or service pipe between the service connection and the building connection. ]
"Sewer" means any pipe or conduit used to convey sanitary sewage, stormwater, or industrial waste streams. Combined sewers convey both stormwater and sanitary sewage.
"Significant deficiency" means any defect in a waterworks' design, operation, maintenance, or administration, as well as the failure or malfunction of any waterworks component, that may cause, or has the potential to cause, an unacceptable risk to health or could affect the reliable delivery of pure potable water to consumers.
"Single-family structure" means, for the purpose of 12VAC5-590-375 B only, a building constructed as a single-family residence that is currently used as either a residence or a place of business.
"Site visit" means a tour of a waterworks by [ the ] department [ staff ] or other authorized persons for purposes including assessing and documenting its physical condition, operations, and compliance activities.
"Slow sand filtration" means a process involving passage of raw source water through a bed of sand at low velocity (generally less than 0.4 m/h), resulting in substantial particulate removal by physical and biological mechanisms.
"Small waterworks" means, for the purpose of 12VAC5-590-375, 12VAC5-590-405, 12VAC5-590-530 F and 12VAC5-590-550 D only, a waterworks that serves 3,300 persons or fewer.
"Standard sample" means that portion of finished drinking water that is examined for the presence of coliform bacteria.
"SMCL" means the [ same as "maximum contaminant level." secondary maximum contaminant level of a contaminant. SMCLs are based on aesthetic qualities related to the public acceptance of drinking water. ]
"SOP" means standard operating procedure.
"Source water" means water as it is pumped or otherwise withdrawn from a well, spring, stream, lake or reservoir, or any body of surface water (natural or impounded), and before any treatment.
"Supervisory control and data acquisition" or "SCADA" means a computer-controlled system used by a waterworks to monitor its operations. Typical design features may be specific to individual waterworks and include alarm, response, control, and data acquisition.
"Surface water" means all water open to the atmosphere and subject to surface runoff.
"SUVA" means specific ultraviolet absorption at 254 nanometers (nm), an indicator of the humic content of the water. It is a calculated parameter obtained by dividing a sample's ultraviolet absorption at a wavelength of 254 nm (UV254) [ (in m-1) (in m-1) ] by its concentration of dissolved organic carbon (DOC) DOC (in mg/L).
"Synthetic organic chemicals" or "SOC" means one of the family of organic manmade compounds generally utilized for agriculture or industrial purposes.
"Synthetic organic chemical" or "SOC" means a man-made organic compound, generally utilized for agriculture or industrial purposes. Table 340.2 lists SOCs regulated as contaminants.
"System hazard" means a condition posing an actual, or threat of, damage to the physical properties of the waterworks or a consumer's water system.
"Terminal reservoir" means an impoundment providing end storage of water prior to treatment.
"TDS" means total dissolved solids.
"TMF" means the technical, managerial, and financial capabilities to operate and maintain a waterworks.
"Too numerous to count" or "TNTC" means that the total number of bacterial colonies exceeds 200 on a 47-mm diameter membrane filter used for coliform detection.
"Total effective storage volume" means the volume available to store water in distribution reservoirs measured as the difference between the reservoir's overflow elevation and the minimum storage elevation. The minimum storage elevation is that elevation of water in the reservoir that can provide a minimum pressure of 20 psi at a flow as determined in 12VAC5-590-690 C to the highest elevation served within that reservoir's service area under systemwide maximum daily water demand.
"Total organic carbon" or "TOC" means total organic carbon in mg/L [ miiligrams milligrams ] per liter (mg/l) measured using heat, oxygen, ultraviolet irradiation, chemical oxidants, or combinations of these oxidants that convert organic carbon to carbon dioxide, rounded to two significant figures.
"Total trihalomethanes" or "TTHM" means the sum of the concentrations of the trihalomethanes (THMs) expressed in milligrams per liter (mg/L) and rounded to two significant figures. For the purpose of these regulations, the TTHMs this chapter, TTHM shall mean trichloromethane (chloroform), dibromochloromethane, bromodichloromethane, and tribromomethane (bromoform).
"Transient noncommunity waterworks" or "TNC" means a noncommunity waterworks that is not a nontransient noncommunity waterworks (NTNC). A TNC serves at least 25 persons daily for at least 60 days out of the year.
"Transmission main" means a water main whose primary purpose is to move significant quantities of treated water among service areas.
"Treatment" means any process that changes the chemical, physical, radiological, or bacteriological quality of water.
"Treatment technique requirement" or "TT" means a requirement that specifies for a contaminant a specific treatment technique(s) technology or process demonstrated to the satisfaction of the division department to lead to a reduction in the level of such a specific contaminant sufficient to comply with these regulations this chapter.
"Triggered source water monitoring" means monitoring required of any groundwater system as a result of a total coliform-positive sample in the distribution system.
"Trihalomethane" or "THM" means one of the family of organic compounds, named as derivatives of methane, wherein three of the four hydrogen atoms in methane are each substituted by a halogen atom in the molecular structure.
"Two-stage lime softening" means a process in which chemical addition and hardness precipitation occur in each of two distinct unit clarification processes in series prior to filtration.
"Ultrafiltration" or "UF" means a membrane technology designed to remove particles up to 0.01 micron in size.
"Unconsolidated" means loose sediment that has not been compacted, cemented, lithified, or metamorphosed into rock. Sediment may be derived from a sedimentary-type, igneous-type, metamorphic-type rock, which includes clay, silt, sand, gravel, and mixtures of these particle types.
"Uncovered finished water storage facility" means a tank, reservoir, or other facility used to store water that will undergo no further treatment to reduce microbial pathogens (except residual disinfection) and is directly open to the atmosphere.
"Unregulated contaminant" or "UC" means a contaminant for which a monitoring requirement has been established, but for which no MCL or treatment technique requirement has been established.
"USBC" means the Uniform Statewide Building Code (13VAC5-63).
"Used water" means any water supplied by a water purveyor from the waterworks to a consumer's water system after it has passed through the service connection and is no longer under the control of the owner.
"UV" means ultraviolet.
"Variance" means a conditional waiver of a specific regulation that is granted to a specific waterworks allowing a waterworks that satisfies the criteria in 12VAC5-590-140 to provide drinking water that does not fully comply with this chapter. A PMCL variance is a variance to a primary maximum contaminant level, or a treatment technique requirement. An operational variance is a variance to an operational regulation or a secondary maximum contaminant level SMCL. Variances for monitoring, reporting and public notification requirements will not be granted.
"Virus" means a microbe virus of fecal origin that is infectious to humans by waterborne transmission and must be preemptively inactivated through disinfection before human consumption.
"Volatile synthetic organic chemical" or "VOC" means one of the family of manmade organic compounds generally characterized by low molecular weight and rapid vaporization at relatively low temperatures or pressures.
"Volatile organic chemical" or "VOC" means an organic compound generally characterized by its low molecular weight and its tendency to vaporize rapidly at relatively low temperatures and pressures. Table 340.2 lists VOCs regulated as contaminants.
"VOSH" means the Virginia Occupational Safety and Health program.
"Waiver" means permission from the department to deviate from the monitoring and reporting requirements in this chapter for a specific contaminant.
"Waterborne disease outbreak" means the significant occurrence of acute infectious illness, epidemiologically associated with the ingestion of water from a waterworks that is deficient in treatment, as determined by the commissioner or the State Epidemiologist.
"Water purveyor" (same as owner).
"Water supply" means the source of water that shall have been taken into a waterworks from all including wells, streams, springs, lakes or reservoirs, and other bodies of surface waters (natural or impounded), and the tributaries thereto, and all impounded groundwater, but the. The term "water supply" shall not include any waters above the point of intake of such the waterworks (see Article 2 (§ 32.1-167 et seq.) of Chapter 6 of Title 32.1 of the Code of Virginia).
"Water supply main" or "main" means any water supply pipeline that is part of a waterworks distribution system.
"Water Well Completion Report" means a report form published by the State Water Control Board entitled "Water Well Completion Report," which requests specific information pertaining to the ownership, driller, location, geological formations penetrated, water quantity and quality encountered as well as construction of water wells. The form is to be completed by the well driller.
"Water treatment plant" means that portion of a waterworks intended specifically for water treatment; it may include, among other operations, coagulation, sedimentation, filtration, and disinfection.
"Waterworks" means a system that serves piped water for human consumption to at least 15 service connections or 25 or more individuals for at least 60 days out of the year. "Waterworks" includes all structures, equipment, and appurtenances used in the storage, collection, purification, treatment, and distribution of pure potable water except the piping and fixtures inside the building where such water is delivered (see Article 2 (§ 32.1-167 et seq.) of Chapter 6 of Title 32.1 of the Code of Virginia).
"Waterworks with a single service connection" means a waterworks that supplies drinking water to consumers via a single service line.
"Waterworks business operation plan" means the same as "comprehensive business plan."
"Wholesale waterworks" means a waterworks that treats source water as necessary to produce finished potable water and then delivers some or all of that finished potable water to another waterworks. Delivery may be through a direct connection or through the distribution system of one or more consecutive waterworks.
B. As used in this chapter, the following units of measurement shall use the abbreviations as shown in this subsection:
C – degrees Celsius
CU – color units
ft2 – square feet of area
ft/min – feet per minute
ft/sec – feet per second
gpd – gallons per day
gpd/ft2 – gallons per day per square foot
gpm – gallons per minute
gpm/ft – gallons per minute per foot
gpm/ft2 – gallons per minute per square foot
in – inches
lb – pounds
lb/day – pounds per day
lb/ft2 – pounds per square foot
MFL – million fibers per liter
MGD – million gallons per day
mg/L – milligrams per liter
min – minutes
mJ/cm2 – millijoules per square centimeter
mrem – millirem
nm – nanometer (10-9 meter)
NTU – nephelometric turbidity units
pCi – picocuries
pCi/L – picocuries per liter
ppb – parts per billion, or micrograms per liter (μg/L)
ppm – parts per million, or milligrams per liter (mg/L)
ppq – parts per quadrillion, or pictograms per liter (pq/L)
ppt – parts per trillion, or nanograms per liter (ng/L)
psi – pounds per square inch
psig – pounds per square inch gauge
scfm/ft2 – standard cubic feet per minute per square foot
µm – micrometers (10-6 meter or microns)
µg/L – micrograms per liter
µS/cm – microSiemens per centimeter
W/m2 – Watts per square meter
Article 2
General Information
12VAC5-590-20. Authority for regulations. (Repealed.)
Article 2 (§ 32.1-5 et seq.) of Chapter 1 of Title 32.1 of the Code of Virginia provides that the State Board of Health has the duty to protect the public health and to ensure that all water supplies destined for public consumption be pure water. In order to discharge that duty, the board is empowered to supervise and regulate all waterworks and water supplies within the state (see Article 2 of Chapter 1 of Title 32.1 of the Code of Virginia).
12VAC5-590-30. Purpose of regulations. (Repealed.)
These regulations have been promulgated by the board to: 1. Ensure that all water supplies destined for public consumption be pure water; 2. Guide the commissioner in his determination of whether a permit for a public water supply or waterworks should be issued; and 3. Assist the owner or his authorized engineer in the preparation of an application, plans, specifications, reports and other data.
12VAC5-590-35. Delegation of authority.
The commissioner, or the commissioner's designee, may perform any act of the board provided under this chapter, except as limited by § 32.1-20 of the Code of Virginia.
12VAC5-590-40. Administration of regulations this chapter.
These regulations are administered by the following parties:
1. State Board of Health, which has responsibility A. The board is responsible for promulgating, amending, and repealing regulations which to ensure a supply of pure potable water.
2. State Health Commissioner, who is the executive officer B. The commissioner is vested with all the authority of the State Board of Health with the authority of the board when it is not in session, and subject to such rules and regulations as may be prescribed by the board.
3.Division of Water Supply Engineering, which C. The department is designated as the primary reviewing agent of the board for the purpose of administering this chapter. It examines and passes upon the technical aspects of all applications and plans for waterworks projects prior to the before drafting of a permit for final approval by the State Health Commissioner commissioner. It also has primary responsibility for monitoring waterworks operations to ensure that water supplied to the public is pure consumers is potable water.
4. Central and field offices, which are maintained by the division, the central office is located in Richmond, Virginia. The Office of Water Programs maintains six field offices which are responsible for activities of the division within their service areas. Applications for waterworks permits should be submitted to the appropriate field office. The addresses of the field offices and a description of the areas that they serve are listed in Appendix C.
5. Waterworks Advisory Committee, which shall be appointed by the commissioner, shall consist of thirteen appointed members and three ex officio members specified below. The commissioner shall appoint to the Waterworks Advisory Committee one individual each from the following: a member of the Virginia Section American Water Works Association; a member of the Virginia Society of Professional Engineers; a member of the Virginia Water Well Association, Inc.; a member of the Consulting Engineers Council; a water treatment plant operator having a valid license of the highest classification in waterworks issued by the State Board for Waterworks and Wastewater Works Operators; a faculty member of a state university or college whose principal field of teaching is Environmental Engineering; a community waterworks owner; a nontransient noncommunity (NTNC) representative; a representative from Virginia Rural Water Association; a representative from Virginia Water Projects, Inc.; a representative from the Virginia Municipal League; a representative from the Virginia Association of Counties; and a citizen representative. Ex officio members shall consist of the Director, Office of Water Programs, who shall act as chairman; Director, Division of Water Supply Engineering; and Director, Division of Consolidated Laboratory Services or their designees.
Appointed members shall serve at the discretion of the commissioner with staggered terms being of three years in duration. The Waterworks Advisory Committee shall make recommendations to the commissioner regarding waterworks and water supply policies, procedures and programs of the division.
12VAC5-590-45. Waterworks Advisory Committee.
A. A Waterworks Advisory Committee (WAC) shall be formed by the commissioner to [ peer ] review [ and make recommendations regarding ] the regulatory, policy, and legislative aspects of the department's authorities. [ Committee WAC ] members shall consist of industry professionals employed outside the department with longstanding expertise or vested interest in waterworks operations and represent a diverse group of stakeholders. Members shall be experts in the fields of water treatment technologies, public health, water quality, economics, environmental science, public utilities, community development, or industry regulations. A minimum of nine persons shall be appointed to the committee by the commissioner.
B. The WAC will convene at least quarterly.
C. WAC meetings will be considered public meetings. Notice of scheduled meetings will be posted on the Virginia Regulatory Town Hall at least [ seven three ] working days before the date of the meeting. Meeting minutes will be posted to the Virginia Regulatory Town Hall within 10 working days after the meeting.
D. Each member of the WAC shall hold office for a term of three years, except that:
1. With approval by the commissioner, members are eligible for reappointment to consecutive terms.
2. Each member of the WAC serves at the pleasure of the commissioner.
E. The commissioner shall appoint the chair of the WAC.
F. The WAC shall have a [ member of the ] department [ staff member ] serve as secretary.
12VAC5-590-50. Application of [ regulations this chapter ] to waterworks and water supplies in operation or planned prior to before [ the effective date of the regulations June 23, 2021 ].
Waterworks and water supplies which were in operation prior to the effective date of the regulations may continue operation if they comply with the operational regulations set forth in Part II. Operation permits, which will be in addition to all permits previously received, will be issued to such waterworks as soon as practicable after the effective date of these regulations.
A. Waterworks and water supplies unable to comply with Part II of this chapter may be issued the appropriate variances and/or exemptions in conjunction with the operation permit to allow continued operation during the period of adjustment. Any variances and/or exemptions will be issued in accordance with the procedures contained in Article 3 of Part I of this chapter The owner shall comply with Part II [ (12VAC5-540-340 et seq.) (12VAC5-590-340 et seq.) ] of this chapter unless a variance or exemption is issued by the commissioner.
B. Compliance with design criteria set forth in Parts Part III and IV of this chapter is necessary for waterworks modification limited to modifications to existing waterworks and for all construction of new waterworks commenced after the effective date of these revised regulations [ (insert effective date of this chapter) June 23, 2021 ]. Portions of waterworks not being modified are not required to comply with the design criteria of Part III (12VAC5-590-640 et seq.). Waterworks construction or modification is deemed to be commenced for purposes of this section upon receipt of final plans and specifications by the field office issuance of the construction permit.
C. Compliance with the requirements set forth in Parts Part III and IV of this chapter including those for materials, construction methods, and disinfection, etc., is necessary for all repairs to pipes, tanks, pumps, and appurtenances which that are part of a waterworks.
D. Volatile Synthetic Organic Chemicals (VOCs) and Unregulated Contaminants (UCs) Regulations are effective immediately for those community and NTNC waterworks which serve more than 10,000 persons. The VOC and UC regulations are effective immediately for community and NTNC waterworks serving 3,300 to 10,000 persons. The VOC and UC regulations become effective on January 1, 1991, for community and NTNC waterworks serving less than 3,300 persons. (See Table 2.7.)
E. The Lead and Copper Regulations establish a treatment technique that includes requirements for corrosion control treatment, water supply (source water) treatment, lead service line replacement, and public education. These requirements are triggered, in some cases, by lead and copper action levels measured in samples collected at consumers' taps. Unless otherwise indicated, each of the provisions of 12VAC5-590-375, 12VAC5-590-405, 12VAC5-590-530 F and 12VAC5-590-550 D applies to community waterworks and nontransient noncommunity waterworks. The requirements set forth in 12VAC5-590-375, 12VAC5-590-530 D and 12VAC5-590-550 D shall take effect on July 7, 1991.
12VAC5-590-55. Relationship of this chapter to the Uniform Statewide Building Code.
A. This chapter governs waterworks facilities from any source water to all service connections.
B. In accordance with § 36-98 of the Code of Virginia and the USBC, the USBC governs the construction of buildings and structures, including plumbing systems and backflow prevention [ methods ]. The USBC also governs the water service piping from the service connection to a building or structure.
C. Notwithstanding subsections A and B of this section, this chapter shall govern:
1. Water treatment, storage, pumping facilities, and water piping that are part of a waterworks and housed in any building or structure; and
2. Backflow prevention assemblies or elimination methods, or both, installed for containment and located downstream from the service connection, including where located in any building or structure.
Article 3
Procedures
12VAC5-590-60. Compliance with the Administrative Process Act. (Repealed.)
The provisions of the Administrative Process Act (Chapter 1.1:1 of Title 9) and Title 32.1 of the Code of Virginia govern this chapter. All procedures outlined below are in addition to, or in compliance with, the requirements of that Act.
12VAC5-590-70. Powers and procedures.
The board reserves the right to authorize utilize any lawful procedure for the enforcement of this chapter that is consistent with the provisions set forth herein and the provisions of Title 32.1 of the Code of Virginia.
12VAC5-590-80. Procedure. (Repealed.)
Regulations for the operations, construction, or modification of a waterworks or water supply are established, amended, or repealed only in accordance with the Administrative Process Act.
12VAC5-590-100. Exception; emergency regulations.
If the establishment of a regulation is necessary for the preservation of public health, safety, or welfare to meet any emergency not provided for by this chapter, the board or commissioner acting on behalf of the board when it is not in session may immediately promulgate and adopt the necessary regulation by complying with the procedures set forth in either § 2.2-4011 or § 32.1-13 of the Code of Virginia.
12VAC5-590-110. Enforcement.
All waterworks must be operated in compliance with the requirements as set forth in this chapter as follows:
1. A. Notice. Whenever the commissioner, his appointed representative, or the division department has reason to believe that a violation of Title 32.1 or of the Code of Virginia or of any section of this chapter has may have occurred or is may be occurring, the division department shall so notify the alleged violator. Such The notice shall (i) be in writing shall; (ii) cite the statute, regulation or regulations that are allegedly being violated, and shall; (iii) state the facts which that form the basis for believing that the violation has may have occurred or is may be occurring; and (iv) include information on the process for obtaining a final decision or fact finding from the department on whether or not a violation has occurred. A notice of violation This notification is not an official finding, case decision, or adjudication but may be accompanied by include a request that certain to the owner to respond timely and to take specific corrective action be taken by a stated deadline.
2. B. Orders. Pursuant to § 32.1-26 of the Code of Virginia, the commissioner board may issue orders to require any owner to comply with the provisions of Title 32.1 of the Code of Virginia or this chapter any law administered by it, the commissioner, or the department; any regulations promulgated by the board, including any section of this chapter; or any case decision of the board or commissioner. The order shall be signed by the commissioner and commissioner, acting on behalf of the board when it is not in session, will sign the order, and the order may require:
a. 1. The immediate cessation or correction of the violation;
b. 2. The acquisition or use of additional equipment, supplies, or personnel to ensure that the violation does not recur;
c. 3. The submission of a plan to prevent future violations;
d. 4. The submission of an application for a variance or exemption;
e. 5. Any other corrective action deemed necessary for proper compliance with the this chapter; or
f. Division review 6. An evaluation and approval, if appropriate, of the required submissions, if appropriate.
3. C. Compliance with effective orders and this chapter. The commissioner may act as the agent of the board to enforce all effective orders and this chapter. Should any owner fail to comply with any effective order or this chapter, the commissioner may:
a. 1. Institute a an administrative proceeding to revoke the owner's permit in accordance with 12VAC5-590-320 and § 32.1-174 of the Code of Virginia or other appropriate administrative remedies;
b. Apply to an appropriate court for an injunction or other legal process to prevent or stop any practice in violation of the order;
c. 2. Request attorney for the Commonwealth to bring a criminal action criminal prosecution by a Commonwealth's attorney with the appropriate jurisdiction in accordance with § 32.1-27 of the Code of Virginia;
d. 3. Request civil action by the Attorney General to bring an action for impose a civil penalty, injunction seek injunctive relief, or other appropriate remedy legal remedies pursuant to §§ 32.1-27 and 32.1-176 of the Code of Virginia; or
e. 4. Do any combination of the above subdivision C 1, C 2, or C 3 of this section.
4. D. Special order. Pursuant to § 32.1-175.01 of the Code of Virginia, the commissioner may, after an informal fact-finding proceeding held in accordance with § 2.2-4019 of the Code of Virginia, issue a special order that may include a civil penalty against an owner who violates the Public Water Supplies Law, §§ 32.1-167 through 32.1-176 of the Code of Virginia, this chapter, or any order of the board.
E. Graduated enforcement actions. Nothing in this section shall prevent the commissioner or the division from taking action prior to issuing an order or department from making efforts to obtain voluntary compliance through conference, warning, or other appropriate means before issuance of an order, instituting an administrative proceeding, or requesting an action by a Commonwealth's Attorney or the Attorney General.
5. Hearing as a matter of right (see 12VAC5-590-180).
12VAC5-590-115. Administrative proceedings.
A. Types of administrative proceedings. Administrative proceedings before the board, the commissioner, or the commissioner's designee, shall include the following forms depending upon the nature of the controversy and the interests of the named party involved.
1. An informal fact-finding proceeding is an informal conference between the department [ staff ] and the named party held in accordance with § 2.2-4019 of the Code of Virginia.
2. A formal hearing is an adjudicatory proceeding before the commissioner or a designated hearing officer held in accordance with § 2.2-4020 of the Code of Virginia.
B. Request for administrative proceeding. The named party may request an administrative proceeding by sending a request in writing to the department.
C. Administrative proceeding as a matter of right. The named party whose rights, duties, or privileges have been or may be affected by any action or inaction of the board, commissioner, or department in the administration of this chapter, has a right to both an informal fact-finding proceeding and a formal hearing; however, the commissioner reserves the right to require participation in an informal fact-finding proceeding before granting the request for a formal hearing.
12VAC5-590-120. Emergency Orders orders.
A. The commissioner may, pursuant to § 32.1-175 of the Code of Virginia, issue emergency orders in any case where there is an imminent danger to the public health resulting from the operation of any waterworks or the source of a water supply.
B. An emergency order may be communicated by the best practical notice under all the circumstances and is effective immediately upon receipt. The order may state any requirements necessary to remove the danger to the public health, including the immediate cessation of the operation of the waterworks or the use of any water supply. The commissioner may order the immediate cessation of the operation of any waterworks or the use of any water supply or the correction of any condition causing the production or distribution of any water constituting an imminent danger to the public health and welfare.
C. Violation of an emergency order is subject to civil enforcement and is punishable as a criminal misdemeanor.
D. Emergency orders shall be effective for a period determined by the commissioner.
E. Emergency orders may be appealed in accordance with the provisions of the Administrative Process Act APA.
12VAC5-590-125. Chronically noncompliant waterworks.
A. The commissioner may identify a waterworks as chronically noncompliant (CNC) whenever he determines that:
1. The waterworks has a documented performance record that demonstrates the waterworks is not a dependable supplier of potable water;
2. The owner has shown inadequate technical, financial, or managerial capabilities to provide potable water;
3. The owner has failed to comply with an order issued by the commissioner;
4. The owner has abandoned the waterworks and has discontinued providing potable water to the consumers; or
5. The owner is subject to a forfeiture order pursuant to § 32.1-174.1 of the Code of Virginia.
B. Once A. If the commissioner [ or department ] determines that a waterworks is CNC a chronically noncompliant waterworks, as defined in § 32.1-167 of the Code of Virginia, he then the commissioner shall issue an order to the owner containing a schedule to bring the waterworks into compliance with this chapter and require the submission of a comprehensive business plan pursuant to § 32.1-172 B of the Code of Virginia waterworks business operation plan. If capital improvements are necessary to bring the waterworks into compliance, and the owner does not possess sufficient assets to make the necessary improvements, the order shall require the owner to make annual, good faith applications for loans, grants, or both, to appropriate financial institutions to secure funding for such improvements, until such the improvements are complete and operational. The owner shall provide a copy of the order to each consumer with a copy of the compliance schedule within 10 calendar days of issuance of the order.
C. The owner shall provide the commissioner a copy of the notice order was distributed and a signed certification of the distribution completion date within five calendar days of completing the notification required in subsection B of this section.
B. Within 15 calendar days of issuance of the commissioner's order, the owner shall certify in writing that a copy of the order was distributed to each consumer within the 10-day period specified in subsection A of this section.
D. C. The commissioner shall send a copy of the order to the chief administrative officer of the locality in which the waterworks is located for appropriate action under § 15.2-2146 of the Code of Virginia.
E. D. In addition to the provisions of § 32.1-27 of the Code of Virginia, any owner who violates this chapter, an order of the board, or a statute governing public water supplies shall be subject to those civil penalties provided in §§ 32.1-167 through 32.1-176 Article 2 (§ 32.1-167 et seq.) of Chapter 6 of Title 32.1 of the Code of Virginia.
12VAC5-590-130. Suspension of this chapter.
If, in the case of a manmade man-made or natural disaster, the commissioner finds determines that certain regulations cannot be complied with and that the public health is better served by access to semiregulated or nonregulated water supplies than by the closing of those affected supplies he may suspend, then the application enforcement of the chapter those regulations may be suspended for specific affected localities designated waterworks and institute a provisional regulatory scheme instituted until the disaster is abated the conditions that brought about the suspension have abated.
12VAC5-590-140. Variances.
A. The commissioner may grant a variance to a primary maximum contaminant level (PMCL), a PMCL, SMCL, treatment technique requirement, or an operational regulation, or a secondary maximum contaminant level (SMCL) by following the appropriate procedures set forth in this section.
1. Requirements for a variance. A PMCL variance may be granted to a waterworks from any requirement respecting with respect to a PMCL or SMCL upon a finding that:
a. Alternative sources of water supplies are not reasonably available to the waterworks;
b. The characteristics of the raw water sources which are source water that is reasonably available to the waterworks prevent prevents the waterworks from meeting the PMCL or SMCL requirements, and on condition that the waterworks installs the best available technology BAT, treatment techniques, or other means, which that the [ commissioner department ] finds are generally available (taking costs into consideration); and
c. The granting of a variance will not result in an unreasonable risk to the health of persons served by the waterworks.
2. The commissioner may grant a one or more treatment technique variance variances to a waterworks from any requirement of a specified treatment technique upon a finding that the waterworks applying for the variance has demonstrated that such the treatment technique is not necessary to protect the health of persons because of the nature of the raw water source of such source water at the waterworks.
3. The commissioner may grant a variance to a waterworks from an operational regulation or a SMCL if a thorough investigation reveals that the hardship imposed outweighs the benefits that may be received by the public and that the granting of such the variance does not subject the public to unreasonable health risks. An operational variance may not be issued from monitoring, reporting, or public notification requirements.
4. An operational variance may not be issued from monitoring, reporting, or public notification requirements.
B. Application Request for a variance. Any owner may apply in writing for a variance. The application should request shall be sent to the appropriate field office department for evaluation. All applications requests for a variance shall include the following:
1. A citation of the regulation from which a variance is requested;
2. The nature and duration of the variance requested;
3. Relevant analytical results of water quality sampling of the waterworks, including results of relevant tests conducted pursuant to the requirements of this chapter;
4. A statement of the hardship to the owner and the anticipated impacts to the public health and welfare if a variance were granted;
5. Suggested conditions that might be imposed on the granting of a variance that would limit its detrimental impact on public health and welfare;
6. Other information, if any, believed by the applicant owner to be pertinent to the application request; and
7. Such Any other information as may be required by the commissioner to make the determination.
8. C. For any application request made for a PMCL variance, the applicant owner shall also include;:
a. Explanation 1. An explanation in full and evidence of the best available treatment technology and techniques BAT;
b. Economic 2. The economic and legal factors relevant to the owner's ability to comply;
c. Analytical 3. The analytic results of raw water source water quality relevant to the variance request;
d. 4. A proposed compliance schedule including the date each step toward compliance will be achieved. Such The schedule shall include as a minimum the following dates:
(1) Date a. The date by which arrangement for an alternative raw water source source water or improvement of an existing raw water source source water will be completed;
(2) Date b. The date of initiation of the connection of the alternative raw water source source water or improvement of the existing raw water source source water; and
(3) Date c. The date by which final compliance is to be achieved.
e. 5. A plan for the provision of safe drinking potable water in the case of an excessive rise in the contaminant level for which the variance is requested; and
f. 6. A plan for interim control measures during the effective period of the variance.; and
7. A plan for notifying the consumers at least once every three months, or more frequently if determined by the commissioner, that the waterworks is operating under the conditions of a variance.
9. D. For any application request made for a treatment technique variance, the applicant owner must also include a statement that monitoring and other reasonable requirements prescribed by the commissioner as a condition to the variance will be performed.
C. E. Consideration of a variance application request.
1. The commissioner shall act on any variance application request submitted pursuant to subsection B of this section within 90 days of receipt of the application submittal.
2. The commissioner will consider comments received during the comment period and testimony in the record of a public hearing held before making a determination.
3. In the commissioner's consideration of whether the waterworks is unable to comply with a contaminant level required by this chapter (PMCL variance) because of the nature of the raw water source source water, the commissioner shall consider such factors as the following:
a. The availability and effectiveness of treatment methods BAT for which the variance is requested.; and
b. Cost The cost and other economic considerations such as implementing treatment, improving the quality of the source water, or using an alternate source.
3. 4. In the commissioner's consideration of whether a waterworks should be granted a variance to a required treatment technique because such the treatment is unnecessary to protect the public health (treatment technique variance), the commissioner shall consider such factors as the following:
a. Quality of the source water source including water quality data and pertinent sources of pollution.; and
b. Source protection measures employed by the waterworks.
4. 5. In the commissioner's consideration of whether a waterworks should be granted a variance to a required operational procedure or SMCL (operational variance), the commissioner shall consider such factors as the following:
a. The effect that such a variance would have on the adequate operation of the waterworks, including operator safety (in accordance with Virginia Occupational Safety and Health laws). in accordance with VOSH laws and regulations;
b. The cost and other economic considerations imposed by this requirement.; and
c. The effect that such a variance would have on the protection of the public health.
D. F. Disposition of a variance application request.
1. The commissioner may reject any application request for a variance by sending a rejection notice to the applicant. The rejection notice shall be in writing and shall state the reasons for the rejection. A rejection notice constitutes a case decision. The applicant has the right to petition for a hearing within 60 days of the date of the rejection to challenge the rejection pursuant to 12VAC5-590-160 and 12VAC5-590-180 If the commissioner proposes to deny the variance, the owner shall be provided with an opportunity for an informal fact-finding proceeding as provided in § 2.2-4019 of the Code of Virginia.
2. If the commissioner grants the variance, the applicant shall be notified in writing of this decision. Such The notice shall identify the variance, the waterworks covered, and shall specify the period of time for which the variance will be effective.
a. For a PMCL variance as specified in subdivision A 1 of this section, such the notice shall provide that the variance will be terminated when the waterworks comes into compliance with the applicable regulation and may be terminated upon a finding by the commissioner that the waterworks has failed to comply with any requirements of a final schedule issued pursuant to subdivision D F 3 of this section.
b. For a treatment technique variance as specified in subdivision A 2 of this section, such the notice shall provide that the variance may be terminated at any time upon a finding by the commissioner that the nature of the raw water source water is such that the specified treatment technique for which the variance was granted is necessary to protect the public health or upon a finding that the waterworks has failed to comply with monitoring and other requirements prescribed by the commissioner as a condition to the granting of the variance.
c. For an operational variance as specified in subdivision A 3 of this section, such the notice shall provide that the variance will be terminated when the waterworks comes into compliance with the applicable regulation and may be terminated upon a finding by the commissioner that the waterworks has failed to comply with any requirements or schedules issued in conjunction with the variance. The effective date of the operational variance shall be the date of its issuance. A public hearing is not required before the issuance of an operational variance.
3. Schedules pursuant to PMCL and treatment technique variances:
a. The proposed schedule for compliance shall specify dates by which steps towards toward compliance are to be taken, including where applicable:
(1) Date by which arrangement for an the alternative water source water or improvement of the existing raw water. source water will be completed;
(2) Date of connection to the alternative raw water source water or improvement of the existing raw water. source water; and
(3) Date by which final compliance is to be achieved.
b. If the waterworks has no access to an alternative raw water source water and can effect or anticipate no adequate improvement of the existing raw water source water, then the proposed schedule may specify an indefinite time period for compliance until a new and effective treatment technology is developed, at which time a new compliance schedule shall be prescribed by the commissioner.
c. The schedule for implementation of interim control measures during the period of variance shall specify interim treatment techniques, methods, and equipment and dates by which steps toward meeting the interim control measures are to be met.
d. The schedule shall be prescribed by the commissioner at the time the variance is granted.
e. For a PMCL variance specified in subdivision A 1 of this section, the commissioner shall propose a schedule for:
(1). Compliance (including increments of progress) by the waterworks with each contaminant level requirement covered by the variance; and
(2). Implementation by the waterworks of such control measures as the commissioner may require for each contaminant level covered by the variance.
E. G. Public hearings on PMCL and treatment technique variances and their schedules.
1. Notice of a public hearing shall be provided before a variance and schedule proposed by the commissioner pursuant to subsection D F of this section may take effect. A notice given pursuant to the preceding sentence this subsection may cover the granting of more than one variance and a public hearing held pursuant to such notice shall include each of the variances covered by the notice.
2. Notice of a public hearing on an application a request for a variance and its schedule shall be advertised in at least one major newspaper of general circulation in the region in which the waterworks is located. The notice shall include a summary of the proposed variance and its schedule and shall contain the time, date, and place of the public hearing. If the schedule exceeds five years from the date of the variance, then the rationale for the extended compliance schedule shall be discussed in the notice.
F. H. Issuance of variance.
1. Within 30 days after the public hearing, the commissioner shall, taking into consideration information obtained during such hearing, revise the proposed variance as necessary and prescribe the final schedule for compliance and interim measures for the waterworks granted a variance. If the schedule for compliance exceeds five years from the date of issuance of the variance, then the commissioner shall document the rationale for the extended compliance schedule.
2. Such The compliance schedule shall establish the timetable by which the waterworks shall comply with each contaminant level and treatment technique requirement prescribed by this chapter. Such schedule shall also consider if the waterworks is to become part of a regional waterworks. Such The compliance schedule shall provide the shortest practicable time schedule under the circumstances.
G. I. Posting of variances. All variances granted to any waterworks are nontransferable. Each variance must be attached to the permit of the waterworks to which it is granted. Each variance is a condition to that permit and is revoked when the permit is revoked.
H. J. No variances shall be granted to 12VAC5-590-380, 12VAC5-590-400, or 12VAC5-590-420, 12VAC5-590-388, 12VAC5-590-395, or 12VAC5-590-411.
12VAC5-590-150. Exemptions.
A. The commissioner may grant an exemption to any primary maximum contaminant level (PMCL) PMCL or treatment technique requirement by following the procedures set forth in this subsection section. An exemption may be granted to a waterworks from any requirement with respect to a PMCL or treatment technique requirement upon a finding that:
1. The waterworks [ must be is ] unable to implement measures to develop an alternative [ supply of source ] of water [ supply ];
2. The waterworks cannot reasonably make management or restructuring changes that will result in compliance or improve the quality of the drinking water;
3. Due to compelling factors (which may include economic factors), the waterworks is unable to comply with such contaminant level or treatment technique requirement requirements;
4. The granting of the exemption will not result in an unreasonable risk to the health of persons served by the waterworks;
5. The waterworks was in operation on the effective date of such contaminant level or treatment technique requirement requirements; and
6. The waterworks has not been granted a variance.
B. Application for exemption. A waterworks The owner may request an exemption for a waterworks by submitting a written application request to the appropriate field office department for evaluation. All applications requests for an exemption shall include the following information:
1. A citation to the regulation from which the exemption is requested;
2. Nature The nature and duration of the exemption requested;
3. Relevant The relevant analytical results of water quality sampling of the waterworks, including results of relevant tests conducted pursuant to the requirements of this chapter;
4. Explanation An explanation of the compelling factors such as time or economic factors which that prevent such waterworks from achieving compliance;
5. Other information believed by the applicant owner to be pertinent to the application request;
6. A proposed compliance schedule, including the date when each step toward compliance will be achieved; and
7. Such other Other information as may be required by the commissioner to make the determination.
C. Consideration of an exemption application request.
1. The commissioner shall act on any exemption application request submitted pursuant to subsection B of this section within 90 days of receipt of the application request.
2. In the commissioner's consideration of whether the waterworks is unable to comply due to compelling factors, the commissioner shall consider such factors as the following:
a. Construction The construction, installation, or modification of treatment equipment or systems;
b. The time needed to put into operation a new water treatment facility plant into operation to replace an existing waterworks which water treatment plant that is not in compliance;
c. The economic feasibility of compliance;
d. The availability of Drinking Water State Revolving Fund, a department program to assist waterworks in achieving the public health protection objectives of the SDWA, assistance or any other federal or state program that is reasonably likely to be available within the period of the exemption;
e. The consideration of rate increases, accounting changes, the appointment of a licensed operator under the state operator's licensure program, or contractual agreements for joint operation with one or more waterworks;
f. The activities consistent with Virginia's capacity development strategy to help the waterworks acquire and maintain technical, financial, and managerial capacity to come into compliance;
g. The ownership changes, physical consolidation with another waterworks, or other feasible and appropriate means of consolidation that would result in compliance; and
h. The availability of an alternative source of drinking water, including the feasibility of partnerships with neighboring waterworks, as identified by the waterworks or by the commissioner consistent with the capacity development strategy.
D. Disposition of an exemption application request.
1. The commissioner may reject any application request for an exemption by sending a rejection notice to the applicant owner. The rejection notice shall be in writing and shall state the reasons for the rejection. A rejection notice constitutes a case decision. The applicant has the right to petition for a hearing within 60 days of the date of the rejection to challenge the rejection pursuant to 12VAC5-590-160 and 12VAC5-590-180. If the commissioner proposes to deny the exemption, then the owner shall be provided with an opportunity for an informal fact-finding proceeding as provided in § 2.2-4019 of the Code of Virginia.
2. If the commissioner grants the exemption, then the applicant owner shall be notified in writing of this decision. Such The notice shall identify the exemption and the waterworks covered and shall specify the termination date of the exemption. Such notice shall provide that the exemption Exemptions shall be terminated when the waterworks comes into compliance with the applicable regulation and may be terminated upon a finding by the commissioner that the waterworks has failed to comply with any requirements of a final schedule issued pursuant to subsection F of this section.
3. The commissioner shall propose a schedule for:
a. Compliance (including increments of progress) by the waterworks with each contaminant level and treatment technique requirement covered by the exemption; and
b. Implementation by the waterworks of such control measures as the commissioner may require for each contaminant level and treatment technique requirement covered by the exemption.
4. The schedule shall be prescribed by the commissioner at the time the exemption is granted.
5. For a waterworks that serves a population of not more than 3,300 persons and that needs financial assistance for the necessary improvements under the initial compliance schedule, an exemption granted by the commissioner may be for one or more additional two-year periods, but not to exceed a total of six additional years, only if the commissioner establishes that the waterworks is taking all practicable steps to meet the requirements of the exemption and the established compliance period. The commissioner will document the findings in granting an extension under this subdivision.
E. Public hearings on exemptions and their schedules.
1. Notice of a public hearing shall be provided before an exemption and schedule proposed by the commissioner pursuant to subsection D of this section may take effect. A Such notice given pursuant to the preceding sentence may cover the granting of more than one exemption, and a public hearing held pursuant to such the notice shall include each of the exemptions covered by the notice.
2. Notice of a public hearing on an application a request for an exemption and its schedule shall be advertised in at least one major newspaper of general circulation in the region in which the waterworks is located.
3. The notice shall include a summary of the proposed exemption and its schedule and shall contain the time, date, and place of the public hearing.
F. Issuance of exemption.
1. Within 30 days after the public hearing, the commissioner shall, taking into consideration information obtained during such the hearing, revise the proposed exemption as necessary and prescribe the final compliance schedule for compliance and interim measures for before issuing the exemption to the waterworks granted an exemption.
2. Such The schedule shall establish the timetable by which the waterworks shall comply with each contaminant level and treatment technique requirement prescribed by this chapter section. If the schedule for compliance exceeds five years from the date of issuance of the exemption, then the commissioner shall document the rationale for the extended compliance period. Such schedule shall also consider if the waterworks is to become part of a regional waterworks.
G. Posting of exemptions. All exemptions granted to any waterworks are nontransferable. Each exemption must be attached to the operation permit of the waterworks to which it is granted. Each exemption is a condition to that permit and is revoked when the permit is revoked.
H. No exemption shall be granted to 12VAC5-590-380, 12VAC5-590-400, or 12VAC5-590-420 B 1 b [ , ] 12VAC5-590-388, or 12VAC5-590-395.
12VAC5-590-160. Types of hearings. (Repealed.)
Hearings before the board, the commissioner, or their designees shall include any of the following forms depending upon the nature of the controversy and the interests of the parties involved.
1. An informal hearing is a meeting with the district engineer and field director and held in accordance with § 9-6.14:11 of the Code of Virginia. The field director may consider all evidence presented at the meeting which is relevant to the issue in controversy. Presentation of evidence, however, is entirely voluntary. The field office has no subpoena power. No verbatim record will be taken at the informal hearing, but the field director may make preliminary findings of fact, and may submit a copy of those preliminary findings, with recommendations, to the commissioner and or division director for review. A copy of the findings shall be mailed to the appellant.
2. The adjudicatory hearing is a formal, public, adjudicatory proceeding before the commissioner or a designated hearing officer held in conformance with § 9-6.14:12. Pursuant to the hearings process:
a. A Notice which states the time, place, and issues involved in the prospective hearing shall be sent to parties requesting the hearing by certified mail at least 15 calendar days before the hearing is to take place;
b. A record of the hearing will be made by a court reporter or other approved means. A copy of the transcript of the hearing, if transcribed, will be provided within a reasonable time to any person upon written request and payment of the cost. If the record is not transcribed, then the cost of preparation of the transcript will be borne by the party requesting the transcript;
c. All interested parties may attend the hearing and present evidence, expert or otherwise, that is material and relevant to the issues in controversy. The admissibility of evidence shall be in accordance with the Administrative Process Act. All parties may be represented by counsel;
d. The commissioner or hearing officer, pursuant to § 9-9.14:13 of the Code of Virginia, may issue subpoenas for the attendance of witnesses and the production of books, papers, maps, and records. The failure of a witness without legal excuse to appear or to testify or to produce documents may be reported by the commissioner to the appropriate circuit court; and
e. The commissioner may designate a hearing officer or subordinate to conduct the hearing, as provided in § 9-6.14:12 of the Code of Virginia, and to make written recommended findings of fact and conclusions of law to be submitted for review and final decision by the commissioner. The final decision of the commissioner shall be reduced to writing and will contain the explicit findings of fact upon which his decision is based. Copies of the decision shall be delivered to the owner affected by it. Notice of a decision will be served upon the parties and become a part of the record. Service may be by personal service or certified mail, return receipt requested.
3. A regulatory hearing is a public meeting of the board which is held for the purpose of adopting, amending, or repealing rules and regulations. A regulatory hearing requires that:
a. A notice shall be published, in at least one newspaper of general circulation in the commonwealth, not less than 60 days prior to the day on which the regulatory hearing is to be held. Such notice shall state the time, place, and nature of the hearing and the express terms or an informative survey of the rules that are to be adopted, amended, or repealed;
b. All interested persons may be present at the hearing and may present comments, arguments, objections, and evidence which concern the proposed rules; and
c. The board may adopt, repeal, or amend any rule or regulation which was included in the general notice published prior to the meeting. Rules and regulations may be adopted in the form in which they were described in the notice, or as amended at the hearing, provided the amendments do not alter the main purpose of the rule or regulation.
12VAC5-590-170. Request for hearing. (Repealed.)
Any person may request a hearing by sending a request, in writing, to the appropriate field office or the central office.
12VAC5-590-180. Hearing as a matter of right. (Repealed.)
Any person whose rights, duties or privileges have been or may be affected by any action or inaction of the board, its agents, or deputies in the administration of this chapter, shall have a right to both an informal and an adjudicatory hearing; however, the commissioner reserves the right to require participation in an informal hearing before granting the request for a full adjudicatory hearing.
12VAC5-590-190. Permits.
A. No owner or other person may cause or allow any waterworks to be operated in the Commonwealth without a written operation permit issued by the commissioner.
B. No owner or other person shall cause or allow the construction or change in the manner of transmission, storage, purification, treatment, or distribution of water (including the extension of water pipes for the distribution of water) at any waterworks or water supply in the Commonwealth without a written construction permit or a general permit for distribution mains from the commissioner. Furthermore, no owner or other person shall cause or permit any waterworks or water supply to be operated without a written operation permit issued by the commissioner which authorizes the operation of the waterworks or water supply. Conditions may be imposed on the issuance of any permit, and no waterworks or water supply may be constructed, modified, or operated in violation of these conditions.
C. Construction permits may not be required for the extension of water distribution piping having a diameter of eight inches or less and serving less than 15 connections (see § 32.1-172 A of the Code of Virginia).
D. Individual construction permits for distribution mains are not required for waterworks that obtain a general permit (see 12VAC5-590-300).
E. Conditions may be imposed on the issuance of any permit, and no waterworks may be constructed, modified, or operated in violation of these conditions.
12VAC5-590-200. Procedure for obtaining a construction permit.
A. Construction permits are issued by the Commissioner commissioner, but all requests for a construction permit are directed initially to the Field Office department. The procedure for obtaining the a construction permit includes the following steps:
(i) the submission of an application, (ii) a preliminary engineering conference, (iii) the submission of an engineer's report (optional at the discretion of the Field Director), and, (iv) the submission of plans, specifications, design criteria and other data in the number requested by the Division.
A. An application for a permit shall be submitted by the owner or authorized agent requesting permission to establish, construct, expand, modify, and/or operate a waterworks or water supply. The application shall clearly indicate whether the affected water supply is a community, nontransient noncommunity, or noncommunity waterworks.
B. A preliminary conference with the Division's appropriate District Engineer will be held. The applicant's engineer shall be prepared to set forth the water supply problems and the proposed solution in such a manner as to support his conclusions and recommendations.
C. The engineer's report and preliminary plans for waterworks shall present the following information where applicable:
1. General information - The report shall include:
a. A description of any existing waterworks and sewerage facilities.
b. Identification of the municipality or area served.
c. The name and mailing address of the owner.
2. Extent of waterworks system - The report shall include:
a. A description of the nature and extent of the area to be served.;
b. Provisions for extending the waterworks system to include additional areas.
c. An appraisal of the future requirements for service, including existing and potential industrial, commercial, institutional and other water supply needs.
3. Alternate plans - Where two or more solutions exist for providing public water supply facilities, each of which is feasible and practicable, the report shall discuss the alternate plans and give reasons for selecting the one recommended, including financial considerations.
4. Soil, groundwater conditions, and foundation problems - The report shall include:
a. A description of the character of the soil through which water mains are to be laid.
b. A description of foundation conditions prevailing at sites of proposed structures.
c. A description of the approximate elevation of ground water in relation to subsurface structures.
5. Water consumption - The report shall include:
a. A description of the population trends as indicated by available records, and the estimated population which will be served by the proposed water supply system or expanded system.
b. Present and estimated future water consumption values used as the basis of design.
c. Present and estimated future yield of the sources of supply.
6. Fire flow requirements: - if fire flows are to be provided, the quantity of fire flow which will be made available by the proposed or enlarged system shall be given.
7. Sewerage system available: - Describe the existing system and sewage treatment works, with special reference to its relationship to the existing or proposed waterworks which may affect the operation of the water supply system, or which may affect the quality of the water supply.
8. Source of water supply: - Describe the proposed source or sources of water supply to be developed and the reasons for their selection by supplying the following data:
a. Surface water sources
(1) Hydrological data, stream flow, and weather records;
(2) Safe yield, including all factors that may affect it;
(3) Maximum flood flow, together with approval for safety features of spillway and dam from appropriate reviewing authority;
(4) Summarized quality of raw water with special references to fluctuation in quality, changing meteorological conditions, sources of contamination, measures to protect the watershed, etc.
b. Groundwater sources
(1) Sites considered,
(2) Advantages of site selected,
(3) Elevation with respect to surroundings and 100-year flood,
(4) Probable character of geological formations through which source is to be developed,
(5) Unusual geological conditions affecting site,
(6) Summary of source exploration, test well depth and method of construction, placement of liners or screens; pumping test, hours, capacity; water level and specified yield, water quality,
(7) Possible sources of contamination.
9. Proposed treatment processes - Summarize and establish the adequacy of proposed processes for the treatment of the specified water under consideration (pilot studies may be required).
10. Waste disposal - Discuss the various wastes from the water treatment plant, their volume, proposed treatment and points for discharge.
11. Automatic equipment - Provide supporting data justifying automatic equipment, including servicing.
12. Project sites - The report shall include:
a. A discussion on various sites considered and advantages of the recommended one,;
b. A description of the proximity of residences, industries, and other establishments,
c. The location of potential sources of pollution that may influence the quality of the supply or interfere with the effective operation of the waterworks system, such as sewage absorption systems, septic tanks, privies, cesspools, sink holes, sanitary landfills, petroleum storage tanks, etc.
13. Financing - The report shall state:
a. The estimated cost of integral parts of the system,
b. The detailed estimated annual cost of operation,
c. The proposed method of financing, both capital charges and operating expenses.
14. Future extensions - Summarize planning for future needs and service.
1. Owners shall notify the department of all proposed construction projects, except distribution main projects that are permitted under the provisions of a general permit for distribution mains (see 12VAC5-590-300), or when the project is for the extension of water distribution piping having a diameter of eight inches or less and serving less than 15 connections (see § 32.1-172 A of the Code of Virginia).
2. The submission of a Waterworks Permit Application to the department on a form approved by the department.
3. Based on the application received, the department shall notify the owner if a preliminary engineering conference is required. A preliminary engineering conference shall be required for projects proposed using alternative delivery methods authorized under § 2.2-4380 of the Code of Virginia. The preliminary engineering conference shall define the scope of the project, project phasing, milestones, and deliverables. An evaluation procedure shall be agreed upon and the conference shall be documented.
4. The submission of preliminary engineering or intermediate design reports if required by the department. The need for and scope of the reports shall be established during the preliminary engineering conference.
5. The submission of a waterworks business operation plan that demonstrates the waterworks TMF [ capability capabilities ]. The waterworks business operation plan consists of four primary components:
a. Waterworks information that includes ownership data, a waterworks facility description, operator requirements, staffing needs, and staff training.
b. Management information that identifies critical business practices necessary for effective management and operation of the waterworks. Management information includes the requirements essential for managing and operating the waterworks and defines the processes, methods, and tasks necessary for complying with this chapter.
c. Financial information that identifies projects, considering the waterworks revenues and cash flow, [ which ] will be sufficient for meeting the cost of operation and maintenance for at least five full years from the initiation of operations. Financial information also demonstrates the owner's ability to direct the waterworks' finances to support technical and managerial capacities and includes a self-assessment consisting of the following [ several ] financial metrics: operating cash reserve, debt service coverage, emergency reserve, and revenue sufficiency.
d. Sustainability improvements that are identified throughout the waterworks business operation plan to address TMF aspects of the waterworks' business processes that need improvement.
6. The submission of plans, specifications, final design criteria, and other supporting design data. This submission may include manufacturers equipment data sheets, drawings, and specifications when the specific materials or equipment to be used in the project have been preselected by the owner with the engineer's concurrence.
B. Well site inspection. When, upon inspection by the department, one or more well locations are found suitable for well sites, tentative approval in writing shall be furnished to the owner authorizing the drilling of wells, the exact location where each well is to be drilled, and the well construction requirements. This tentative approval will become void after a 12-month period.
D. C. Plans for waterworks improvements construction shall provide the following information, where applicable:
1. A general layout which that includes:
a. Suitable title, to include name of waterworks,;
b. Name of owner of waterworks,;
c. Area or institution to be served,;
d. Scale, in feet,;
e. North Point,;
f. Datum used,;
g. Boundaries of the municipality or area to be served,
h. g. Date, address, and name of designing owner's engineer,;
i. Imprint of professional engineer's seal ( see 12VAC5-590-220),
j. Legible prints suitable for microfilming, with size not to exceed 30 inches by 42 inches,
k. h. Location and size of existing water mains, distribution system; and
l. i. Location and nature of existing waterworks structures and appurtenances affecting the proposed improvements construction noted on one sheet.
2. Detailed plans which that include, where applicable:
a. Stream crossings, providing profiles with elevations of the stream bed and the normal and extreme high and low water levels, water level;
b. Profiles having a horizontal scale of not more than 100 feet to the inch and a vertical scale of not more than 10 feet to the inch, with both scales clearly indicated,;
c. Location and size of the property to be used for the groundwater development with respect to known references such as street intersections or section lines,;
d. Topography and arrangement of present or planned wells or structures, with contour intervals not greater than two feet,;
e. Elevation of highest known flood level, floor of structure, upper terminal of protective casing, and outside surrounding grade, using United States Coast and Geodetic Survey, United States Geological Survey, or equivalent elevations where applicable as a reference,;
f. Schematic drawing A completed Uniform Water Well Completion Report, Form GW-2, and schematic drawings of well construction, showing diameter and depth of drillholes drill holes, casing and liner diameters and depths, grouting depths, elevations and designation of geological formation, water levels, and other details to describe the proposed well completely,;
g. Location If not previously submitted in the preliminary engineering report (PER): the location of all potential sources of pollution within 250 1,000 feet (or further, depending upon aquifer type and recharge area) of drilled wells, 100 feet of treated water storage facilities, five miles upstream from surface water intakes, and the entire drainage area of springs;
h. Size, length, identity, and location or of sewers, drains, water mains distribution systems, and water treatment plant structures;
i. Schematic flow diagrams and hydraulic profiles showing the flow through various water treatment plant units,;
j. Piping in sufficient detail to show flow through the water treatment plant, including waste lines,;
k. Location of all chemical feeding equipment and points of chemical application,;
l. All appurtenances, specific structures, equipment, water treatment plant waste disposal units, and point of discharge having any relationship to the plans for water mains and/or distribution system or waterworks structures,;
m. Location of sanitary or other facilities such as lavatories, showers, toilets, and lockers,;
n. Location, dimensions, and elevations of all proposed water treatment plant facilities,; and
o. Adequate description of all features not otherwise covered by the specifications.
E. Complete, detailed, technical specifications shall be supplied for the proposed project which include where applicable:
D. Specifications for waterworks construction improvements shall provide the following information, where applicable:
1. A program for keeping existing waterworks facilities in operation during construction of additional facilities so as to minimize interruption of service,;
2. Laboratory The laboratory facilities and equipment, as well as sampling taps and their locations,;
3. Number The number and design of treatment process components,;
4. Materials The materials or proprietary equipment for sanitary or other facilities including any necessary backflow or backsiphonage backflow protection,;
5. Workmanship,; and
6. Other equipment.
F. E. Design criteria. A summary of complete design criteria shall be submitted for the proposed project, containing but not limited to the following information, where applicable:
1. Yield of source of supply, Source water capacity;
2. Reservoir surface area,
3. Area of watershed,
4. 2. Estimated water consumption, including average day, maximum day, and peak hour flows;
5. 3. Number and type of proposed services,;
6. Fire-fighting 4. Firefighting requirements,;
7. 5. Basin capacities,;
8. 6. Retention times,;
9. 7. Unit loadings,;
10. 8. Filter area and proposed filtration rate,;
11. 9. Backwash rate,; and
12. 10. Feeder capacities and ranges.
F. For community waterworks, a copy of the duly recorded (i) plat plan of the well lot or subdivision plan showing the well lot and (ii) dedication document stating that the well lot shall be used only for waterworks appurtenances as long as the lot is utilized as part of a waterworks.
G. For noncommunity waterworks, the [ commissioner department ] may on a case-by-case basis require a copy of a duly recorded plat plan of a well lot and a dedication document stating that the well lot shall be used only for waterworks appurtenances as long as the lot is utilized as part of a waterworks. In imposing such a requirement, the [ commissioner department ] shall take into consideration public health protection and the waterworks operations, treatment processes, and appurtenances.
12VAC5-590-210. Formal requirements Requirements for the submission of engineering data.
A. In accordance with Article 1 (§ 54.1-400 et seq.) of Chapter 4 (§ 54.1-400 et seq.) of Title 54.1 of the Code of Virginia, all drawings, specifications, and engineer's reports submitted for approval shall be prepared by or under the supervision of a licensed professional engineer legally qualified to practice in Virginia, unless submitted under § 54.1-408 of the Code of Virginia for practice of land surveying in subdivisions.
The front cover of each set of drawings, of each copy of the engineer's report, and of each copy of the specifications submitted for review shall bear the signed imprint of the seal of the licensed professional engineer who prepared or supervised the preparation and be signed with an original signature. In addition, each drawing submitted shall bear an imprint or a legible facsimile of such seal. B. The quantity, format, and method of submission shall meet the evaluation needs of the department and shall be consistent with the requirements in Chapter 42.1 (§ 59.1-479 et seq.) of Title 59.1 of the Code of Virginia.
C. All reports, plans, and specifications shall be submitted to the field office department at least 60 days prior to before the date upon which action by the division department or commissioner is desired.
D. If the procedures for obtaining a construction permit in 12VAC5-590-200 are not complied with or if plans and specifications are found to be incomplete or inadequate for detailed review evaluation, then the plans and specifications will be returned to the submitting party. If revisions to the plans or specifications or both are necessitated, a letter will be sent to the owner and engineer who prepared them outlining the will be notified in writing of the necessary revisions. Revised plans, or specifications, or both constitute a resubmittal; however, the division will make every resubmission. Every effort will be made to complete the review of such evaluation of these revisions promptly. Preliminary plans and the engineer's report should be submitted for review prior to preparation of final plans.
12VAC5-590-220. Compliance with the Manual of Practice.
A. The design guidelines set forth in the Manual of Practice (Part III) Part III Manual of Practice for Waterworks Design (12VAC5-590-640 et seq.) of this chapter (Manual of Practice) specify general criteria for the design and construction of waterworks. The division commissioner may impose standards or requirements which that are more stringent than those contained in the Manual of Practice when required for critical areas or special conditions to meet drinking water quality standards. Any such special standards or requirements with a federal mandate shall take precedence over the criteria in the manual Manual of Practice and will be items which that warrant careful consideration at the preliminary engineering conference, referenced in 12VAC5-590-200 B.
B. Designs submitted for waterworks must demonstrate that the system waterworks will adequately safeguard public health. Submissions which that are in substantial compliance with the Manual of Practice or and any additional requirements of the department commissioner, as noted above in [ subdivision subsection ] A of this section, will be approved. Justification for a design may be required for those portions of the submitted design which that differ from the criteria of the division, set forth in the Manual of Practice, or accepted engineering practices and any established by the commissioner. Deviations from "shall" mandatory criteria which the design engineer, in his judgment, believes to be substantial in nature contained in the Manual of Practice shall be identified and justified. The division For each deviation, the commissioner may require changes in designs which are not in substantial compliance with the manual and which are not adequately justified by the engineer owner issue a design exception or require compliance with the criteria.
C. Final, complete, and detailed plans and specifications submitted in accordance with the provisions of 12VAC5-590-200 and 12VAC5-590-210 will be reviewed evaluated by the division department as soon as practicable upon receipt. Such plans Plans and specifications will be approved if they demonstrate substantial compliance with the design criteria set forth in the Manual of Practice and any established by the commissioner and if the waterworks, as constructed or modified, will be able to function in compliance with the operating regulations set forth in Part II (12VAC5-590-340 et seq.) of this chapter. One set of the approved plans and specifications will be stamped by the division and returned to the owner.
D. Compliance with the Manual of Practice for transient noncommunity waterworks is allowed the following exceptions as long as the conditions in subsection E of this section are satisfied:
1. The design of a transient noncommunity waterworks is not required to satisfy the professional engineer licensure requirement of 12VAC5-590-210 under the following conditions:
a. The waterworks shall serve no more than 100 persons per day.
b. The waterworks shall consist only of one supply of source water, a pressure tank no greater than 250 gallon capacity, and a single service connection.
c. The single service connection shall be a building or structure of less than 5,000 square feet total floor space. The determination of square footage shall be calculated using the outside perimeter of the building or structure.
2. Although the owner of a transient noncommunity waterworks is required to use a water well systems provider certified by DPOR for drilling wells, the remainder of the waterworks facility construction at a transient noncommunity waterworks may be performed by a master plumber or a certified water well systems provider, as defined in § 54.1-1129.1 of the Code of Virginia.
E. The conditions for exceptions to the Manual of Practice for transient noncommunity waterworks specified in subsection D of this section are as follows:
1. The owner shall submit a signed and dated statement attached to the permit application, certifying that subsection D of this section will be satisfied.
2. The owner shall submit information related to the design, construction, and materials used as required by the department.
12VAC5-590-230. Issuance of the construction permit.
A. Upon approval of the plans and specifications, the commissioner will issue a permit to the owner to construct or modify his the waterworks or water supply in accordance with the approved plans and specifications.
B. The construction permit shall be valid for a period of five years. If construction has not begun within five years but were to proceed in the future, then the owner shall reapply for a new construction permit.
C. The construction permit may include conditions for securing equipment certifications and performance validations.
12VAC5-590-240. Revisions of approved plans.
A. Any deviations from the approved plans and specifications affecting capacity, hydraulic conditions, operating units, the functioning of water treatment processes, or the quality of water to be delivered must be approved by the division department before any such changes of these deviations are made implemented.
B. Revised plans and specifications shall be submitted in time to permit allow the review evaluation and approval of such these plans or specifications before any construction work which that will be affected by such these changes is begun may begin.
12VAC5-590-250. Statement required upon completion of construction.
A. Upon completion of the construction or modification of the waterworks, the owner shall submit to the field office department a statement signed by a licensed professional engineer stating that the construction work was completed in accordance with the approved plans and specifications, revised only in accordance with the provisions of 12VAC5-590-240. This statement is called a statement of completion of construction and shall be based upon inspections of the waterworks during and after construction or modifications, that. These inspections are to be adequate to insure ensure the truth of the statement of completion of construction.
B. The project documents may require a performance validation report to confirm the design, performance criteria, and appropriate emergency procedures for specific processes and equipment. The project documents may also require operator training. If these requirements are included in the project documents, then the statement of completion of construction shall also include the performance validation report and a certification of successful operator training, as applicable.
12VAC5-590-260. Issuance of the operation permit.
A. Upon receipt of the 12VAC5-590-250 statement of completion of construction, receipt of all required certifications and test results, inspection by the department to ensure that the project has been satisfactorily completed in accordance with the approved design documents, and verification that bacteriological test results comply with the requirements set forth in Part II of this chapter, as appropriate, the commissioner will issue an operating operation permit. However, the commissioner may delay the granting of the permit pending inspection by the field office to insure that the work has been satisfactorily completed.
B. The owner shall not operate a waterworks without first having obtained an operation permit except as provided in 12VAC5-590-290.
C. The commissioner shall establish the type (community waterworks, NTNC, or TNC), classification, and permitted capacity of the waterworks and specify these on the operation permit. Conditions may be included with the permit for operator, monitoring, and reporting requirements.
12VAC5-590-270. Inspection and correction Start-up testing and inspections.
A. Within 30 days after Before placing a new or modified waterworks or water supply into operation following construction, the owner shall test the water produced at the entry point to the distribution system in a manner acceptable to the division department. The field office will be notified owner shall notify the department of the time and place of the tests. Results The owner shall send the results of the tests will be sent to the field office department.
B. The commissioner, a member of the board, or a member of the division [ has and department have ] a right to inspect any waterworks or water supply and to be present for any testing in accordance with Title 32.1 of the Code of Virginia.
12VAC5-590-280. Procedure for obtaining a construction permit for well sources. (Repealed.)
Since the quantity and quality of water from proposed wells cannot be anticipated, the following procedure shall be used:
1. Submittal of application--see 12VAC5-590-200 A.
2. Preliminary engineering conference--see 12VAC5-590-200 B.
3. When, upon inspection by the division's engineer, one or more well lots are found suitable for well sites, then tentative approval in writing will be furnished to the owner authorizing him to proceed with the drilling of the well or wells and this letter will specify the exact location on the lot where each well is to be drilled. Also, the letter will specify that the well shall be Class I or Class II, meeting the specifications set forth in Part III Article 2, Source Development. This tentative approval will become void after a 12-month period and the site must be reinspected before construction when so voided.
4. Submittal of engineer's report and preliminary plans--see 12VAC5-590-200 C.
5. Submittal of plans, specifications, and other data--see subsections D, E, and F of 12VAC5-590-200; 12VAC5-590-210 and 12VAC5-590-840. One of the following must also be submitted:
a. A copy of the plat plan showing that it has been duly recorded and signed by the clerk of the court, giving the deed book and page number and date of recording, will be required before a construction permit can be issued, or
b. If the well lot is identified on a recorded plan of the subdivision as a well lot, then this is acceptable, if recorded as required by this subsection.
In addition, a dedication document duly recorded with the clerk of the circuit court must be furnished stating that the well lot shall be used only for waterworks appurtenances as long as this lot is utilized as part of a waterworks.
6. Compliance with 12VAC5-590-220 through 12VAC5-590-270 is required.
12VAC5-590-290. Procedure for issuance of special permits for new or nonconventional methods, processes, and equipment Issuance of a temporary operation permit.
A. Water treatment methods, processes, and equipment which that are not covered by the design criteria of Part III or Part IV (12VAC5-590-640 et seq.) of this chapter, and which that in principle or application are new or nonconventional, are subject to a special temporary permit application procedure in lieu instead of that set forth in 12VAC5-590-200. A special temporary permit may be issued only after detailed review evaluation of all engineering data and after a period of extensive monitoring of the water treatment plant performance.
B. The policy of the board is to encourage The department encourages the development of any new or nonconventional methods, processes, and equipment which, that by virtue of treatability studies, appear to have application for the purification of raw water treatment. However, these new or nonconventional developments shall have been thoroughly tested in a full scale full-scale or representative pilot plant installation before approval of a plant utilizing this process these methods, processes, and equipment can be employed are approved and an operation permit issued. The result of this testing must results shall be submitted to the field office department. The testing required on new or nonconventional developments will shall generally follow these guidelines:
1. All procedures used in validating the process shall be conducted under the supervision of (i) a licensed professional engineer experienced in the field of environmental engineering, (ii) the owner's engineering staff, or (iii) a testing firm acceptable to the division [ commissioner department ];
2. Samples shall be collected and analyzed in a manner which would that shall demonstrate water treatment plant effectiveness and efficiency under adverse conditions and over extended periods of time in the area of the proposed installation;
3. The data shall be from the continuous operation of a full scale full-scale or pilot plant treating the type of water to be handled;
4. Automatic indicating, recording, and totalizing flow measuring equipment shall be provided, and the total flow shall be measured and recorded daily;
5. At installations treating surface waters, employing coagulation, flocculation, sedimentation, filtration, and disinfection, automatic indicating and recording equipment shall be provided for continuously monitoring the turbidity of the raw water, settled water, and each filter effluent, as well as pH monitoring of the treated water (flash mix effluent);
6. 5. If the raw water source source water receives upstream discharges of treated industrial wastes or sewage effluents treated wastewater, then automatic indicating and recording equipment shall be provided for continuously monitoring the pH of raw the source and finished water and in addition to the chlorine residual of the finished water;
7. 6. The minimum sampling and analysis program will be established by the division [ commissioner department ] in accordance with the process under investigation; and,
8. 7. All analyses shall be made in accordance with the most current edition of Standard Methods for the Examination of Water and Wastewater, published by the American Public Health Association, the American Water Works Association, and the Water Pollution Control Federation or analytical methods approved in advance by the division utilize methods that are consistent with 12VAC5-590-440.
C. Detailed plans shall be submitted where possible showing how, in case of nonacceptance, the water treatment plant or unit water treatment methods, processes, and equipment will be converted to, or replaced with, a proven process. Also, financial resources must be assured to make the conversion (for example:, funds placed in escrow or a bond posted) posted.
D. After review evaluation of the plans and testing data, the commissioner will issue a construction permit if he is satisfied the performance data verifies that the method, process, or equipment will may efficiently produce water that will meet in accordance with the design specifications and the operation standards of Part II, and that the method, process, or equipment may be converted to a conventional technique, if necessary (12VAC5-590-340 et seq.) of this chapter.
E. Upon completion of construction or modification, a provisional temporary permit for a definite period of time will be issued for the operation of the new or nonconventional methods, processes, and equipment. Not more than one provisional temporary permit will be granted for a similar installation during the evaluation period. The provisional temporary operation permit shall require that:
1. The evaluation period shall be a minimum of 12 months and no longer than 18 months; and
2. The holder of a provisional temporary operation permit must shall submit reports on operation during the evaluation period as required by the division [ commissioner department ]. The reports shall be prepared by (i) a licensed professional engineer experienced in the field of environmental engineering, (ii) the owner's operating or engineering staff, or (iii) a testing firm acceptable to the division organization.
F. The commissioner will issue an operation permit upon lapse of the provisional permit, if, on the basis of testing during that period, he finds that the new or nonconventional method, process, or equipment efficiently meets the operation standards of Part II. If the standards are not met, then the commissioner will issue an order which will require the alteration of the waterworks or water supply in a manner that will enable those standards to be met.
F. The commissioner may issue a temporary operation permit if the waterworks is not in compliance with this chapter and public health will not be jeopardized. The temporary permit may be issued for a period of time and subject to conditions as the commissioner may deem appropriate for the owner to achieve compliance with this chapter.
1. The commissioner may require, as a condition to a temporary operation permit, the submission of a waterworks business operation plan by new waterworks and existing waterworks that have demonstrated limited TMF [ capability capabilities ] or significant noncompliance with this chapter.
2. The waterworks business operation plan shall satisfy the requirements of 12VAC5-590-200 A 5.
12VAC5-590-300. Procedure for obtaining Issuance of a general permit for construction of distribution mains.
In lieu A. Instead of obtaining a permit for each distribution main project, an owner may elect to obtain a general permit for the construction of distribution mains. These general permits are issued by the commissioner, but all requests for a general permit are directed initially to the field office department.
B. The following procedure for obtaining the requirements shall be satisfied for the issuance of a general permit shall be used:
1. The owner shall develop, adopt, and have division the [ commissioner's department's ] approval of general specifications and plan details covering water distribution main design and construction. The general specifications shall be at least as stringent as the requirements contained in this chapter.
2. The owner shall enter into a memorandum of understanding (MOU) with the division which outlines the following system-specific [ commissioner department ]. The [ commissioner department ] will outline the waterworks-specific requirements, and the owner's method of compliance with such the requirements:. The waterworks-specific requirements include the following:
a. The maximum size of pipe to be covered by the general permit;
b. The means for modifying the division department's approved general specifications and plan details;
c. The maintenance of engineering capabilities satisfactory to the division [ commissioner department ], either on-staff or through contractual arrangements;
d. The preparation of engineering plans and specifications for individual projects;
e. The maintenance of up-to-date distribution system maps and other appropriate records; and
f. The submission by the owner to the division department of appropriate reports, including an annual report and summary, concerning all projects constructed under the terms of the general permit MOU and information concerning changes to the distribution system.
C. Once the general specifications are approved and the MOU is agreed to by the [ commissioner department ], [ the commissioner will issue ] a general permit for distribution mains [ shall be issued ] with the MOU attached.
D. The general permit allows for the construction of distribution mains. The duration for the general permit is five years.
12VAC5-590-310. Amendment or reissuance of operation permits.
A. The commissioner may amend or reissue a an operation permit where (i) when there is a change in the manner of storage, the treatment, or the source of supply of the source water at the permitted location,; (ii) when the existing permit is no longer valid; or (iii) for any other cause incident to the protection of the public health,; or (iv) for the supplying of pure potable water, provided. A notice is may be required to be given to the owner, and, if one is required, a hearing held in accordance with the provisions of subdivisions 1 and 2 of 12VAC5-590-160 12VAC5-590-115.
B. The commissioner may require submission of a waterworks business operation plan as a condition to amend or reissue an operation permit. The waterworks business operation plan shall satisfy the requirements of 12VAC5-590-200 A 5.
12VAC5-590-320. Revocation or suspension of a an operation permit.
A. The commissioner may suspend or revoke a an operation permit in accordance with Administrative Process Act the APA. Reasons for revocation of permits are as follows include:
1. Failure to comply with the conditions of the permit;
2. Violation of Title 32.1 of the Code of Virginia or of any of this chapter from which no variance or exemption has been granted;.
3. Change in ownership;
4. Abandonment of the waterworks and discontinuing the supplying of pure water; and
5. Any of the grounds specified in § 32.1-174 of the Code of Virginia.
1. The waterworks can no longer be depended upon to furnish potable water;
2. The capacity of the waterworks is inadequate for the purpose of furnishing potable water;
3. The owner has failed to abide by an order issued by the commissioner;
4. The owner has abandoned the waterworks and discontinued supplying potable water; or
5. The owner has failed to pay the waterworks operation fee required by § 32.1-171.1 of the Code of Virginia.
B. Procedure for revocation of operation permit. When revoking or suspending permits an operation permit in accordance with the above subsection A of this section, the commissioner shall:
1. Send a written notice of intent to suspend or revoke by certified mail to the last known address of the waterworks owner. The notice shall state the reasons for the proposed suspension or revocation of the operation permit, the authority under which the commissioner proposes to act, and shall give the time and place of the hearing; and offer the opportunity for an administrative proceeding in accordance with 12VAC5-590-115.
2. Provide at least 30 days advance notice of the hearing administrative proceeding.
C. An owner who is given notice of intent to revoke or suspend his permit has a right to a hearing as specified in 12VAC5-590-160 and 12VAC5-590-180.
12VAC5-590-330. Monitoring, records, and reporting.
A. The commissioner or the division department may require the owner or operator of any waterworks or water supply to install, use, and maintain monitoring equipment for the control and testing of water flowing through the water treatment plant to:
1. Identify and determine the cause of operational problems;
2. Determine the necessary corrective actions for these problems;
3. Ensure compliance with Part II of this chapter; and
4. Prepare the finished water for entry into the distribution system.
B. Sampling and testing shall be by methods approved by the division [ commissioner department ]. Test results shall be recorded, compiled, and reported to the field office department in [ a an acceptable manner and ] format [ approved by acceptable to the division commissioner ].
12VAC5-590-340. General Compliance standards.
A. All physical, chemical, bacteriological, or radiological analyses for the purpose of demonstrating compliance with primary and secondary maximum contaminant levels action levels or contaminants that do not have PMCLs but for which compliance samples must be analyzed by certified laboratories the requirements of this chapter shall be performed by [ the ] Commonwealth of Virginia, Department of General Services, Division of Consolidated Laboratory Services (DCLS) [ DCLS or ] in [ by ] laboratories [ certified by the that have received certification by EPA or DCLS as specified ] Division of Consolidated Laboratory Services [ DCLS for such purposes unless listed ] in 12VAC5-590-440 [ C ]. The owner is responsible for the collection and submission of all samples. The department may require sampling and testing that exceeds the minimal requirements specified in this chapter. A sample is deemed to have been collected only if and when its results are made known to the Office of Drinking Water department.
B. Specific limits. No attempt has been made to prescribe specific limits for every contaminant that might occur in a water supply or a waterworks. Although the need exists for continued attention to the entry of chemical, physical, bacteriological, and radiological substances into drinking water, the limits are confined to substances recognized as being detrimental to the health or well-being of the consumer or that cause significant degradation of the usefulness of the water. Limits for innumerable substances would require an impossible burden of analytical examination. The specific limits included in this chapter are listed in Tables 340.1 through 340.7.
C. Compliance is determined:
1. Based on sample results or calculated averages, where appropriate, rounded to the same number of significant figures as the PMCL, SMCL, AL, or MRDL of the contaminant in question, or
2. By the application of the specific treatment technique for particular contaminants (see 12VAC5-590-391).
EDITOR'S NOTE: Tables 340.1 through 340.7 are not further amended from the proposed regulation, therefore they are not published. View the tables as proposed at 36:6 VA.R. 475-845 November 11, 2019.
D. Notwithstanding the MRDLs in Table 340.7, an owner may increase the residual disinfectant level of chlorine or chloramines (but not chlorine dioxide) in the distribution system to a level and for a time necessary to protect public health. This may include specific microbiological contamination problems caused by circumstances such as distribution line breaks, storm runoff events, water supply contamination events, or cross-connection events.
12VAC5-590-350. Sanitary surveys Assessments and sanitary surveys.
A. Frequent assessments shall be made by the owner of the water supply source and waterworks to locate and identify health hazards to the waterworks. The manner and frequency of making these assessments, and the rate at which discovered health hazards are to be removed, shall be the responsibility of the owner. Every effort shall be made by the owner, to the extent of his jurisdiction, to prevent the degradation of the quality of water supply sources supplies.
B. The commissioner may perform sanitary surveys. Owners The department is required to perform sanitary surveys and site visits to assess the condition of a waterworks and its source water. Pursuant to § 32.1-25 of the Code of Virginia, the department [ personnel have the right, shall, upon presentation of appropriate credentials and ] with the owner's consent, [ have the right ] of entry onto the waterworks property and the facilities to inspect, investigate, evaluate, conduct tests, and collect samples for testing for the purposes of determining compliance with the provisions of any law, regulation, or order administered by the board or commissioner or any conditions in a permit, license, or certificate issued by the board or commissioner. The owner shall provide any existing information requested by the department that will enable the commissioner the department [ personnel ] to conduct the sanitary survey or site visit.
C. A sanitary survey includes, but is not limited to, an onsite evaluation of all of the following eight components:
1. Source;
2. Treatment;
3. Distribution system;
4. Finished water storage;
5. Pumps, pumping facilities, and controls;
6. Monitoring, reporting, data verification, and a special monitoring evaluation during each sanitary survey to determine whether the waterworks monitoring is appropriate or needs modification;
7. Waterworks system management and operation; and,
8. Number and classification of licensed operator(s) required in 12VAC5-590-460 operators. Licensed operators Operators shall also comply with all applicable regulations promulgated by the Virginia Board for Waterworks and Wastewater Works Operators and Onsite Sewage System Professionals, Department of Professional and Occupational Regulation and DPOR.
D. Significant deficiencies discovered as a result of a sanitary survey shall be addressed in accordance with the following:
1. The commissioner department shall issue written notification describing the significant deficiency to the owner.
2. Within 30 days of the significant deficiency significant-deficiency notification, the owner shall consult with the commissioner department regarding the appropriate corrective action with a schedule for implementing the corrective action. Any A waterworks with one or more significant deficiencies must have a Corrective Action Plan (CAP) CAP as described in 12VAC5-590-421 A.
3. Within 45 days of the significant deficiency significant-deficiency notification, the owner shall submit to the department a CAP with a schedule for meeting the requirements of 12VAC5-590-421 A.
12VAC5-590-360. Responsibility; Responsibilities of the owner.
A. The water utility owner or owner of the property served, to the extent of their respective jurisdictions, shall provide and maintain conditions through throughout the entirety of the water supply system waterworks in a manner which that will assure a high degree of capability and reliability to effect compliance with these standards comply with Part II (12VAC5-590-340 et seq.) of this chapter. This requirement shall pertain to the source of supply source water, transmission, treatment, transmission, storage, and distribution system facilities and the operation thereof. In addition, this requirement shall include specific and continuing assessment of the capability, effectiveness, and reliability of the treatment process in relation to potential contaminants in the source of supply. Finally, this requirement shall include the identification and evaluation of all The owner shall identify and evaluate factors having with the potential for impairing the quality of the water as delivered to customers and appropriate preventive and control the consumers. Preventative control measures identified in Part II of this chapter shall be promptly implemented to protect public health.
B. For the purpose of application of this chapter, responsibility for the conditions in the water supply system shall be considered to be held by: 1. The owner from the source of supply to the customer's service connection; and 2. The owner of the property served and the municipal, county, or other authority having legal jurisdiction from the customer's service connection to the free-flowing outlet. For the purpose of achieving compliance with this chapter, the owner shall exercise control of the waterworks from the source water to the service connection. This requirement does not imply ownership of or maintenance for any portion of the service line where local agreements and conditions dictate otherwise.
C. The property owner shall exercise control of all buildings, structures, and equipment up to the point of the service connection to the waterworks. This requirement does not limit or modify ownership of or maintenance for the service line, that may be specified by local agreements and conditions.
Article 2
General Information
12VAC5-590-370. Sampling frequency Monitoring requirements.
The commissioner may exempt consecutive waterworks that obtain potable water from another water system for distribution from all monitoring requirements in this section except for bacteriological (subsection A of this section); disinfectant residuals, disinfection byproducts, and disinfection byproduct precursors (subdivision B 3 of this section); and lead and copper (12VAC5-590-375). The required sampling frequencies are as follows:
A. Bacteriological monitoring.
1. The owner shall collect total coliform samples at specific sites and according to a schedule that is representative of water quality throughout the distribution system, which shall be documented in a written bacteriological sample siting plan (BSSP) BSSP. The BSSP shall be established or approved by the commissioner department after investigation of the source water, method of treatment and storage, and protection of the water concerned the final delivery of the drinking water through the distribution system. The BSSP shall include, but is not limited to, the following:
a. Specific routine, repeat, and triggered source water monitoring sites, identified by address or location.
b. Distribution map maps showing the location where specific sampling sites will be selected with all monitoring sites identified.
c. A minimum of three routine sample sites identified for each required routine sample for waterworks serving 3,300 or fewer people.
d. Sample A sample collection schedule with the number of routine samples required per monitoring period in accordance with Table 2.1 370.1 and subdivision A 4 of this section.
e. Repeat sample sites for each routine sample site that shall include the original routine location, at least one tap within five service connections upstream, and at least one tap within five service connections downstream with the following exceptions:
(1) Alternative repeat sample sites may be allowed when a routine site is one connection away from or at the end of a water supply distribution system main or as approved by the commissioner department;
(2) Groundwater waterworks A groundwater system serving 1,000 or fewer people may propose repeat sample sites, such as an entry point to the distribution system, that differentiate potential source water and distribution system contamination; or
(3) Groundwater waterworks A groundwater system serving 1,000 or fewer people with a single well source and no treatment may propose that one repeat sample be collected at the triggered source water monitoring site, provided that representative sampling of the distribution system is still achieved.
f. A repeat sampling site shall not be eliminated from future collections solely based on a history of questionable water quality unless the sampling point is unacceptable as determined by the commissioner department.
g. A seasonal waterworks may collect special samples in accordance with an approved start-up procedure pursuant to subdivision A 10 12 a of this section.
2. The minimum number of bacteriological samples for total coliform evaluation to be collected and analyzed monthly from the distribution system of a community waterworks, or nontransient noncommunity waterworks a NTNC shall be in accordance with Table 2.1. Owners of all 370.1. The owner of a (i) transient noncommunity waterworks TNC that use uses a surface water source or a groundwater source under the direct influence of surface water and or (ii) a large transient noncommunity TNC (serving 1,000 or more persons per day) waterworks shall collect and submit samples monthly for analysis in accordance with Table 2.1 370.1. Owners of For all other transient noncommunity waterworks TNCs, the owner shall collect and submit samples for analysis each calendar quarter in accordance with Table 2.1. 370.1. The minimum number of samples must be collected and submitted even if the waterworks has exceeded the E. coli PMCL or the total coliform treatment technique triggers.
3. The samples shall be taken collected at reasonably evenly spaced time intervals as practical throughout the month, except that a waterworks that use uses only groundwater serving and serves 4,900 or fewer people may collect all have the required samples collected on a single day if the samples are taken collected from different sites.
4. If the results of a sanitary survey or other factors determine that some other frequency is more appropriate than that stated in subdivisions A 2 and A 3 and A 4 of this section, then a modified BSSP may be required. The altered frequency shall be confirmed or changed on the basis of subsequent sanitary surveys or as otherwise determined by the commissioner department.
5. An The owner may conduct more compliance monitoring than is required by this section to investigate potential problems in the distribution system and to assist in uncovering problems. An The owner may take collect more than the minimum number of required routine samples. If the samples are taken collected in accordance with the existing BSSP and are representative of water quality throughout the distribution system, then all of the results shall be included in determining whether a coliform treatment technique has been triggered.
6. An The owner may propose repeat monitoring locations believed to be representative of a pathway for contamination of the distribution system. An The owner may elect to specify either alternative fixed locations or criteria for selecting repeat sampling sites on a situational basis in a standard operating procedure (SOP) SOP in its BSSP. The owner shall design the SOP to focus on the collection of repeat samples at locations that best verify and determine the extent of potential contamination of the distribution system area based on specific situations. The commissioner department shall require modifications to the SOP or require alternative monitoring locations as needed.
TABLE 2.1 370.1
Bacteriological Monitoring
|
POPULATION SERVED PER DAY
|
MINIMUM NUMBER OF SAMPLESa
(See subdivision A 2 of this section)
|
25 to 1,000b
|
1
|
1,001 to 2,500
|
2
|
2,501 to 3,300
|
3
|
3,301 to 4,100
|
4
|
4,101 to 4,900
|
5
|
4,901 to 5,800
|
6
|
5,801 to 6,700
|
7
|
6,701 to 7,600
|
8
|
7,601 to 8,500
|
9
|
8,501 to 12,900
|
10
|
12,901 to 17,200
|
15
|
17,201 to 21,500
|
20
|
21,501 to 25,000
|
25
|
25,001 to 33,000
|
30
|
33,001 to 41,000
|
40
|
41,001 to 50,000
|
50
|
50,001 to 59,000
|
60
|
59,001 to 70,000
|
70
|
70,001 to 83,000
|
80
|
83,001 to 96,000
|
90
|
96,001 to 130,000
|
100
|
130,001 to 220,000
|
120
|
220,001 to 320,000
|
150
|
320,001 to 450,000
|
180
|
450,001 to 600,000
|
210
|
600,001 to 780,000
|
240
|
780,001 to 970,000
|
270
|
970,001 to 1,230,000
|
300
|
1,230,001 to 1,520,000
|
330
|
1,520,001 to 1,850,000
|
360
|
1,850,001 to 2,270,000
2,270,001 to 3,020,000
3,020,001 to 3,960,000
3,960,001 or more
|
390
420
450
480
|
aMonthly monitoring is required for the following waterworks: (i) community, (ii) nontransient noncommunity, (iii) all noncommunity waterworks that use a surface water source, a GUDI source, or both, (iv) all seasonal waterworks, and (v) large noncommunity (serving more than 1,000 people per day). Quarterly monitoring is required for noncommuntity waterworks not specifically identified in the monthly requirements. Annual monitoring may be allowed at a TNC that meets the criteria specified in subdivision A 8 of this section.
bIncludes a waterworks that have at least 15 service connections, but serve fewer than 25 persons.
|
7. All bacteriological analyses shall be performed in accordance with 12VAC5-590-440 by the Division of Consolidated Laboratory Services (DCLS) DCLS or by a laboratory certified by the DCLS for drinking water samples.
8. Annual monitoring. The department may reduce the bacteriological monitoring frequency at a well-operated TNC from a quarterly sample to one annual sample, and the waterworks may remain at the annual monitoring frequency provided that all of the following conditions are continuously met:
a. The waterworks serves 1,000 or fewer people per day.
b. The waterworks uses groundwater only and is not under the influence of surface water.
c. The waterworks has a clean compliance history for a minimum of 12 consecutive months.
d. The most recent sanitary survey shows that the waterworks is free of sanitary defects or has corrected all identified sanitary defects.
e. The waterworks has a protected water source.
f. The waterworks meets existing approved construction standards.
g. The department has conducted an annual site visit within the last 12 months, and all identified sanitary defects have been corrected. For the purposes of this section, an annual site visit is equivalent to a voluntary Level 2 assessment that meets the criteria in 12VAC5-590-392 C. A sanitary survey may meet the requirement for an annual site visit in the year in which the sanitary survey is completed if all identified sanitary defects have been corrected.
8. 9. Increased monitoring.
a. A transient noncommunity waterworks TNC on quarterly or annual monitoring shall begin monthly monitoring in the month following an event if any of the following were to occur occurs: (i) the waterworks triggers a Level 2 assessment or two Level 1 assessments under the provisions of 12VAC5-590-392 in a rolling 12-month period, (ii) the waterworks has an E. coli PMCL violation, (iii) the waterworks has a coliform treatment technique violation, (iv) the owner has two monitoring violations under 12VAC5-590-370 A 2, or (v) the owner has one monitoring violation under 12VAC5-590-370 A 2 and one Level 1 assessment under 12VAC5-590-392 in a rolling 12-month period. Owners The owner shall continue monthly monitoring until the requirements in subdivisions A 9 a A 10 a and A 9 b A 10 b of this section are met. A waterworks on monthly monitoring for other reasons is not considered to be on increased monitoring for the purpose of this subdivision.
b. A TNC on annual monitoring that experiences one monitoring violation of 12VAC5-590-370 must begin quarterly monitoring in the quarter following the event. The owner shall continue quarterly monitoring until the conditions in subdivision A 11 of this section are continuously met and the department reduces the monitoring frequency.
9. 10. Returning to quarterly routine monitoring. The commissioner department may return the monitoring frequency of a transient noncommunity waterworks TNC subject to subdivision A 9 a of this section and using groundwater not under the influence of surface water to quarterly monitoring if:
a. The commissioner department has completed a sanitary survey or a site visit within the last 12 months, and the transient noncommunity waterworks TNC is free of sanitary defects and has a protected water source; and
b. The owner waterworks has maintained a clean compliance history, defined as a record of no PMCL violations for microbiological contaminants, no monitoring violations under 12VAC5-590-370, and no coliform treatment technique trigger exceedances or treatment technique violations under 12VAC5-590-392, for a minimum of 12 consecutive months following the event.
11. Returning to annual routine monitoring. The department may reduce the monitoring frequency of a TNC subject to subdivision A 9 of this section and using groundwater not under the influence of surface water to annual monitoring if:
a. An annual site visit or sanitary survey is conducted by the department, and all identified sanitary defects are corrected. The waterworks may substitute a voluntary Level 2 assessment for the annual site visit.
b. The waterworks has a protected water source and maintained a clean compliance history for a minimum of 12 consecutive months following the event.
c. The waterworks has in place or has adopted one or more of the following additional barriers to contamination: (i) an approved cross-connection control program, (ii) a licensed operator, (iii) continuous disinfection and maintenance of a residual in the distribution system in accordance with criteria specified by the department, (iv) demonstration of maintenance of at least a 4-log removal or inactivation of viruses in accordance with 12VAC5-590-379 A, or (v) other equivalent enhancements approved by the department.
10. 12. Seasonal waterworks monitoring.
a. All A seasonal waterworks shall demonstrate completion of an approved start-up procedure that may include start-up sampling prior to before serving water.
b. A seasonal waterworks shall monitor every month that it is in operation.
c. The commissioner department may waive any seasonal waterworks from some or all of the requirements for seasonal waterworks if the entire distribution system remains pressurized during the entire period that the waterworks is not operating.
d. Failure to complete an approved start-up procedure prior to before serving water is a treatment technique violation and requires the owner to provide public notification under Tier 2 conditions in 12VAC5-590-540 12VAC5-590-540 A 2.
e. Failure to submit certification of completion to the commissioner department after the owner completes an approved start-up procedure is a reporting violation and requires the owner to provide public notification under Tier 3 conditions in 12VAC5-590-540 A 3.
11. 13. Additional routine monitoring in the month following a total coliform-positive sample.
a. Owners The owner collecting samples on a quarterly or annual frequency shall collect at least three additional routine samples during the month following one or more total coliform-positive samples, with or without a Level 1 treatment trigger. The owner shall use the results of additional routine samples in coliform treatment technique trigger calculations under 12VAC5-590-392 B.
b. The requirements specified in subdivision A 11 13 a of this section may be waived by the commissioner department if:
(1) The commissioner department conducts a site visit before the end of the next month in which the waterworks provides water and has determined whether additional monitoring or corrective action is needed;
(2) The commissioner department has determined why the sample was total coliform positive and has established that the owner corrected the problem or will correct the problem before the end of the next month in which the waterworks serves water. In this case, the decision and the rationale for the decision shall be documented and approved in writing by the commissioner department. The commissioner department shall make this document available to EPA and the public. The documentation shall describe the specific cause of the total coliform-positive sample and what action the owner has taken or will take to correct this problem; or
(3) The commissioner department determines that the owner has corrected the contamination problem before collecting the set of repeat samples required in 12VAC5-590-380 D 3, and all repeat samples are total coliform negative. The commissioner department may waive the requirement for additional routine monitoring the next month.
c. The requirements specified in subdivision A 11 13 a of this section may not be waived by the commissioner department solely on the grounds that all repeat samples are total coliform negative.
12. 14. [ Failure to collect every required routine or additional routine sample in a compliance period is a monitoring violation and requires the owner Any one of the following is a monitoring violation: (i) failure to collect every required routine or additional routine sample in a compliance period, and (ii) failure to analyze for E. coli following a total coliform-positive sample. For each violation, the owner is required ] to provide public notification under Tier 3 conditions in 12VAC5-590-540 A 3.
13. 15. [ Failure to submit monitoring results after the owner properly conducts monitoring is a reporting violation and requires the owner Any one of the following is a reporting violation: (i) failure to submit monitoring results after the owner properly conducts monitoring, (ii) failure to submit a completed assessment form, and (iii) failure to notify the department following an E. coli-positive sample. The reporting requirements in 12VAC5-590-530 are applicable to this subdivision. For each violation, the owner is required ] to provide public notification under Tier 3 conditions in 12VAC5-590-540 A 3.
B. Chemical monitoring. The location of sampling points, the chemicals measured, the frequency, and the timing of sampling within each compliance period shall be established or approved by the commissioner department at the time of issuance of a waterworks operation permit because of changes in this chapter or conditions at the waterworks.
1. The commissioner department may increase required monitoring where necessary to detect variations within the waterworks and to provide quality control for any treatment processes that are employed.
2. Analysis of field composite samples shall not be allowed.
3. Samples for contaminants that may exhibit seasonal variations shall be collected during the period of the year when contamination is most likely to occur.
4. Failure to comply with the sampling schedules in this section [ , which includes the collection of confirmation samples cited in 12VAC5-590-382 A for inorganic chemicals, 12VAC5-590-382 B for nitrate and nitrite, and 12VAC5-590-383 A for organic chemicals, is a monitoring violation and ] shall require public notification pursuant to 12VAC5-590-540 A 3.
C. The department may allow a consecutive waterworks that obtains potable water from another waterworks to limit monitoring to bacteriological, residual disinfectant, DBPs, and lead and copper.
D. Monitoring requirements for a waterworks developing new sources of source water are provided in 12VAC5-590-820, 12VAC5-590-830, and 12VAC5-590-840.
E. The department may require an owner to collect additional samples to provide quality control for any treatment processes that are employed.
F. Surface water sampling requirements specified in 12VAC5-590-372 through 12VAC5-590-378 apply to GUDI sources.
EDITOR'S NOTE: Text stricken in 12VAC5-590-370 B through D in the proposed regulation has not been further amended, therefore it is not published. See proposed stricken text at 36:6 VA.R. 475-845 November 11, 2019.
12VAC5-590-372. Inorganic chemicals monitoring.
A. The owner of a community waterworks or a NTNC shall conduct monitoring to determine compliance with the PMCLs and SMCLs listed in Table 340.1 in accordance with this section. The owner of a TNC shall conduct monitoring to determine compliance with the nitrate, nitrite, and nitrate-nitrite PMCLs listed in Table 340.1 in accordance with this section.
B. If a waterworks draws water from more than one source and the sources are combined before distribution, then the owner shall sample at an entry point to the distribution system during periods of normal operating conditions (i.e., when water is representative of all sources being used).
C. When the results of sampling for antimony, arsenic, asbestos, barium, beryllium, cadmium, cyanide (as free cyanide), chromium, fluoride, mercury, nickel, selenium, or thallium exceed the applicable PMCL, the owner shall collect a confirmation sample, at the same sampling site, within two weeks of notification of the analytical results of the first sample.
D. Monitoring frequency.
1. Asbestos. The [ commissioner department ] has granted a statewide waiver for asbestos. If the statewide waiver is removed or if site-specific waterworks conditions warrant monitoring for asbestos, then monitoring to determine compliance with the PMCL for asbestos specified in Table 340.1 shall be conducted as follows:
a. The owner of a community waterworks or a NTNC shall monitor for asbestos during the first three-year compliance period of each nine-year compliance cycle.
b. If the statewide waiver is removed, and the owner believes the waterworks is not vulnerable to asbestos contamination from either its source water or due to corrosion of its asbestos-cement pipe, then the owner may apply to the [ commissioner department ] for a monitoring waiver for asbestos. If the [ commissioner department ] grants the monitoring waiver, then the owner is not required to monitor.
c. The [ commissioner department ] may grant a waiver based on a consideration of the following factors:
(1) Potential asbestos contamination of the source water; and
(2) The use of asbestos-cement pipe for finished water distribution and the corrosive nature of the water.
d. A waiver remains in effect until the completion of the compliance period (i.e., three years).
e. The owner of a waterworks vulnerable to asbestos contamination due solely to corrosion of its asbestos-cement pipe shall collect one sample at a tap served by the asbestos-cement pipe and under conditions where asbestos contamination is most likely to occur.
f. The owner of a waterworks vulnerable to asbestos contamination due to its source water shall monitor at the entry points.
g. The owner of a waterworks vulnerable to asbestos contamination due both to its source water and corrosion of its asbestos-cement pipe shall collect one sample at a tap served by the asbestos-cement pipe and under conditions where asbestos contamination is most likely to occur.
h. The owner of a waterworks that exceeds the PMCL as determined in 12VAC5-590-382 A shall monitor quarterly beginning in the next quarter after the exceedance occurred.
i. The department may decrease the quarterly monitoring requirement to the frequency specified in subdivision D 1 a of this section provided the department has determined that the waterworks is reliably and consistently below the PMCL. In no case shall the department make this determination unless the owner of a groundwater system collects a minimum of two quarterly samples or the owner of a waterworks that uses a surface water source, in whole or in part, collects a minimum of four quarterly samples.
2. Antimony, arsenic, barium, beryllium, cadmium, chromium, cyanide (as free cyanide), fluoride, mercury, nickel, selenium, and thallium. Monitoring to determine compliance with the PMCL for these contaminants specified in Table 340.1 shall be conducted as follows:
a. The owner shall collect one sample at each groundwater source entry point during each compliance period.
b. The owner shall collect one sample annually at each surface water source entry point, in whole or in part.
c. The owner may apply to the department for a waiver from the monitoring frequencies specified in subdivisions D 2 a and D 2 b of this section.
(1) A condition of the waiver shall require that the owner collect a minimum of one sample while the waiver is effective. The waiver remains in effect for one compliance cycle (i.e., nine years).
(2) The department may grant a waiver provided the owner has monitored surface water source entry points, in whole or in part, annually for at least three years and has conducted a minimum of three rounds of monitoring at groundwater source entry points. At least one sample shall have been collected since January 1, 1990. The owner shall demonstrate that all previous analytical results were less than the PMCL. A waterworks that uses a new groundwater or surface water source is not eligible for a waiver until three rounds of monitoring from the new source have been completed.
(3) In determining the appropriate reduced monitoring frequency, the department shall consider:
(a) The reported concentrations from all previous monitoring;
(b) The degree of variation in reported concentrations; and
(c) Other factors that may affect contaminant concentrations such as changes in groundwater pumping rates, changes in the waterworks configuration, changes in the waterworks operating procedures, or changes in stream flows or characteristics.
(4) A decision by the department to grant a waiver shall be made in writing and shall set forth the basis for the determination. The request for a waiver may be initiated by the department or upon an application by the owner. The owner shall specify the basis for the request. The department shall evaluate and, where appropriate, revise the determination of the appropriate monitoring frequency when the owner submits new monitoring data or when other data relevant to the appropriate monitoring frequency become available.
(5) No arsenic waivers shall be granted by the department.
d. The owner of a waterworks that exceed the PMCLs as calculated in 12VAC5-590-382 shall monitor quarterly beginning in the next quarter after the exceedance occurred. The department may decrease the quarterly monitoring requirement to the frequencies specified in subdivision D 2 a, D 2 b, or D 2 c of this section provided a determination has been made that the analytical results are reliably and consistently below the PMCL. In no case may the department make this determination unless the owner collects a minimum of two quarterly samples from each groundwater source entry point and a minimum of four quarterly samples from each surface water source entry point, in whole or in part.
3. Nitrate and combined nitrate-nitrite as nitrogen. Monitoring to determine compliance with the PMCL for nitrate and combined nitrate-nitrite as nitrogen specified in Table 340.1 shall be conducted as follows:
a. The owner shall collect one sample annually at each groundwater source entry point.
b. The owner shall collect one sample quarterly at each surface water source entry point, in whole or in part.
c. For groundwater source entry points at community and NTNCs, the repeat monitoring frequency shall be quarterly for at least one year following any one sample in which the concentration is greater than 50% of the PMCL. After four consecutive quarters of monitoring, the department may allow the owner to reduce the sampling frequency to annually after determining the results are reliably and consistently less than the PMCL.
d. For surface water source entry points, in whole or in part, the department may allow the owner to reduce the sampling frequency to annually if all analytical results from four consecutive quarters are less than 50% of the PMCL. The waterworks shall return to quarterly monitoring if the concentration found in any one sample is greater than or equal to 50% of the PMCL.
e. After any round of quarterly sampling is completed as required by subdivisions D 3 c and D 3 d of this section, the owner who is monitoring annually shall collect subsequent samples during the quarter that previously resulted in the highest analytical result.
f. No monitoring waivers shall be issued for nitrate or combined nitrate-nitrite as nitrogen.
4. Nitrite. Monitoring to determine compliance with the PMCL for nitrite specified in Table 340.1 shall be conducted as follows:
a. The owner shall collect one sample at each entry point during the initial compliance period.
b. After the initial sample, the owner of a waterworks where an analytical result for nitrite is less than 50% of the PMCL shall monitor at the frequency specified by the department.
c. The repeat monitoring frequency for an owner shall be quarterly for at least one year following any one sample in which the concentration is greater than 50% of the PMCL. The department may allow an owner to reduce the sampling frequency to annually after determining the analysis results are reliably and consistently less than the PMCL.
d. The owner of a waterworks that is monitoring annually shall collect each subsequent sample during the quarter that previously resulted in the highest analytical result.
e. No monitoring waivers shall be issued for nitrite.
5. Aluminum, chloride, copper, corrosivity, fluoride, foaming agents (surfactants), iron, manganese, silver, sulfate, and zinc. Monitoring to determine compliance with the SMCL for these contaminants specified in Table 340.1 shall be conducted as follows:
a. The owner shall collect one sample at each groundwater source entry point during each compliance period.
b. The owner shall collect one sample annually at each surface water source entry point, in whole or in part.
[ 6. Sodium. All community waterworks shall monitor for sodium as follows:
a. The number of samples to be collected shall be determined by the department based on the waterworks infrastructure and occurrence concentrations where applicable.
(1) The owner shall collect at least one sample annually at each surface water source entry point, in whole or in part.
(2) The owner shall collect one sample at each groundwater source entry point at least every three years.
(3) The department may require the owner to collect and analyze water samples for sodium more frequently where sodium content is variable.
b. Sodium shall be analyzed in accordance with methods and laboratory requirements identified in 12VAC5-590-440.
c. Sample results shall be submitted to the department in accordance with 12VAC5-590-530.
d. The department shall notify local and state health officials of the sodium levels.
e. The results of the special monitoring for sodium shall be included in the Consumer Confidence Report in accordance with 12VAC5-590-545 C 5 f. ]
12VAC5-590-373. Organic chemicals monitoring.
A. The owner of a community waterworks or a NTNC shall conduct monitoring to determine compliance with PMCLs listed in Table 340.2 in accordance with this section. Where two or more sources are combined before distribution, the owner shall sample at the entry point for the combined sources during periods of normal operation conditions.
1. The owner of a waterworks that uses groundwater shall collect a minimum of one sample at each entry point.
2. The owner of a waterworks that uses surface water, in whole or in part, shall collect a minimum of one sample at each entry point.
B. During the initial compliance period and each subsequent compliance period, the owner shall monitor during four consecutive calendar quarters for each contaminant listed in Table 340.2. A minimum of one sample at each entry point shall be collected during each calendar quarter.
C. Reduced monitoring.
1. Volatile organic chemicals (VOCs).
a. The requirement for four quarterly samples during [ the ] initial monitoring [ period ] as specified in subsection B of this section may not be reduced.
b. The department may decrease the requirement for quarterly monitoring during subsequent compliance periods provided it has been determined that the analytical results are reliably and consistently below the PMCL. [ In no case shall the department make this determination unless: ]
(1) [ In no case shall the department make this determination unless the The ] owner collects a minimum of two quarterly samples at each groundwater source entry point; or
(2) The owner collects a minimum of four quarterly samples at each surface water source entry point, in whole or in part.
c. If the department determines that the waterworks is reliably and consistently below the PMCL, then the department may allow the owner to monitor annually. The owner who monitors annually shall monitor during the quarter that previously yielded the highest analytical result.
d. For a groundwater system only. After a minimum of three years of annual sampling, the department may allow the owner with no previous detection of any VOCs listed in Table 340.2 to collect one sample during each compliance period.
e. The owner of a groundwater system that has three consecutive annual samples with no detection of a contaminant may apply to the department for a waiver [ , in accordance with 12VAC5-590-373 F ].
2. Synthetic organic chemicals (SOCs).
a. The owner of a waterworks serving more than 3,300 persons that does not detect any SOCs listed in Table 340.2 in the initial compliance period may reduce the sampling frequency to a minimum of two quarterly samples in one year during each repeat compliance period.
b. The owner of a waterworks serving fewer than [ than ] or equal to 3,300 persons that does not detect any SOCs listed in Table 340.2 in the initial compliance period may reduce the sampling frequency to a minimum of one sample during each repeat compliance period.
[ c. The department may decrease the requirement for quarterly monitoring during subsequent monitoring periods as specified in subsection B of this section provided the analytical results of the four quarterly samples required during the initial monitoring are reliably and consistently below the PMCL.
d. c. ] The department may reduce the [ increased quarterly ] monitoring required by subdivision [ B or ] D [ 1 ] of this section provided the department has determined that the analytical results are reliably and consistently below the PMCL. In no case shall the department make this latter determination unless:
(1) The owner collects a minimum of two quarterly samples at each groundwater source entry point.
(2) The owner collects a minimum of four quarterly samples at each surface water source entry point, in whole or in part.
[ e. d. ] If the department determines that the analytical results are reliably and consistently below the PMCL, the department may allow the owner to monitor annually. The owner of a waterworks that monitors annually shall monitor during the quarter that previously yielded the highest analytical result.
[ f. e. ] The owner of a waterworks that has three consecutive annual samples with no detection of a contaminant may apply to the department for a waiver for SOC monitoring by submitting a waiver application as specified in subdivisions [ E F ] 1 b and [ E F ] 2 b of this section. The waiver remains in effect for one compliance period (i.e., three years).
[ 3. Return to compliance. The owner of a waterworks that exceeds the PMCLs listed in Table 340.2 for VOCs or SOCs, as determined by 12VAC5-590-383, shall monitor quarterly. After a minimum of four consecutive quarterly samples that show the waterworks is in compliance as specified in 12VAC5-590-383 and the department determines that the analytical results are reliably and consistently below the PMCL, the owner may monitor at the frequency and time specified in subdivisions C 1 c and C 2 e of this section. ]
D. Increased monitoring.
1. If the owner of a waterworks that is on reduced monitoring detects a contaminant listed in Table 340.2 (see 12VAC5-590-383 A regarding confirmation samples), then the owner shall monitor quarterly at each sampling point where the contaminant was detected unless:
a. That contaminant was previously detected and the department determined it was reliably and consistently below the PMCL according to subdivisions C 1 b and C 2 [ d c ] of this section;
b. The historical sampling data do not indicate a meaningful increase in the contaminant concentration; and
c. The contaminant concentration does not exceed the PMCL.
2. [ The owner of a waterworks that exceeds the PMCLs listed in Table 340.2 for VOCs or SOCs, as determined by 12VAC5-590-383, shall monitor quarterly.
a. If, after a minimum of four consecutive quarterly samples that show the waterworks is in compliance as specified in 12VAC5-590-383; and
b. The department determines that the analytical results are reliably and consistently below the PMCL; then
c. The owner may monitor at the frequency and time specified in subdivisions C 1 c and C 2 d of this section.
E. Other monitoring requirements.
1. ] Vinyl chloride.
a. The owner of a groundwater system that has detected one or more of the following two-carbon organic compounds: trichloroethylene, tetrachloroethylene, 1,2-dichloroethane, 1,1,1-trichloroethane, cis-1,2-dichloroethylene, trans-1,2-dichloroethylene, or 1,1-dichloroethylene, shall monitor quarterly for vinyl chloride. A vinyl chloride sample shall be collected at each sampling point at which one or more of the two-carbon organic compounds were detected. If the results of the first analysis do not detect vinyl chloride, then the department may reduce the quarterly monitoring frequency of vinyl chloride monitoring to one sample during each compliance period.
b. The owner of a waterworks that [ uses surface water in whole or in part ] is required to monitor for vinyl chloride as specified by the department [ will monitor at each surface water source entry point, in whole or in part ].
[ 3. 2. ] If monitoring detects one or more of certain related contaminants (heptachlor and heptachlor epoxide), then subsequent monitoring shall analyze for all related contaminants.
[ 4. 3. ] For entry points sampled and analyzed for contaminants listed in Table 340.2, the following detection limits apply:
a. A VOC is detected at a level equal to or greater than 0.0005 mg/L; and
b. A SOC is detected at a level equal to or greater than defined by EPA under 40 CFR 141.24(h)(18) or by the department.
[ E. F. ] Monitoring waivers.
1. Groundwater source entry points.
a. The owner of a waterworks that does not detect a VOC contaminant listed in Table 340.2 may apply to the department for a waiver from the subsequent compliance period requirements of subsection B and [ subdivisions subdivision ] C 1 c [ and C 1 d ] of this section after completing the initial monitoring. A waiver shall be effective for no more two compliance periods (i.e., six years).
b. The owner of a waterworks may apply to the department for a SOC monitoring waiver from the requirements of subsection B and subdivision C 2 of this section. The owner must reapply for a waiver for each subsequent compliance period (i.e., three years).
2. Surface water source entry points, in whole or in part.
a. No VOC monitoring waivers shall be issued.
b. The owner of a waterworks that does not detect a SOC contaminant listed in Table 340.2 may apply to the [ commissioner department ] for a SOC monitoring waiver from the requirements of subsection B and subdivision C 2 of this section. The owner must reapply for a waiver for each subsequent compliance period (i.e., three years).
3. Monitoring waiver applications. The owner shall submit a monitoring waiver application for evaluation on a form approved by the department. The [ commissioner department ] may grant a waiver after an evaluation of the use, transport, storage, or disposal of any organic contaminant within the watershed or zone of influence of the source.
a. If an evaluation by the department reveals no previous use of the contaminants within the watershed or zone of influence, then a waiver may be granted.
b. If an evaluation by the department reveals either previous use of the contaminants or that use is unknown, then the following factors shall be used to determine whether a waiver is granted:
(1) Previous analytical results.
(2) The proximity of the source water to land use activities that are potential point or nonpoint sources of organic contamination and to potential conduits to groundwater. Point sources include spills and leaks of chemicals at or near a waterworks or at manufacturing, distribution, or storage facilities or from hazardous or municipal waste landfills and other waste handling or treatment facilities. Nonpoint sources for SOCs include the use of pesticides to control insects and weed pests on agricultural areas, forest lands, home and gardens, and other land application uses.
(3) The environmental persistence and transport of the contaminants listed in Table 340.2.
(4) The implementation of [ a watershed protection program for surface water systems and ] wellhead protection measures [ for groundwater systems ] by the owner.
(5) For groundwater well sources: well construction, well depth, soil type, geological conditions, and well structure integrity.
(6) Special factors, as follows:
(a) For VOCs, the number of persons served by the waterworks and the proximity of a smaller waterworks to a larger waterworks.
(b) For SOCs, elevated nitrate levels at the waterworks' source water.
(c) For SOCs, use of PCBs in equipment used in the production, storage, or distribution of water (i.e., PCBs used in pumps, transformers, and other equipment).
c. An entry point at which treatment has been installed to remove VOCs or SOCs is not eligible for a monitoring waiver for the VOCs or SOCs for which treatment has been installed.
d. All waterworks are granted a waiver from monitoring dioxin, endothall, and glyphosate unless the department determines that there is a source of these contaminants that poses a threat to the source water.
4. Condition for waivers.
a. Groundwater source entry points.
(1) As a condition of the VOC waiver, the owner shall collect one sample at each entry point during the time the waiver is effective (i.e., one sample during two compliance periods or six years) [ and update the waterworks vulnerability assessment ]. Based on this data, the department may reconfirm that the source is [ nonsusceptible nonvulnerable ]. If the department does not make this reconfirmation within three years of the initial determination, then the waiver is invalidated and the owner is required to sample annually.
(2) There are no conditions to SOC waivers.
b. Surface water source entry points, in whole or in part. There are no conditions to VOC and SOC waivers for waterworks in regard to these entry points.
12VAC5-590-374. Residual disinfectant, disinfection byproducts, and disinfection byproduct precursors monitoring.
A. Unless otherwise noted, an owner of a waterworks that uses a chemical disinfectant shall comply with the requirements of this section as follows:
1. The owner of a community waterworks or a NTNC shall comply with this section.
2. The owner of a TNC that uses any combination of a surface water source, a GUDI source, or a groundwater source and uses chlorine dioxide as a disinfectant or oxidant shall comply with all the requirements for chlorine dioxide in this section.
B. The owner shall collect all samples during normal operating conditions.
1. Analysis under this section for DBPs (TTHM, HAA5, chlorite, and bromate) shall be conducted by [ a laboratory laboratories ] that [ has have ] received certification by the [ EPA or ] DCLS [ as specified in 12VAC5-590-440, ] except as noted in subdivisions B 2 and B 3 of this section.
2. Measurement under this section of daily chlorite samples at the entry point to the distribution system, residual disinfectant (free chlorine, combined chlorine, total chlorine, and chlorine dioxide), alkalinity, [ bromide, ] TOC, SUVA (DOC and UV254), pH, and magnesium shall be made by a party approved by the department.
3. Residual disinfectant concentrations for free chlorine, combined chlorine, total chlorine, and chlorine dioxide shall be made using equipment deemed satisfactory by the department.
C. Monitoring plan. The owner required to monitor under this section shall develop and implement a monitoring plan. The owner shall maintain the plan and make it available for inspection by the department and the general public. The owner of a community waterworks or a NTNC that uses a surface water source, a GUDI source, or both and serves more than 3,300 people shall submit a copy of the monitoring plan to the department no later than the date of the first report required under 12VAC5-590-531 A. The department may also require the plan to be submitted by any other owner. After evaluation, the department may require changes in any of the plan elements. The plan shall include at least the following:
1. Specific locations and schedules with monitoring dates for collecting samples for any parameters included in this section.
2. How the owner will calculate compliance with PMCLs, MRDLs, and treatment techniques.
3. The sampling plan for a consecutive waterworks shall reflect the entire consecutive distribution system.
[ 4. All new waterworks shall comply with the monitoring location requirements of 40 CFR 141 Subpart U, Initial distribution system evaluations, in the development of the waterworks monitoring plan. ]
D. Failure to monitor in accordance with the monitoring plan required under subsection C of this section is a monitoring violation. Failure to monitor shall be treated as a violation for the entire period covered by the annual average where compliance is based on an RAA of monthly or quarterly samples or averages, and the owner's failure to monitor makes it impossible to determine compliance with PMCLs or MRDLs.
E. The owner may use only data collected under the provisions of this section to qualify for reduced monitoring.
F. TTHM and HAA5 monitoring. The owner of a community waterworks or a NTNC shall conduct the LRAA monitoring for TTHM and HAA5 at the frequency given below, unless otherwise indicated.
1. This subdivision establishes monitoring and other requirements for achieving compliance with PMCLs based on the LRAA for TTHM and HAA5, and for achieving compliance with MRDLs for chlorine and chloramines for certain consecutive waterworks.
2. This subdivision applies to a community waterworks or a NTNC that uses a primary or secondary disinfectant other than UV light or delivers water that has been treated with a primary or secondary disinfectant other than UV light.
3. Routine monitoring.
a. If the waterworks is a NTNC serving fewer than 10,000 people, then the owner shall monitor at the location or locations and dates identified in the monitoring plan in subsection C of this section, updated as required by subdivision F 3 e of this section.
b. The owner shall monitor at no fewer than the number of locations identified in Table 374.1:
Editor's Note: Tables 374.1 and 374.2 are not further amended from the proposed regulation, therefore they are not published. View the tables as proposed at 36:6 VA.R. 475-845 November 11, 2019.
c. The owner of a waterworks not using disinfection that then begins using a disinfectant other than UV light shall consult with the department to identify compliance monitoring locations. The owner shall develop a monitoring plan under subdivision F 3 e of this section to include those monitoring locations.
d. The owner shall use an approved method listed in 12VAC5-590-440 for TTHM and HAA5 analyses. Analyses shall be conducted by laboratories that have received certification by [ the ] EPA or DCLS as specified in 12VAC5-590-440.
e. The owner may revise the monitoring plan to reflect changes in treatment, distribution system operations and layout (including new service areas), or other factors that may affect TTHM or HAA5 formation, or for reasons approved by the department after consultation with the department regarding the need for changes and the appropriateness of the changes. If the owner changes monitoring locations, then the owner shall replace existing compliance monitoring locations with the lowest LRAA with new locations that reflect the current distribution system locations with expected high TTHM or HAA5 levels. The department may also require modifications in the monitoring plan. The owner of a waterworks using a surface water source, a GUDI source, or both and serving more than 3,300 people shall submit a copy of the modified monitoring plan to the department before the date the owner is required to comply with the revised monitoring plan.
4. Reduced monitoring.
a. The owner may reduce monitoring to the level specified in Table 374.2 any time the LRAA is less than or equal to 0.040 mg/L for TTHM and less than or equal to 0.030 mg/L for HAA5 at all monitoring locations. The owner may only use data collected under the provisions of this section to qualify for reduced monitoring. In addition, the source water annual average TOC level, before any treatment, shall be less than or equal to 4.0 mg/L at each water treatment plant treating a surface water source, a GUDI source, or both based on monitoring conducted under subsection J of this section.
b. The owner may remain on reduced monitoring as long as the TTHM LRAA is less than or equal to 0.040 mg/L and the HAA5 LRAA is less than or equal to 0.030 mg/L at each monitoring location (for waterworks with quarterly reduced monitoring) [ or each TTHM sample is less than or equal to 0.060 mg/L and each HAA5 sample is less than or equal to 0.045 mg/L (for waterworks with annual or less frequent monitoring) ]. In addition, the source water annual average TOC level, before any treatment, shall be less than or equal to 4.0 mg/L at each water treatment plant treating a surface water source or a GUDI source, based on monitoring conducted under subsection J of this section.
c. If the LRAA based on quarterly monitoring at any monitoring location exceeds either 0.040 mg/L for TTHM or 0.030 mg/L for HAA5 or if the annual (or less frequent) sample at any location exceeds either 0.060 mg/L for TTHM or 0.045 mg/L for HAA5, or if the source water annual average TOC level, before any treatment, is greater than 4.0 mg/L at any water treatment plant treating a surface water source, a GUDI source, or both then the owner shall resume routine monitoring under subdivision F 3 of this section or begin increased monitoring if subdivision F 5 of this section applies.
d. A waterworks may return to routine monitoring at the department's discretion.
5. Increased monitoring.
a. The owner of a waterworks required to monitor at a particular location annually or less frequently than annually under subdivision F 3 or F 4 of this section, shall increase monitoring to dual sample sets once per quarter (collected every 90 days) at all locations if a TTHM sample is greater than 0.080 mg/L or a HAA5 sample is greater than 0.060 mg/L at any location.
b. The owner may return to routine monitoring once the waterworks has conducted increased monitoring for at least four consecutive quarters and the LRAA for every monitoring location is less than or equal to 0.060 mg/L for TTHM and less than or equal to 0.045 mg/L for HAA5.
G. Chlorite. The owner of a community waterworks or a NTNC using chlorine dioxide, for disinfection or oxidation, shall conduct monitoring for chlorite.
1. Routine monitoring.
a. The owner shall collect daily samples at the entry point to the distribution system. For any daily sample that exceeds the chlorite PMCL listed in Table 340.6, the owner shall collect additional samples in the distribution system the following day at the locations required by subdivision G 1 c of this section, in addition to the sample required at the entrance to the distribution system.
b. The owner shall collect a three-sample set each month in the distribution system. The owner shall collect one sample at each of the following locations: near the first customer, at a location representative of average residence time, and at a location reflecting maximum residence time in the distribution system. Any additional routine sampling shall be conducted in the same manner (as three-sample sets, at the specified locations). The owner may use the results of additional monitoring conducted under subdivision G 1 c of this section to meet the requirement for monitoring in this subdivision G 1 b.
c. On each day following a routine sample monitoring result that exceeds the chlorite PMCL listed in Table 340.6 at the entrance to the distribution system, the owner is required to collect three chlorite distribution system samples at the following locations: as close to the first customer as possible, in a location representative of average residence time, and as close to the end of the distribution system as possible (reflecting maximum residence time in the distribution system).
2. Reduced monitoring.
a. Chlorite monitoring at the entrance to the distribution system required by subdivision G 1 a of this subsection may not be reduced.
b. Chlorite monitoring in the distribution system required by subdivision G 1 b of this section may be reduced to one three-sample set per quarter after one year of monitoring where no individual chlorite sample collected in the distribution system under subdivision G 1 b of this section has exceeded the chlorite PMCL listed in Table 340.6 and the owner has not been required to conduct monitoring under subdivision G 1 c of this section. The owner may remain on the reduced monitoring schedule until either any of the three individual chlorite samples collected quarterly in the distribution system under subdivision G 1 b of this section exceeds the chlorite PMCL or the owner is required to conduct monitoring under subdivision G 1 c of this section, at which time the owner shall revert to routine monitoring.
H. Bromate.
1. The owner of a community waterworks or a NTNC water treatment plant using ozone for disinfection or oxidation shall collect one sample per month and analyze it for bromate. The owner shall collect samples monthly at the entrance to the distribution system while the ozonation system is operating under normal conditions.
2. The owner required to analyze for bromate may reduce monitoring from monthly to quarterly if the waterworks RAA bromate concentration is less than or equal to 0.0025 mg/L based on monthly bromate measurements under subdivision H 1 of this section for the most recent four quarters. If a waterworks has qualified for reduced bromate monitoring under this subdivision, then the owner may remain on reduced monitoring as long as the RAA of quarterly bromate samples is equal to or less than 0.0025 mg/L. If the RAA bromate concentration is greater than 0.0025 mg/L, then the owner shall resume routine monitoring required by subdivision H 1 of this section.
I. Monitoring requirements for the residual disinfectant.
1. Chlorine and chloramines.
a. The owner of a waterworks that uses chlorine or chloramines shall measure the residual disinfectant level in the distribution system at the same point in the distribution system and at the same time as total coliform bacteria are sampled, as specified in 12VAC5-590-370 A and 12VAC5-590-380 D. The owner of a waterworks using a surface water source, a GUDI source, or both may use the results of the residual disinfectant concentration sampling found in 12VAC5-590-376 D instead of collecting separate samples.
b. Residual disinfectant level monitoring may not be reduced.
2. Chlorine dioxide.
a. The owner of a waterworks that uses chlorine dioxide for disinfection or oxidation shall collect daily samples at the entrance to the distribution system. For any daily sample that exceeds the MRDL listed in Table 340.7, the owner shall collect samples in the distribution system the following day at the locations required by subdivision I 2 b of this section, in addition to the sample required at the entrance to the distribution system.
b. On each day following a routine sample monitoring result that exceeds the MRDL listed in Table 340.7, the owner is required to collect three chlorine dioxide distribution system samples. If chlorine dioxide or chloramines are used to maintain a residual disinfectant in the distribution system, or if chlorine is used to maintain a residual disinfectant in the distribution system and there is no rechlorination after the entry point, then the owner shall collect three samples as close to the first customer as possible, at intervals of at least six hours. If chlorine is used to maintain a residual disinfectant in the distribution system and there are one or more rechlorination points after the entry point, then the owner shall collect one sample at each of the following locations: as close to the first customer as possible, in a location representative of average residence time, and as close to the end of the distribution system as possible (reflecting maximum residence time in the distribution system).
c. Chlorine dioxide monitoring may not be reduced.
3. Ozone. Ozone residual levels shall be monitored continuously and recorded. A portable ozone meter is recommended as a backup.
4. Additional monitoring and reporting requirements are specified in 12VAC5-590-500 to demonstrate log inactivation or removal of Giardia lamblia, virus, and Cryptosporidium.
J. Monitoring requirements for DBPPs.
1. The owner of a community waterworks or a NTNC using a surface water source, a GUDI source, or both and using conventional filtration treatment, as defined in 12VAC5-590-10, shall monitor each water treatment plant for TOC no later than the point of CFE turbidity monitoring and representative of the treated water. The owner shall also monitor for TOC in the source water before any treatment at the same time as monitoring for TOC in the treated water. These samples (source water and treated water) are referred to as paired samples. At the same time as the source water sample is collected, the owner shall monitor for alkalinity in the source water before any treatment. The owner shall collect one paired sample and one source water alkalinity sample per month per water treatment plant at a time representative of normal operating conditions and influent water quality.
2. The owner of a community waterworks or a NTNC that uses a surface water source, a GUDI source, or both with an average treated water TOC of less than 2.0 mg/L for two consecutive years, or less than 1.0 mg/L for one year, may reduce monitoring for both TOC and alkalinity to one paired sample and one source water alkalinity sample per water treatment plant per quarter. The owner shall revert to routine monitoring in the month following the quarter when the annual average treated water TOC is equal to or greater than 2.0 mg/L.
12VAC5-590-375. Lead and copper monitoring.
A. The owners owner of all a community and nontransient noncommunity waterworks waterworks or a NTNC shall monitor for lead and copper in tap water (subsection B of this section), water quality (corrosion) parameters in the distribution system and at entry points (subsection C of this section), and lead and copper in water supplies (subsection D of this section).
B. Monitoring requirements for lead and copper in tap water.
1. Sample site location.
a. By the commissioner determined date determined by the department for commencement of monitoring under subdivision B 4 a of this section, each the owner shall complete a materials evaluation of the distribution system in order to identify a pool of targeted sampling sites that meets the requirements of this subdivision, and that is sufficiently large to ensure that the owner can collect the number of lead and copper tap samples required in subdivision B 3 of this section. All sites from which first draw first-draw samples are collected shall be selected from this pool of targeted sampling sites. Sampling sites may not include faucets that have point-of-use POU devices or point-of-entry treatment POE devices designed to remove inorganic contaminants.
b. When the distribution system evaluation required in subdivision B 1 a of this section is insufficient to locate the requisite number of lead and copper sampling sites that meet the targeting criteria of this section, the owner shall review the sources of information listed below in order in subdivisions B 1 b (1), B 1 b (2), and B 1 b (3) of this section to identify a sufficient number of sampling sites. In addition, the owner shall seek to collect such information where possible in the course of its normal operations (e.g., checking service line materials when reading water meters or performing maintenance activities):
(1) All plumbing codes, permits, and records in the files of the building department or departments that indicate the plumbing materials that are installed within publicly and privately owned structures connected to the distribution system;
(2) All inspections and records of the distribution system that indicate the material composition of the service connections that connect a structure to the distribution system; and
(3) All existing water quality information, which includes the results of all prior analyses of the waterworks or individual structures connected to the waterworks, indicating locations that may be particularly susceptible to high lead or copper concentrations.
c. The sampling sites selected for a community waterworks' sampling pool (tier 1 (Tier 1 sampling sites) shall consist of single family single-family structures that:
(1) Contain copper pipes with lead solder installed between January 1983 and April 1986 or contain lead pipes; or
(2) Are served by a lead service line.
NOTE: When multiple-family residences comprise at least 20% of the structures served by a waterworks, the owner may include these types of structures in the sampling pool.
d. The owner of any a community waterworks with insufficient tier Tier 1 sampling sites shall complete the sampling pool with tier Tier 2 sampling sites consisting of buildings, including multiple-family residences that:
(1) Contain copper pipes with lead solder installed between January 1983 and April 1986 or contain lead pipes; or
(2) Are served by a lead service line.
e. The owner of any a community waterworks with insufficient tier Tier 1 and tier Tier 2 sampling sites shall complete the sampling pool with tier Tier 3 sampling sites, consisting of single family structures that contain copper pipes with lead solder installed before 1983. The owner of a community waterworks with insufficient tier Tier 1, tier Tier 2, and tier Tier 3 sampling sites shall complete the sampling pool with representative sites throughout the distribution system. For the purpose of this subdivision, a representative site is a site in which the plumbing materials used at that site would be commonly found at other sites served by the waterworks.
f. The sampling sites selected for a nontransient noncommunity waterworks (tier 1 NTNC (Tier 1 sampling sites) shall consist of buildings that:
(1) Contain copper pipes with lead solder installed between January 1983 and April 1986 or contain lead pipes; or
(2) Are served by a lead service line.
g. The owner of a nontransient noncommunity waterworks NTNC with insufficient tier Tier 1 sites that meet the targeting criteria in subdivision B 1 f of this section shall complete the sampling pool with sampling sites that contain copper pipes with lead solder installed before 1983. If additional sites are needed to complete the sampling pool, the owner of a nontransient noncommunity waterworks NTNC shall use representative sites throughout the distribution system. For the purpose of this subdivision, a representative site is a site in which the plumbing materials used at that site would be commonly found at other sites served by the waterworks.
h. The owner of any a waterworks whose distribution system contains lead service lines shall draw 50% of the samples the owner collects during each monitoring period from sites that contain lead pipes, or copper pipes with lead solder, and 50% of the samples the owner collects from sites served by a lead service line. Any The owner who cannot identify a sufficient number of sampling sites served by a lead service line shall collect first draw first-draw tap samples from all of the sites identified as being served by such these lines.
2. Sample collection methods.
a. All tap samples for lead and copper, with the exception of lead service line samples collected under 12VAC5-590-405 C 4 and samples collected under subdivision B 2 e of this section, shall be first draw first-draw samples.
b. Each first-draw tap sample for lead and copper shall be one liter in volume, and have stood motionless in the plumbing system of each sampling site for at least six hours, and have been collected without flushing the tap. First draw First-draw samples from residential housing shall be collected from the cold-water kitchen tap or from a bathroom sink tap. First-draw samples from a nonresidential building shall be one liter in volume and shall be collected at an interior tap from which water is typically drawn for consumption. Non-first-draw samples collected in lieu of instead of first-draw samples pursuant to subdivision B 2 e of this section shall be one liter in volume and shall be collected at an interior tap from which water is typically drawn for consumption. First draw First-draw samples may be collected by the owner or the owner may allow residents to collect first draw first-draw samples after instructing the residents of the sampling procedures specified in this subdivision. To avoid problems of residents handling nitric acid, acidification of first draw first-draw samples may be done up to 14 days after the sample is collected. After acidification to resolubilize the metals, the sample must stand in the original container for the time specified in the approved EPA method before the sample can be analyzed. If an owner allows residents to perform sampling, then the owner may not challenge, based on alleged errors in sample collection, the accuracy of sampling results.
c. Each lead service line sample collected pursuant to 12VAC5-590-405 C 4 for the purpose of avoiding replacement shall be one liter in volume and have stood motionless in the lead service line for at least six hours. Lead service line samples shall be collected in one of the following three ways:
(1) At the tap after flushing the volume of water between the tap and the lead service line. The volume of water shall be calculated based on the interior diameter and length of the pipe between the tap and the lead service line;
(2) Tapping directly into the lead service line; or
(3) If the sampling site is a building constructed as a single-family residence, then allowing the water to run until there is a significant change in temperature that would be indicative of water that has been standing in the lead service line.
d. An The owner shall collect each first draw first-draw tap sample from the same sampling site from which the owner collected a previous sample. If, for any reason, the owner cannot gain entry to a sampling site in order to collect a follow-up tap sample, then the owner may collect the follow-up tap sample from another sampling site in the sampling pool as long as the new site meets the same targeting criteria and is within reasonable proximity of the original site.
e. The owner of a nontransient noncommunity waterworks NTNC, or a community waterworks that meets the criteria of 12VAC5-590-405 D 2 e (2) that does not have enough taps that can supply first-draw samples, as defined in subdivision B 2 b of this section, may apply to the district engineer department in writing to substitute non-first-draw samples. If approved by the commissioner department, such owners then an owner shall collect as many first-draw samples from appropriate taps as possible and identify sampling times and locations that would likely result in the longest standing time for the remaining sites.
3. Number of samples.
a. Owners The owner shall collect at least one sample during each monitoring period specified in subdivision B 4 of this section from the number of sites listed in the first column (standard monitoring) of the table in subdivision B 3 c of this section Table 375.1. The owner of a waterworks conducting reduced monitoring under subdivision B 4 d of this section shall collect at least one sample from the number of sites specified in the second column (reduced monitoring) of the table in subdivision B 3 c of this section Table 375.1 during each monitoring period specified in subdivision B 4 d of this section. Such reduced Reduced monitoring sites shall be representative of the sites required for standard monitoring. The commissioner department may specify sampling locations when an owner is conducting reduced monitoring.
b. The owner of a waterworks that has fewer than five drinking water taps that are normally used for human consumption meeting the sample site criteria of subdivision B 1 of this section to reach the required number of sample sites listed in the table in subdivision B 3 c of this section, Table 375.1 shall collect at least one sample from each tap and then shall collect additional samples from those taps on different days during the monitoring period to meet the required number of sites. Alternatively, the commissioner department may allow these owners the owner to collect a number of samples less than the number of sites specified in the table in subdivision B 3 c of this section Table 375.1, provided that 100% of all taps that are normally used for human consumption are sampled. The commissioner must department shall approve this reduction of the minimum number of samples in writing based on a request from the owner or onsite verification by the district engineer designated department representative.
c. The lead and copper tap sample table is as follows:
TABLE 375.1
Tap Samples for Lead and Copper
|
System Size WATERWORKS SIZE (Number of People Served)
|
Number of Sites NUMBER OF SITES (Standard Monitoring)
|
Number of Sites NUMBER OF SITES (Reduced Monitoring)
|
greater Greater than 100,000
|
100
|
50
|
10,001-100,000
|
60
|
30
|
3,301 to 10,000
|
40
|
20
|
501 to 3,300
|
20
|
10
|
101 to 500
|
10
|
5
|
less Less than or equal to 100
|
5
|
5
|
4. Timing of monitoring.
a. Initial tap sampling. The first six-month monitoring period for small (serving less than 3,300 population), medium-size medium (serving 3,301 to 50,000 population), and large waterworks (serving greater than 50,000 population) shall be established by the commissioner department.
(1) Owners The owner of all a large waterworks shall monitor during two consecutive six-month periods.
(2) Owners The owner of all a small and medium-size or a medium waterworks shall monitor during each six-month monitoring period until the waterworks exceeds the lead or copper action level AL and is therefore required to implement the corrosion control treatment requirements under 12VAC5-590-405 A 2, in which case the owner shall continue monitoring in accordance with subdivision B 4 b of this section, or the waterworks meets the lead and copper action levels ALs during two consecutive six-month monitoring periods, in which case the owner may reduce monitoring in accordance with subdivision B 4 d of this section.
b. Monitoring after installation of corrosion control and water supply (source water) source water treatment.
(1) The owner of any a large waterworks that installs optimal corrosion control treatment pursuant to 12VAC5-590-405 A 2 d (4) shall monitor during two consecutive six-month monitoring periods by the date specified in 12VAC5-590-405 A 2 d (5).
(2) The owner of any a small or medium-size a medium waterworks that installs optimal corrosion control treatment pursuant to 12VAC5-590-405 A 2 e (5) shall monitor during two consecutive six-month monitoring periods by the date specified in 12VAC5-590-405 A 2 d e (6).
(3) The owner of any a waterworks that installs source water treatment pursuant to 12VAC5-590-405 B 1 c shall monitor during two consecutive six-month monitoring periods by the date specified in 12VAC5-590-405 B 1 d.
c. Monitoring after the commissioner department specifies water quality parameter values for optimal corrosion control. After the commissioner department specifies the values for water quality control parameters under 12VAC5-590-405 A 1 f, the owner shall monitor during each subsequent six-month monitoring period, with the first monitoring period to begin on the date the commissioner department specifies the optimal values.
d. Reduced monitoring.
(1) The owner of a small or medium-size a medium waterworks that meets the lead and copper action levels ALs during each of two consecutive six-month monitoring periods may reduce the number of samples in accordance with subdivision B 3 of this section, and reduce the frequency of sampling to once per year. The owner of a small or a medium water system waterworks collecting fewer than five samples, as specified in subdivision B 3 b of this section, that meets the lead and copper action levels ALs during each of two consecutive six-month monitoring periods may reduce the frequency of sampling to once per year. In no case may the owner reduce the number of samples required below the minimum of one sample per available tap. This sampling shall begin during the calendar year immediately following the end of the second consecutive six-month monitoring period.
(2) The owner of any a waterworks that meets the lead action level AL and maintains the range of values for the water quality control parameters reflecting optimal corrosion control treatment specified by the commissioner department under 12VAC5-590-405 A 1 f during each of two consecutive six-month monitoring periods may reduce the frequency of monitoring to once per year and to reduce the number of lead and copper samples in accordance with subdivision B 3 of this section if the owner receives written approval from the commissioner department. This sampling shall begin during the calendar year immediately following the end of the second consecutive six-month monitoring period. The commissioner must review department shall evaluate monitoring, treatment, and other relevant information submitted by the owner in accordance with 12VAC5-590-530 F 12VAC5-590-532 and must shall notify the owner in writing when a determination is made that the owner is eligible to commence reduced monitoring pursuant to this subdivision. The commissioner must review, department shall evaluate and, where appropriate, revise his the determination when the owner submits new monitoring or treatment data, or when other data relevant to the number and frequency of tap sampling becomes available.
(3) The owner of a small or medium-size a medium waterworks that meets the lead and copper action levels ALs during three consecutive years of monitoring may reduce the frequency of monitoring for lead and copper from annually to once every three years. The owner of any a waterworks that meets the lead action level AL and maintains the range of values for the water quality control parameters reflecting optimal corrosion control treatment specified by the commissioner department under 12VAC5-590-405 A 1 f during three consecutive years of monitoring may reduce the frequency of monitoring from annually to once every three years if the owner receives written approval from the commissioner department. Samples collected once every three years shall be collected no later than every third calendar year. The commissioner must review, department shall evaluate monitoring, treatment, and other relevant information submitted by the owner in accordance with 12VAC5-590-530 F 12VAC5-590-532 and must shall notify the owner in writing when a determination is made that the owner is eligible to commence reduced monitoring pursuant to this subdivision. The commissioner must review, department shall evaluate and where appropriate, revise his the determination when the owner submits new monitoring or treatment data, or when other data relevant to the number and frequency of tap sampling becomes available.
(4) The owner of a waterworks that reduces the number and frequency of sampling shall collect these samples from representative sites included in the pool of targeted sampling sites identified in subdivision B 1 of this section. Owners The owner sampling annually or less frequently shall conduct the lead and copper tap sampling during the months of June, July, August, or September. For a nontransient noncommunity waterworks NTNC that does not operate during the months of June through September, the commissioner department shall designate an alternate monitoring period that represents a time of normal operation for the waterworks. This sampling shall begin in the calendar year immediately following the end of the second consecutive six-month monitoring period of for the owners owner initiating annual monitoring, and during the three-year period following the end of the third consecutive calendar year of annual monitoring for the owners owner initiating triennial monitoring.
(5) The owner of any a waterworks that demonstrates for two consecutive six-month monitoring periods that the tap water lead level computed under 12VAC5-590-385 C is less than or equal to 0.005 mg/L and the tap water copper level computed under 12VAC5-590-385 C is less than or equal to 0.65 mg/L may reduce the number of samples in accordance with subdivision B 3 of this section and reduce the frequency of sampling to once every three calendar years.
(6) The owner of a small or medium-size a medium waterworks subject to reduced monitoring that exceeds the lead or copper action level AL shall resume sampling in accordance with subdivision B 4 c of this section and collect the number of samples specified for standard monitoring under subdivision B 3 of this section. Such The owner shall also conduct water quality parameter monitoring in accordance with subdivision C 2, 3, or 4 subdivisions C 2, C 3, and C 4 of this section (as appropriate) during the monitoring period in which the action level AL is exceeded. The owner of any such a waterworks may resume annual monitoring for lead and copper at the tap at the reduced number of sites specified in subdivision B 3 of this section after it has completed two subsequent consecutive six-month rounds of monitoring that meet the criteria of subdivision B 4 d (1) of this section or may resume triennial monitoring for lead and copper at the reduced number of sites after it demonstrates through subsequent rounds of monitoring that it meets the criteria of either subdivision B 4 d (3) or B 4 d (5) of this section.
(7) The owner of any a waterworks subject to the reduced monitoring frequency that fails to meet the lead action level ALs during any four-month monitoring period or that fails to operate at or above the minimum value or within the range of values for the water quality parameters specified by the commissioner department under 12VAC5-590-405 A 1 f for more than nine days in any six-month period specified in subdivision C 4 of this section shall conduct tap water sampling for lead and copper at the frequency specified in subdivision B 4 c of this section, collect the number of samples specified for standard monitoring under subdivision B 3 of this section, and resume monitoring for water quality parameters within the distribution system in accordance with subdivision C 4 of this section. This standard tap water sampling shall begin no later than the six-month period beginning January 1 of the calendar year following the lead action level AL exceedance or water quality parameter excursion. The owner of such a waterworks may resume reduced monitoring for lead and copper at the tap and for water quality parameters within the distribution system under the following conditions:
(a) The owner may resume annual monitoring for lead and copper at the tap at the reduced number of sites specified in subdivision B 3 of this section after completion of two subsequent six-month rounds of monitoring that meet the criteria of subdivision B 4 d 2 (2) of this section and the owner has received written approval from the commissioner department that it is appropriate to resume reduced monitoring on an annual frequency. This sampling shall begin during the calendar year immediately following the end of the second consecutive six-month monitoring period.
(b) The owner may resume triennial monitoring for lead and copper at the tap at the reduced number of sites after demonstration through subsequent rounds of monitoring that it meets the criteria of either subdivision B 4 d (3) or B 4 d (5) of this section and the owner has received written approval from the commissioner department that it is appropriate to resume triennial monitoring.
(c) The owner may reduce the number of water quality parameter tap water samples required in accordance with subdivision C 5 a of this section and the frequency with which it collects such these samples in accordance with subdivision C 5 b of this section. The owner of such a waterworks may not resume triennial monitoring for water quality parameters at the tap until it demonstrates, in accordance with the requirements of subdivision C 5 b of this section, that it has requalified for triennial monitoring.
(8) The owner of any a waterworks subject to a reduced monitoring frequency under subdivision B 4 d of this section shall notify the district engineer department in writing in accordance with 12VAC5-590-530 F 1 c and 12VAC5-590-532 of any upcoming long-term change in the treatment or addition of a new water source water as described in this section. The commissioner must review department shall evaluate and approve the addition of a new water source water or long-term change in the water treatment before it is implemented by the owner. The commissioner department may require the owner to resume sampling in accordance with subdivision B 4 c of this section and collect the number of samples specified for standard monitoring under subdivision B 3 of this section or take other appropriate steps such as increased water quality parameter monitoring or re-evaluation of its corrosion control treatment given the potentially different water quality considerations.
5. Additional monitoring by owner. The results of any monitoring conducted in addition to the minimum requirements of this section shall be considered by the owner and the commissioner department in making any determinations (i.e., calculating the 90th percentile lead or copper level) under 12VAC5-590-385 C.
6. Invalidation of lead or copper tap water samples. A sample invalidated under this subdivision does not count toward determining lead or copper 90th percentile levels under 12VAC5-590-385 C or toward meeting the minimum monitoring requirements of subdivision B 3 of this section.
a. The commissioner department may invalidate a lead or copper tap water sample if at least one of the following conditions is met.:
(1) The laboratory establishes that improper sample analysis caused erroneous results.
(2) The commissioner department determines that the sample was taken collected from a site that did not meet the site selection criteria of this section.
(3) The sample container was damaged in transit.
(4) There is substantial reason to believe that the sample was subject to tampering.
b. The owner shall report the results of all samples to the district engineer department and all supporting documentation for samples the owner believes should be invalidated.
c. To invalidate a sample under subdivision B 6 a of this section, the decision and the rationale for the decision shall be documented in writing. The commissioner department may not invalidate a sample solely on the grounds that a follow-up sample result is higher or lower than that of the original sample.
d. The owner shall collect a replacement samples sample for any samples a sample invalidated under this section if, after the invalidation of one or more samples, the owner has too few samples to meet the minimum requirements of subdivision B 3 of this section. Any such A replacement samples sample shall be taken collected as soon as possible, but no later than 20 days after the date the [ commissioner department ] invalidates the sample or by the end of the applicable monitoring period, whichever occurs later. Replacement samples taken collected after the end of the applicable monitoring period shall not also be used to meet the monitoring requirements of a subsequent monitoring period. The replacement samples shall be taken collected at the same locations as the invalidated samples or, if that is not possible, at locations other than those already used for sampling during the monitoring period.
7. Monitoring waivers for small waterworks. The owner of any a small waterworks that meets the criteria of this subdivision may apply to the commissioner department to reduce the frequency of monitoring for lead and copper to once every nine years (i.e., a full waiver) if the owner meets all of the materials criteria specified in subdivision B 7 a of this section and all of the monitoring criteria specified in subdivision B 7 b of this section. The owner of any a small waterworks that meets the criteria in subdivisions B 7 a and B 7 b of this section only for lead, or only for copper, may apply to the commissioner department for a waiver to reduce the frequency of tap water monitoring to once every nine years for that contaminant only (i.e., a partial waiver).
a. Materials criteria. The owner shall demonstrate that the distribution system and service lines and all drinking water supply plumbing and plumbing connected to the waterworks, including plumbing conveying drinking water within all residences and buildings connected to the waterworks, are free of lead-containing materials or copper-containing materials, as those terms are defined in this subdivision, as follows:
(1) Lead. To qualify for a full waiver, or a waiver of the tap water monitoring requirements for lead (i.e., a lead waiver), the owner shall provide certification and supporting documentation to the commissioner department that the waterworks is free of all lead-containing materials, as follows:
(a) It contains no plastic pipes that contain lead plasticizers, or plastic service lines that contain lead plasticizers; and
(b) It is free of lead service lines, lead pipes, lead soldered pipe joints, and leaded brass or bronze alloy fittings and fixtures, unless such fittings and fixtures meet the specifications of any standard established pursuant to 42 USC § 300g-6(e) (SDWA § 1417(e)).
(b) Solders and flux contain no more than 0.2% lead; and
(c) The weighted average of wetted surface of pipes, pipe fittings, plumbing fittings, and plumbing fixtures contain no more than 0.25% lead.
(2) Copper. To qualify for a full waiver, or a waiver of the tap water monitoring requirements for copper (i.e., a copper waiver), the owner shall provide certification and supporting documentation to the commissioner department that the waterworks contains no copper pipes or copper service lines.
b. Monitoring criteria for waiver issuance. The owner shall have completed at least one six-month round of standard tap water monitoring for lead and copper at sites approved by the commissioner department and from the number of sites required by subdivision B 3 of this section and demonstrate that the 90th percentile levels for any and all rounds of monitoring conducted since the owner became free of all lead-containing or copper-containing materials, as appropriate, meet the following criteria:
(1) Lead levels. To qualify for a full waiver, or a lead waiver, the owner shall demonstrate that the 90th percentile lead level does not exceed 0.005 mg/L.
(2) Copper levels. To qualify for a full waiver, or a copper waiver, the owner shall demonstrate that the 90th percentile copper level does not exceed 0.65 mg/L.
c. Commissioner Department approval of waiver application. The commissioner department shall notify the owner of the waiver determination, in writing, setting forth the basis of his the decision and any condition of the waiver. As a condition of the waiver, the commissioner department may require the owner to perform specific activities (e.g., limited monitoring, periodic outreach to customers to remind them to avoid installation of materials that might void the waiver) to avoid the risk of lead or copper concentration of concern in tap water. The owner of a small waterworks shall continue monitoring for lead and copper at the tap as required by subdivisions B 4 a through B 4 d of this section, as appropriate, until it receives written notification from the commissioner department that the waiver has been approved.
d. Monitoring frequency for owners with waivers.
(1) An The owner with a full waiver shall conduct tap water monitoring for lead and copper in accordance with subdivision B 4 d (4) of this section at the reduced number of sampling sites identified in subdivision B 3 of this section at least once every nine years and provide the materials certification specified in subdivision B 7 a of this section for both lead and copper to the commissioner department along with the monitoring results. Samples collected every nine years shall be collected no later than every ninth calendar year.
(2) An The owner with a partial waiver shall conduct tap water monitoring for the waived contaminant in accordance with subdivision B 4 d (4) of this section at the reduced number of sampling sites specified in subdivision B 3 of this section at least once every nine years and provide the materials certification specified in subdivision B 7 a of this section pertaining to the waived contaminant along with the monitoring results. Such an The owner also shall continue to monitor for the nonwaived contaminant in accordance with requirements of subdivisions B 4 a through B 4 d of this section, as appropriate.
(3) Any The owner with a full or partial waiver shall notify the district engineer department in writing in accordance with 12VAC5-590-530 F 1 c 12VAC5-590-532 B 3 of any upcoming long-term change in the treatment or addition of a new source water, as described in that section 12VAC5-590-532. The commissioner must review department shall evaluate and approve the addition of a new source water or a long-term change in water treatment before it is implemented by the owner. The commissioner department has the authority to require the owner to add or modify waiver conditions (e.g., require recertification that the waterworks is free of lead-containing or copper-containing materials; require additional round or rounds of monitoring), if it deems such these modifications are necessary to address treatment or source water changes at the waterworks.
(4) If an owner with a full or partial waiver becomes aware that it is no longer free of lead-containing or copper-containing materials, as appropriate, (e.g., as a result of new construction or repairs), then the owner shall notify the district engineer department in writing no later than 60 days after becoming aware of such a the change.
e. Continued eligibility. If the owner continues to satisfy the requirements of subdivision B 7 d of this section, then the waiver will be renewed automatically, unless any of the conditions listed in subdivisions subdivision B 7 e (1), B 7 e (2), or B 7 e (3) of this section occurs. An The owner whose waiver has been revoked may reapply for a waiver at such time as it when the owner again meets the appropriate materials and monitoring criteria of subdivisions B 7 a and B 7 b of this section.
(1) A waterworks with a full waiver or a lead waiver no longer satisfies the materials criteria of subdivision B 7 a (1) of this section or has a 90th percentile lead level greater than 0.005 mg/L.
(2) A waterworks with a full waiver or a copper waiver no longer satisfies the materials criteria of subdivision B 7 a (2) of this section or has a 90th percentile copper level greater than 0.65 mg/L.
(3) The commissioner department notifies the owner, in writing, that the waiver has been revoked, setting forth the basis of the decision.
f. Requirements following waiver revocation. A waterworks whose full or partial waiver has been revoked by the commissioner department is subject to the corrosion control treatment and lead and copper tap water monitoring requirements, as follows:
(1) If the waterworks exceeds the lead or copper action level AL, then the owner shall implement corrosion control treatment in accordance with the deadlines specified in 12VAC5-590-405 A 2 e and any other applicable requirements of this section.
(2) If the waterworks meets both the lead and the copper action level ALs, then the owner shall monitor for lead and copper at the tap no less frequently than once every three years using the reduced number of sample sites specified in subdivision B 3 of this section.
g. Pre-existing waivers. Waivers for small waterworks approved by the commissioner department in writing prior to before April 11, 2000, shall remain in effect under the following conditions:
(1) If the waterworks has demonstrated that it is both free of lead-containing and copper-containing materials, as required by subdivision B 7 a of this section and that its 90th percentile lead levels and 90th percentile copper levels meet the criteria of subdivision B 7 b of this section, then the waiver remains will remain in effect so long as the owner continues to meet the waiver eligibility criteria of subdivision B 7 e of this section. The first round of tap water monitoring conducted pursuant to subdivision B 7 d of this section shall be completed no later than nine years after the last time the owner has monitored for lead and copper at the tap.
(2) If the waterworks has met the materials criteria of subdivision B 7 a of this section but has not met the monitoring criteria of subdivision B 7 b of this section, then the owner shall conduct one six-month round of standard tap water monitoring for lead and copper at sites approved by the commissioner department demonstrating that it meets the criteria of subdivision B 7 b of this section. Thereafter, the waiver shall remain in effect as long as the owner meets the continued eligibility criteria of subdivision B 7 e of this section. The first round of tap water monitoring conducted pursuant to subdivision B 7 d of this section shall be completed no later than nine years after the round of monitoring conducted pursuant to subdivision B 7 b of this section.
C. Monitoring requirements for water quality parameters. The owners of all large waterworks and all small and medium-size medium waterworks that exceed the lead or copper action level AL shall monitor for water quality parameters in addition to lead and copper in accordance with this section.
1. General requirements.
a. Sample collection methods.
(1) Tap samples shall be representative of water quality throughout the distribution system taking into account the number of persons served, the different sources of water, the different treatment methods employed by the waterworks, and seasonal variability. Tap sampling under this section is not required to be conducted at taps targeted for lead and copper sampling under subdivision B 1 of this section. Owners The owner may find it convenient to conduct tap sampling for water quality parameters at sites approved for coliform sampling.
(2) Samples collected at the entry point or points to the distribution system shall be from locations representative of each source water after treatment. If a waterworks draws water from more than one source water and the sources source waters are combined before distribution, then the owner shall sample at an entry point to the distribution system during periods of normal operating conditions (i.e., when water is representative of all sources source waters being used).
b. Number of samples.
(1) Owners The owner shall collect two tap samples from the standard monitoring number of sites given in Table 375.2 for applicable water quality parameters during each monitoring period specified under subdivision subdivisions C 2 through C 5 of this section from the following number of sites.
TABLE 375.2
Water Quality Monitoring for Lead and Copper
|
|
NUMBER OF SITES FOR WATER QUALITY PARAMETERS
|
System Size WATERWORKS SIZE
(Number of People Served)
|
Number of Sites for Water Quality Parameters STANDARD MONITORING
|
REDUCED MONITORING
|
greater Greater than 100,000
|
25
|
10
|
10,001-100,000
|
10
|
7
|
3,301 to 10,000
|
3
|
3
|
501 to 3,300
|
2
|
2
|
101 to 500
|
1
|
1
|
less Less than or equal to 100
|
1
|
1
|
(2) Except as provided in subdivision C 3 c of this section, owners the owner shall collect two samples for each applicable water quality parameter at each entry point to the distribution system during each monitoring period specified in subdivision C 2 of this section. During each monitoring period specified in subdivision subdivisions C 3 through, C 4, and C 5 of this section, owners the owner shall collect one sample for each applicable water quality parameter at each entry point to the distribution system.
2. Initial sampling. The owners owner of all a large waterworks shall measure the applicable water quality parameters as specified below at taps and at each entry point to the distribution system during each six-month monitoring period specified in subdivision B 4 a of this section. The owners owner of all a small and medium-size or a medium waterworks shall measure the applicable water quality parameters at the locations specified below during each six-month monitoring period specified in subdivision B 4 a of this section during which the waterworks exceeds the lead or copper action level AL.
a. At taps:
(1) pH;
(2) Alkalinity;
(3) Orthophosphate, when an inhibitor containing a phosphate compound is used;
(4) Silica, when an inhibitor containing a silicate compound is used;
(5) Calcium;
(6) Conductivity; and
(7) Water temperature.
b. At each entry point to the distribution system: all of the applicable parameters listed in subdivision C 2 a of this section.
3. Monitoring after installation of corrosion control. The owner of any a large waterworks which that installs optimal corrosion control treatment pursuant to 12VAC5-590-405 A 2 d (4) shall measure the water quality parameters at the locations and frequencies specified below during each six-month monitoring period specified in subdivision B 4 b (1) of this section. The owner of any a small or medium-size a medium waterworks that installs optimal corrosion control treatment shall conduct such monitoring during each six-month monitoring period specified in subdivision B 4 b (2) of this section in which the waterworks exceeds the lead or copper action level AL.
a. At taps, two samples for:
(1) pH;
(2) Alkalinity;
(3) Orthophosphate, when an inhibitor containing a phosphate compound is used;
(4) Silica, when an inhibitor containing a silicate compound is used; and
(5) Calcium, when calcium carbonate stabilization is used as part of corrosion control.
b. Except as provided in subdivision C 3 c of this section, at each entry point to the distribution system, at least one sample no less frequently than every two weeks (bi-weekly) (biweekly) for:
(1) pH;
(2) When alkalinity is adjusted as part of optimal corrosion control, a reading of the dosage rate of the chemical used to adjust the alkalinity, and the alkalinity concentration; and
(3) When a corrosion inhibitor is used as part of optimal corrosion control, a reading of the dosage rate of the inhibitor used, and the concentration of orthophosphate or silica (whichever is applicable).
c. The owner of any a groundwater waterworks system may limit entry point sampling described in subdivision C 3 b of this section to those entry points that are representative of water quality and treatment conditions throughout the waterworks. If water from untreated ground water groundwater sources mixes with water from treated ground water groundwater sources, then the owner shall monitor for water quality parameters both at representative entry points receiving treatment and representative entry points receiving no treatment. Prior to Before the start of any monitoring under this subdivision, the owner shall provide to the commissioner department written information identifying the selected entry points and documentation, including information on seasonal variability, sufficient to demonstrate that the sites are representative of water quality and treatment conditions throughout the waterworks.
4. Monitoring after the commissioner department specifies water quality parameter values for optimal corrosion control. After the commissioner department specifies the values for applicable water quality control parameters reflecting optimal corrosion control treatment under 12VAC5-590-405 A 1 f, the owners owner of all a large waterworks shall measure the applicable water quality parameters in accordance with subdivision C 3 of this section and determine compliance with the requirements of 12VAC5-590-405 A 1 g every six months with the first six-month period to begin on either January 1 or July 1, whichever comes first, after the commissioner department specifies the optimal values under 12VAC5-590-405 A 1 f. The owner of any a small or medium-size a medium waterworks shall conduct such monitoring during each six-month monitoring period specified in this subdivision in which the waterworks exceeds the lead or copper action level AL. For the owner of any such a small and medium-size or a medium waterworks that is subject to a reduced monitoring frequency pursuant to subdivision B 4 d of this section at the time of the action level AL exceedance, the start of the applicable six-month period under this subdivision shall coincide with the start of the applicable monitoring period under subdivision B 4 d of this section. Compliance with the commissioner-designated department-designated optimal water quality parameter values shall be determined as specified under 12VAC5-590-405 A 1 g.
5. Reduced monitoring.
a. The owner of any a waterworks that maintains the range of values for the water quality parameters reflecting optimal corrosion control treatment during each of two consecutive six-month monitoring periods under subdivision C 4 of this section shall continue monitoring at the entry point or points to the distribution system as specified in subdivision C 3 b of this section. The owner of such the waterworks may collect two tap samples for applicable water quality parameters from the following reduced number of sites during each six-month monitoring period shown in Table 375.2.
Size of Water System (Number of People Served)
|
Reduced Number of WQP Monitoring Sites
|
greater than 100,000
|
10
|
10,001 to 100,000
|
7
|
3,301 to 10,000
|
3
|
501 to 3,300
|
2
|
101 to 500
|
1
|
less than or equal to 100
|
1
|
b. The owner of any a waterworks that maintains the range of values for the water quality parameters reflecting optimal corrosion control treatment specified by the commissioner department under 12VAC5-590-405 A 1 f during three consecutive years of monitoring may reduce the frequency with which the owner collects the number of tap samples for applicable water quality parameters specified in subdivision C 5 of this section from every six months to annually. This sampling begins during the calendar year immediately following the end of the monitoring period in which the third consecutive year of six-month monitoring occurs. The owner of any a waterworks that maintains the range of values for the water quality parameters reflecting optimal corrosion control treatment specified by the commissioner department under 12VAC5-590-405 A 1 f during three consecutive years of annual monitoring under this subdivision may reduce the frequency with which it collects the number of tap samples for applicable water quality parameters specified in subdivision C 5 a of this section from annually to every three years. This sampling begins during the calendar year immediately following the end of the monitoring period in which the third consecutive year of six-month monitoring occurs.
c. The owner of a waterworks may reduce the frequency with which tap samples are collected for applicable water quality parameters specified in subdivision C 5 a of this section to every three years if the owner demonstrates during two consecutive monitoring periods that the tap water lead level at the 90th percentile is less than or equal to the PQL for lead (0.005 mg/L), that the tap water copper level at the 90th percentile is less than or equal to 0.65 mg/L for copper, and that the owner also has maintained the range of values for water quality parameters reflecting optimal corrosion control treatment specified by the commissioner department under 12VAC5-590-405 A 1 f. Monitoring conducted every three years shall be done no later than every third calendar year.
d. The owner of a waterworks that conducts sampling annually shall collect these samples evenly throughout the year so as to reflect seasonal variability.
e. The owner of any a waterworks subject to the reduced monitoring frequency that fails to operate at or above the minimum value or within the range of values for the water quality parameters specified by the commissioner department under 12VAC5-590-405 A 1 f for more than nine days in any six-month period specified in 12VAC5-590-405 A 1 g shall resume distribution system tap water sampling in accordance with the number and frequency requirements in subdivision C 4 of this section. Such an The owner may resume annual monitoring for water quality parameters at the tap at the reduced number of sites specified in subdivision C 5 of this section after completion of two subsequent consecutive six-month rounds of monitoring that meet the criteria of that subdivision or may resume triennial monitoring for water quality parameters at the tap at the reduced number of sites after demonstration through subsequent rounds of monitoring that the criteria of either subdivision C 5 b or C 5 c of this section has been met.
6. Additional monitoring by owners. The results of any monitoring conducted in addition to the minimum requirements of this section shall be considered by the owner and the commissioner department in making any determinations under this section or 12VAC5-590-405 A 1.
D. Monitoring requirements for lead and copper in water supplies (source water).
1. Sample location, collection methods, and number of samples.
a. The owner of a waterworks that fails to meet the lead or copper action level AL on the basis of tap samples collected in accordance with subsection A of this section shall collect lead and copper water supply source water samples in accordance with the following requirements regarding sample location, number of samples, and collection methods:
(1) The owner of a waterworks served by groundwater sources shall take collect a minimum of one sample at every entry point to the distribution system that is representative of each well after treatment (hereafter called a sampling point). The owner shall take collect one sample at the same sampling point unless conditions make another sampling point more representative of each source water or water treatment plant.
(2) The owner of a waterworks served by surface water sources shall take collect a minimum of one sample at every entry point to the distribution system after any application of treatment or in the distribution system at a point that is representative of each source after treatment (hereafter called a sampling point). The owner shall take collect each sample at the same sampling point unless conditions make another sampling point more representative of each source water or water treatment plant. Note that for the purpose of this subdivision, a waterworks served by a surface water source includes waterworks served by a combination of surface water and ground groundwater sources.
(3) If a waterworks draws water from more than one source water and the sources source waters are combined before distribution, then the owner shall collect samples at an entry point to the distribution system during periods of normal operating conditions (i.e., when water is representative of all sources source waters being used).
(4) The commissioner department may reduce the total number of samples that must be analyzed by allowing the use of compositing. Compositing of samples shall be done by certified laboratory personnel. Composite samples from a maximum of five samples are allowed, provided that if the lead concentration in the composite sample is greater than or equal to 0.001 mg/L or the copper concentration is greater than or equal to 0.160 mg/L, then either a follow-up sample shall be collected and analyzed within 14 days at each sampling point included in the composite; or if duplicates of or sufficient quantities from the original samples from each sampling point used in the composite are available, then the owner may use these instead of resampling.
b. Where the results of sampling indicate an exceedance of maximum permissible water supply source water levels established under 12VAC5-590-405 B 4, the commissioner department may require that one additional sample be collected as soon as possible after the initial sample was taken collected (but not to exceed two weeks) at the same sampling point. If a commissioner required confirmation sample required by the department is taken collected for lead or copper, then the results of the initial and confirmation sample shall be averaged in determining compliance with the commissioner-specified department-specified maximum permissible levels. Any A sample value below the method detection limit MDL shall be considered to be zero. Any A value above the method detection limit MDL but below the PQL shall either be considered as the measured value or be considered one-half the PQL. The PQL for lead is equal to 0.005 mg/L, and the PQL for copper is equal to 0.050 mg/L.
2. Monitoring frequency after a waterworks exceeds a tap action level AL. The owner of any a waterworks which that exceeds the lead or copper action level AL at the tap shall collect one water supply source water sample from each entry point to the distribution system no later than six months after the end of the monitoring period during which the lead or copper action level AL was exceeded. For monitoring periods that are annual or less frequent, the end of the monitoring period is September 30 of the calendar year in which the sampling occurs, or if the commissioner department has established an alternate monitoring period, the last day of that period.
3. Monitoring frequency after installation of water supply source water treatment. The owner of any a waterworks that installs water supply source water treatment pursuant to 12VAC5-590-405 B 1 c shall collect an additional source water supply sample from each entry point to the distribution system during two consecutive six-month monitoring periods by the deadline specified in 12VAC5-590-405 B 1 d.
4. Monitoring frequency after the commissioner department specifies maximum permissible water supply source water lead and copper levels or determines that water supply source water treatment is not needed.
a. An The owner shall monitor at the frequency specified below in subdivisions D 4 a (1) and D 4 a (2) of this section in cases where the commissioner department specifies maximum permissible water supply source water lead and copper levels under 12VAC5-590-405 B 1 e or determines that the owner is not required to install water supply source water treatment under 12VAC5-590-405 B 2 b.
(1) The owner of a waterworks using only groundwater shall collect samples once during the three-year compliance period in effect when the applicable commissioner department determination under subdivision D 4 a of this section is made. Owners of such waterworks The owner shall collect samples once during each subsequent compliance period. Triennial samples shall be collected every third calendar year.
(2) The owner of a waterworks using surface water (or a combination of surface water and groundwater) shall collect samples once during each year, the first annual monitoring period to begin during the year in which the applicable commissioner department determination is made under subdivision D 4 a of this section.
b. An The owner is not required to conduct water supply source water sampling for lead or copper if the waterworks meets the action level AL for the specific contaminant in tap water samples during the entire water supply source water sampling period applicable to the waterworks under subdivision D 4 a (1) or D 4 a (2) of this section.
5. Reduced monitoring frequency.
a. The owner of a waterworks using only groundwater may reduce the monitoring frequency for lead and copper in water supplies source waters to once during each nine-year compliance cycle provided that the samples are collected no later than every ninth calendar year and if the owner meets one of the following criteria:
(1) The owner demonstrates that the finished drinking water entering the distribution system has been maintained below the maximum permissible lead and copper concentrations specified by the commissioner department under 12VAC5-590-405 B 1 e during at least three consecutive compliance periods under subdivision D 4 a of this section; or
(2) The commissioner department has determined that water supply source water treatment is not needed and the owner demonstrates that, during the last three consecutive compliance periods in which sampling was conducted under subdivision D 4 a of this section, the concentration of lead in the water supply source water was less than or equal to 0.005 mg/L and the concentration of copper in the water supply source water was less than or equal to 0.65 mg/L.
b. The owner of a waterworks using surface water (or a combination of surface and ground waters) water and groundwater sources) may reduce the monitoring frequency for lead and copper in water supplies source waters to once during each nine-year compliance cycle provided that the samples are collected no later than every ninth calendar year and if the owner meets one of the following criteria:
(1) The owner demonstrates that finished drinking water entering the distribution system has been maintained below the maximum permissible lead and copper concentrations specified by the commissioner department under 12VAC5-590-405 B 1 e for at least three consecutive years; or
(2) The commissioner department has determined that water supply source water treatment is not needed and the owner demonstrates that, during the last three consecutive years, the concentration of lead in the water supply source water was less than or equal to 0.005 mg/L and the concentration of copper in the water supply source water was less than or equal to 0.65 mg/L.
c. Owners The owner of a waterworks that uses a new water supply source water is not eligible for reduced monitoring for lead or copper until concentrations in samples collected from the new supply source water during three consecutive monitoring periods are below the maximum permissible lead and copper concentrations specified in 12VAC5-590-405 B 1 e.
12VAC5-590-376. Surface water and GUDI sources treatment monitoring.
A. The owner of a waterworks that uses a surface water source, a GUDI source, or both and provides filtration treatment shall monitor in accordance with this section.
B. Turbidity measurements shall be performed on representative samples of the filtered water every four hours (or more frequently) that the waterworks serves water to the public. The owner may substitute continuous turbidity monitoring for grab sample monitoring if the owner validates the continuous measurement for accuracy on a regular basis using a protocol approved by the department. For a waterworks using slow sand filtration or filtration treatment other than conventional treatment, direct filtration, or diatomaceous earth filtration, the department may reduce the sampling frequency to once per day if the department determines that less frequent monitoring is sufficient to indicate effective filtration performance. For a waterworks serving 500 or fewer persons, the department may reduce the turbidity sampling frequency to once per day, regardless of the type of filtration treatment used, if the department determines that less frequent monitoring is sufficient to indicate effective filtration performance.
1. The owner of a waterworks supplied by a surface water source, a GUDI source, or both using conventional filtration treatment or direct filtration shall conduct continuous monitoring of turbidity for each individual filter. The turbidimeter shall be calibrated using the procedure specified by the turbidimeter manufacturer. The owner shall record the results of individual filter turbidity monitoring a minimum of every 15 minutes.
2. If there is a failure in the continuous turbidity monitoring equipment, then the owner shall conduct grab sampling every four hours instead of continuous monitoring but for no more than five working days (for a waterworks serving 10,000 or more persons) or 14 days (for a waterworks serving less fewer than 10,000 persons) following the failure of the equipment.
3. If a waterworks serving fewer than 10,000 persons consists of two or fewer filters, continuous monitoring of the CFE may be used instead of individual filter monitoring.
C. The residual disinfectant concentration of the water entering the distribution system shall be monitored continuously, and the lowest and highest values shall be recorded each day. If there is a failure in the continuous monitoring equipment, then grab sampling every four hours shall be conducted instead of continuous monitoring, but such grab sampling shall be conducted for no more than five working days following the failure of the equipment. The owner of a waterworks serving 3,300 or fewer persons may collect grab samples instead of continuous monitoring on an ongoing basis at the frequencies prescribed in Table 376.1.
1. The day's samples cannot be collected at the same time.
2. The sampling intervals are subject to department's evaluation and approval.
3. If at any time the residual disinfectant concentration falls below 0.2 mg/L in a waterworks using grab sampling instead of continuous monitoring, then the owner shall collect a grab sample every four hours until the residual disinfectant concentration is equal to or greater than 0.2 mg/L.
TABLE 376.1
Grab Sample Monitoring Frequency
|
WATERWORKS SIZE BY POPULATION
|
SAMPLES/DAY
|
500 or less
|
1
|
501 - 1,000
|
2
|
1,000 - 2,500
|
3
|
2,501 - 3,300
|
4
|
D. The residual disinfectant concentration shall be measured at least at the same points in the distribution system and at the same time as total coliform bacteria are sampled, as specified in 12VAC5-590-370 A and 12VAC5-590-380 D, except that the department may allow the owner of a waterworks that uses a groundwater source along with a surface water source, a GUDI source, or both to collect residual disinfectant samples at points other than the total coliform sampling points if the department determines that these points are more representative of treated (disinfected) water quality within the distribution system. Heterotrophic bacteria, measured as HPC as specified in 12VAC5-590-395 A 2 a (3), may be measured instead of residual disinfectant concentration.
E. The following information on the samples collected in the distribution system in conjunction with total coliform monitoring pursuant to 12VAC5-590-395 A 2 shall be reported monthly to the department by the owner:
1. Number of instances where the residual disinfectant concentration is measured;
2. Number of instances where the residual disinfectant concentration is not measured but heterotropic plate count (HPC) is measured;
3. Number of instances where the residual disinfectant concentration is measured but not detected and no HPC is measured;
4. Number of instances where no residual disinfectant concentration is detected and where the HPC is greater than 500/mL;
5. Number of instances where the residual disinfectant concentration is not measured and HPC is greater than 500/mL; and
6. For the current and previous month the waterworks serves water to the public, the value of "V," in percent, in the following formula:
V = [(c + d + e) / (a + b)] X 100
where
a = the value in subdivision E 1 of this section;
b = the value in subdivision E 2 of this section;
c = the value in subdivision E 3 of this section;
d = the value in subdivision E 4 of this section;
e = the value in subdivision E 5 of this section.
12VAC5-590-377. Physical constituent monitoring.
A. Monitoring to determine compliance with the SMCLs for color, odor, pH, and total dissolved solids as specified in Table 340.3 shall be conducted as follows:
1. The owner shall collect one sample at each groundwater source entry point during each compliance period.
2. The owner shall collect one sample annually at each surface water source entry point, in whole or in part.
B. Onsite daily turbidity measurements may be required to be performed on representative samples collected at each entry point for groundwater sources not required to filter, to determine compliance set forth in 12VAC5-590-379 B. The turbidity monitoring requirements for a waterworks required to filter are specified in 12VAC5-590-376 B.
12VAC5-590-378. Radiological monitoring.
A. The location of sampling points, the radionuclides measured in community waterworks, the frequency, and the timing of sampling within each compliance period shall be established or approved by the department. The department may increase required monitoring where necessary to detect variations within the waterworks. Failure to comply with the sampling schedules in this section will require public notification pursuant to 12VAC5-590-540 A 3.
B. The owner of a community waterworks shall conduct monitoring to determine compliance with the PMCLs listed in Table 340.4 and 12VAC5-590-388 in accordance with this section.
1. Monitoring requirements for gross alpha particle activity, radium-226, radium-228, and uranium.
a. The owner shall conduct initial monitoring to determine compliance with the PMCLs listed in Table 340.4 for gross alpha particle activity, radium-226, radium-228, and uranium. For the purposes of monitoring for gross alpha particle activity, radium-226, radium-228, uranium, and beta particle and photon radioactivity in drinking water, "detection limit" is defined as specified in Table 378.1.
(1) Applicability and sampling location for an existing community waterworks or its sources. The owner using groundwater, surface water, or both groundwater and surface water shall sample at every entry point to the distribution system that is representative of all sources being used under normal operating conditions. The owner shall collect each sample at the same entry point unless conditions make another sampling point more representative of each source.
(2) Applicability and sampling location for a new community waterworks or its sources. A new community waterworks or a community waterworks that uses a new source water shall begin to conduct initial monitoring for the new source water within the first quarter after initiating use. The owner shall conduct more frequent monitoring when directed by the department in the event of possible contamination or when changes in the distribution system or treatment processes occur that may increase the concentration of radioactivity in the finished water.
b. Initial monitoring. The owner shall conduct initial monitoring for gross alpha particle activity, radium-226, radium-228, and uranium as follows:
(1) The owner shall collect four consecutive quarterly samples at all entry points.
(2) For gross alpha particle activity, uranium, radium-226, and radium-228 monitoring, the department may waive the final two quarters of initial monitoring for an entry point if the results of the samples from the previous two quarters are below the detection limit as defined by and as specified in Table 378.1.
(3) If the average of the initial monitoring results for an entry point is above the PMCL, then the owner shall collect and analyze quarterly samples at that entry point until the owner has results from four consecutive quarters that are at or below the PMCL, unless the owner enters into another schedule as part of a formal compliance agreement with the department.
c. Reduced monitoring. The department may allow the owner to reduce the future frequency of monitoring from once every three years to once every six or nine years at each entry point, based on the following criteria:
(1) If the average of the initial monitoring results for each contaminant (i.e., gross alpha particle activity, uranium, radium-226, or radium-228) is below the detection limit as specified in Table 378.1, then the owner shall collect and analyze for that contaminant using at least one sample at that entry point every nine years.
(2) For gross alpha particle activity, combined radium, and uranium, if the average of the initial monitoring results for each contaminant is at or above the detection limit as specified in Table 378.1, but at or below half of the PMCL, then the owner shall collect and analyze for that contaminant using at least one sample at that entry point every six years.
(3) For gross alpha particle activity, combined radium, and uranium, if the average of the initial monitoring results for each contaminant is above half the PMCL but at or below the PMCL, then the owner shall collect and analyze at least one sample at that entry point every three years.
(4) The owner shall use the samples collected during the reduced monitoring period to determine the monitoring frequency for subsequent monitoring periods (e.g., if a waterworks entry point is on a nine-year monitoring period, and the sample result is above half the PMCL, then the next monitoring period for that entry point is three years).
(5) If the owner has a monitoring result that exceeds the PMCL while on reduced monitoring, then the owner shall collect and analyze quarterly samples at that entry point until the results from four consecutive quarters are below the PMCL, unless the waterworks enters into another schedule as part of a formal compliance agreement with the department.
d. Compositing. To fulfill quarterly monitoring requirements for gross alpha particle activity, radium-226, radium-228, or uranium, the owner may composite up to four consecutive quarterly samples from a single entry point if analysis is done within a year of the first sample. The department will treat analytical results from the composited sample as the average analytical result to determine compliance with the PMCLs and the future monitoring frequency. If the analytical result from the composited sample is greater than half the PMCL, then the department may direct the owner to collect additional quarterly samples before allowing the owner to sample under a reduced monitoring schedule.
e. A gross alpha particle activity measurement may be substituted for the required radium-226 measurement provided that the measured gross alpha particle activity does not exceed 5 pCi/L. A gross alpha particle activity measurement may be substituted for the required uranium measurement provided that the measured gross alpha particle activity does not exceed 15 pCi/L. The gross alpha measurement shall have a confidence interval of 95% (1.65 σ, where σ is the standard deviation of the net counting rate of the sample) for radium-226 and uranium. When an owner uses a gross alpha particle activity measurement instead of a radium-226 or uranium measurement, the gross alpha particle activity analytical result will be used to determine the future monitoring frequency for radium-226 or uranium. If the gross alpha particle activity result is less than the detection limit as specified in Table 378.1, then half the detection limit will be used to determine compliance and the future monitoring frequency.
2. Monitoring requirements for beta particle and photon radioactivity. To determine compliance with the PMCL in Table 340.4 for beta particle and photon radioactivity, an owner shall monitor at a frequency as follows:
a. The owner (using surface water or groundwater sources) designated by the department as vulnerable shall sample for beta particle and photon radioactivity. The owner shall collect quarterly samples for beta emitters and annual samples for tritium and strontium-90 at each entry point to the distribution system, beginning within one quarter after being notified by the department. A waterworks already designated by the department shall continue to sample until the department evaluates and either reaffirms or removes the designation.
(1) If the gross beta particle activity minus the naturally occurring potassium-40 beta particle activity at an entry point has an RAA (computed quarterly) less than or equal to 50 pCi/L (screening level), then the department may reduce the frequency of monitoring at that entry point to once every three years. The owner shall collect all samples required in subdivision B 2 a of this section during the reduced monitoring period.
(2) For a waterworks in the vicinity of a nuclear facility, the department may allow the owner to utilize environmental surveillance data collected by the nuclear facility instead of monitoring at the waterworks entry point, where the department determines the data is applicable to a particular waterworks. In the event that there is a release from a nuclear facility, the owner who is using surveillance data shall begin monitoring at the waterworks entry point in accordance with subdivision B 2 a of this section.
b. The owner (using a surface water, a groundwater source, or both) designated by the department as utilizing waters contaminated by effluents from nuclear facilities shall sample for beta particle and photon radioactivity. The owner shall collect quarterly samples for beta emitters and iodine-131 and annual samples for tritium and strontium-90 at each entry point to the distribution system, beginning within one quarter after being notified by the department. The owner of a waterworks already designated by the department as using waters contaminated by effluents from nuclear facilities shall continue to sample until the department evaluates and either reaffirms or removes the designation.
(1) Quarterly monitoring for gross beta particle activity shall be based on the analysis of monthly samples or the analysis of a composite of three monthly samples. The former procedure, analysis of monthly samples, is recommended.
(2) For iodine-131, a composite of five consecutive daily samples shall be analyzed once each quarter. As directed by the department, more frequent monitoring shall be conducted when iodine-131 is identified in the finished water.
(3) Annual monitoring for strontium-90 and tritium shall be conducted by means of the analysis of a composite of four consecutive quarterly samples or analysis of four quarterly samples. The latter procedure, analysis of monthly samples, is recommended.
(4) If the gross beta particle activity minus the naturally occurring potassium-40 beta particle activity at a sampling point has an RAA (computed quarterly) less than or equal to 15 pCi/L (screening level), then the department may reduce the frequency of monitoring at that sampling point to every three years. The owner shall collect all samples required in subdivision B 2 b of this section during the reduced monitoring period.
(5) For a waterworks in the vicinity of a nuclear facility, the department may allow the owner to utilize environmental surveillance data collected by the nuclear facility instead of the monitoring at the waterworks entry point, where the department determines the data is applicable to a particular waterworks. In the event that there is a release from a nuclear facility, the owner who is using surveillance data shall begin monitoring at the waterworks entry point in accordance with subdivision B 2 b of this section.
c. The owner of a waterworks designated by the department to monitor for beta particle and photon radioactivity cannot apply to the department for a waiver from the monitoring frequencies specified in subdivision B 2 a or B 2 b of this section.
d. The owner may analyze for naturally occurring potassium-40 beta particle activity from the same or equivalent sample used for the gross beta particle activity analysis. The owner is allowed to subtract the potassium-40 beta particle activity value from the total gross beta particle activity value to determine if the screening level is exceeded. The potassium-40 beta particle activity shall be calculated by multiplying elemental potassium concentrations (in mg/L) by a factor of 0.82.
e. If the gross beta particle activity minus the naturally occurring potassium-40 beta particle activity exceeds the appropriate screening level, then an analysis of the sample shall be performed to identify the major radioactive constituents present in the sample and the appropriate doses shall be calculated and summed to determine compliance with the PMCL for beta particles and photon radioactivity. Doses shall also be calculated and combined for measured levels of tritium and strontium to determine compliance.
f. The owner shall monitor monthly at each entry point that exceeds the PMCLs listed in Table 340.4 beginning the month after the exceedance occurs. The owner shall continue monthly monitoring until the waterworks has established, by a rolling average of three monthly samples, that the PMCL is being met. The owner who establishes that the PMCL is being met shall return to quarterly monitoring until the requirements set forth in subdivision B 2 a (1) or B 2 b (4) of this section are met.
3. General monitoring requirements for radionuclides.
a. The department may require more frequent monitoring than specified in subdivisions B 1 and B 2 of this section or may require confirmation samples at the department's discretion. The results of the initial and confirmation samples shall be averaged for use in compliance determinations.
b. The owner shall monitor at the time designated by the department during each compliance period.
c. The department has the discretion to delete results of obvious sampling or analytic errors.
d. Table 378.1 provides the minimum detection limits for radiological analyses.
TABLE 378.1
Minimum Detection Limits for Radiological Analyses
|
CONTAMINANT
|
DETECTION LIMIT (pCi/L unless otherwise noted)
|
Gross alpha
|
3
|
Gross beta
|
4
|
Cesium-134
|
10
|
Iodine-131
|
1
|
Radium-226
|
1
|
Radium 228
|
1
|
Strontium-89
|
10
|
Strontium-90
|
2
|
Tritium
|
1,000
|
Uranium
|
1 (µg/L)
|
12VAC5-590-379. Groundwater waterworks system monitoring.
A. General monitoring requirements.
1. Owners The owner of a groundwater waterworks system, including consecutive and wholesale waterworks, shall conduct monitoring in accordance with this section, except that requirements do not apply to waterworks that combine all of their groundwater sources with surface water sources or with groundwater under the direct influence of surface water prior to GUDI sources before treatment in accordance with 12VAC5-590-420 12VAC5-590-395.
2. Source water monitoring for owners of by the owner of a groundwater waterworks system that do does not provide 4-log treatment of viruses for their groundwater sources before or at the first customer are is described in subsection B of this section.
3. Owners of The owner of a groundwater waterworks system that provide provides at least 4-log treatment of viruses before or at the first customer are is required to conduct compliance monitoring in accordance with 12VAC5-590-421 C.
4. Owners The owner of a groundwater waterworks system that have has confirmed fecal E. coli contamination, as determined by source water monitoring conducted under subsection B of this section or have has been notified of a significant deficiency as described in 12VAC5-590-350 D shall implement one or more of the corrective actions outlined in 12VAC5-590-421 A 1, as prescribed by the commissioner department.
5. Owners The owner of a groundwater waterworks system that do does not provide 4-log treatment of viruses before or at the first customer and are is not performing compliance monitoring shall provide a triggered source water monitoring plans plan to the commissioner department.
6. Any source water sample collected in accordance with this section shall be analyzed for E. coli using one of the analytical methods in 40 CFR 141.402(c).
B. Groundwater source microbial monitoring.
1. Triggered source water monitoring.
a. General requirements. Groundwater waterworks owners The groundwater system owner shall conduct triggered source water monitoring if both the conditions identified in subdivisions B 1 a (1) and B 1 a (2) of this section exist.
(1) The groundwater waterworks system owner does not provide at least 4-log treatment of viruses before or at the first customer for each groundwater source; and
(2) The groundwater waterworks system owner is notified that a sample collected under 12VAC5-590-370 A is total coliform-positive coliform positive and the sample is not invalidated under 12VAC5-590-380 E.
b. Sampling requirements. Groundwater waterworks owners The groundwater system owner shall collect, within 24 hours of notification of the total coliform-positive sample, one groundwater source water sample from each groundwater source in use at the time the total coliform-positive sample was collected under 12VAC5-590-370 A, except as provided in this subdivision B 1 b.
(1) The commissioner department may extend the 24-hour time limit on a case-by-case basis if the owner cannot collect the groundwater source water sample within 24 hours due to circumstances beyond his control. In the case of an extension, the commissioner department shall specify how much time the owner has to collect the sample.
(2) If approved by the commissioner department, owners the owner of a waterworks with more than one groundwater source may meet the requirements of this subdivision B 1 by sampling a representative groundwater source or sources. Owners The owner shall submit, for the commissioner's department's approval, a triggered source water monitoring plan that identifies one or more groundwater sources that are representative of each monitoring site in the waterworks' bacteriological sample siting report or that identifies groundwater sources that are hydro-geologically hydrogeologically similar and clearly identifies which sources will be sampled.
(3) A groundwater system serving 1,000 people or fewer may use a triggered source water sample collected from a groundwater source to meet both the requirements of 12VAC5-590-380 and to satisfy the monitoring requirements of this subdivision B 1 for a groundwater source.
c. Additional requirements.
(1) If an E. coli-positive triggered source water sample collected under this subdivision B 1 is not invalidated under subdivision B 2 of this section, then the groundwater waterworks system owner shall provide public notification and collect five additional source water samples from the same source within 24 hours of being notified of the E. coli-positive sample.
(a) If the E. coli-positive triggered source water sample is also used as a repeat sample, then an E. coli PMCL violation is incurred under 12VAC5-590-380 B 1 a.
(b) If a waterworks takes collects more than one repeat sample at the monitoring location required for triggered source water monitoring, then the number of additional source water samples required under subdivision B 1 c (1) of this section may be reduced by the number of repeat samples taken collected at that location that were not E. coli positive.
(2) If any of the five additional samples are E. coli positive, the groundwater system owner shall comply with the treatment technique requirements of 12VAC5-590-421.
d. Consecutive and wholesale waterworks.
(1) A consecutive groundwater waterworks system owner that has a total coliform-positive sample collected in accordance with 12VAC5-590-370 A shall notify the wholesale waterworks owner and the district engineer department within 24 hours of being notified of the total coliform-positive sample.
(2) A The wholesale groundwater waterworks system owner shall comply with the following:
(a) A The wholesale groundwater waterworks system owner that receives notice from a consecutive waterworks it serves that a sample collected in accordance with 12VAC5-590-370 A is total coliform-positive coliform positive shall, within 24 hours of being notified, collect a sample from its each groundwater source(s) source as described in subdivision B 1 of this section.
(b) If the sample collected under this subdivision B 1 is E. coli positive, then the wholesale groundwater system owner shall within 24 hours notify all consecutive waterworks served by that groundwater source of the E. coli coli-positive source water positive sample as described in 12VAC5-590-540 and shall meet the requirements of subdivision B 1 c of this section.
e. Exception to the triggered source water monitoring requirements. A groundwater system owner is not required to comply with the source water monitoring requirements of this subdivision B 1 if the commissioner department determines, and documents in writing, that:
(1) The total coliform-positive sample collected in accordance with 12VAC5-590-370 A is invalidated under 12VAC5-590-380 E.
(2) The total coliform-positive sample collected in accordance with 12VAC5-590-370 A is caused by a distribution system deficiency (sanitary defect).
(3) The total coliform-positive sample collected in accordance with 12VAC5-590-370 A was caused by distribution system conditions that will cause total coliform-positive samples.
2. Invalidation of an E. coli-positive groundwater source sample.
a. A The groundwater waterworks system owner may obtain the commissioner's department's invalidation of an E. coli-positive groundwater source sample collected under subdivision B 1 of this section only under the following conditions specified in subdivisions B 2 a (1) and (2) of this section:
(1) The groundwater waterworks system owner provides the commissioner department with written notice from the laboratory that improper sample analysis occurred; or
(2) The commissioner department determines and documents in writing that there is substantial evidence that the E. coli-positive groundwater source sample is not related to source water quality.
b. If the commissioner department invalidates an E. coli positive coli-positive groundwater source sample, then the groundwater system owner shall collect another source water sample under subdivision B 1 of this section within 24 hours of being notified by the commissioner department of the invalidation decision and have it the source water sample analyzed for E. coli.
3. Sampling location. All groundwater source samples required under subdivision B 1 of this section shall be collected at a location prior to before any treatment of the groundwater source unless otherwise approved by the commissioner department.
4. Public notification. The owner of a groundwater waterworks system with a source water sample collected under this subsection that is E. coli positive and that is not invalidated under subdivision B 2 of this section, including consecutive waterworks served by the groundwater source, shall conduct public notification as required in 12VAC5-590-540 A 1.
5. Monitoring violations. Failure to meet the monitoring requirements of subdivision B 1 of this section is a violation and requires the groundwater waterworks system owner to provide public notification as required in 12VAC5-590-540 A 3.
C. Monitoring requirements for source water.
1. The owner of a groundwater source utilizing chlorine disinfection or any other treatment or chemical addition that may alter or affect the bacteriological quality of the source water shall collect source water samples for bacteriological analysis in accordance with this section.
2. All bacteriological samples under this section shall be collected from the source water before any treatment or chemical addition.
a. The owner shall provide a suitable source water sample tap at each groundwater source.
b. If conditions indicate that it is not possible to install a source water sample tap, then an alternate sample location acceptable to the department may be utilized for this monitoring.
3. All samples shall be analyzed by a test method that will yield a most probable number (MPN) result for both total coliforms and E. coli.
4. Number of samples.
a. The number of routine source water samples to be collected and the frequency of sampling shall be determined by the department. The department will notify the owner of the source water sampling requirements.
b. As a minimum, the owner shall collect source water samples in accordance with Table 379.1.
TABLE 379.1
Monitoring Requirements for Source Water Samples
|
SOURCE TYPE
|
MINIMUM ROUTINE SOURCE WATER MONITORING FREQUENCY
|
PARAMETERS
|
Well located in non-karst geology
|
One sample per year
|
Total coliforms MPN and E coli MPN
|
Well located in karst geology
|
One sample per calendar quarter
|
Total coliforms MPN and E coli MPN
|
Spring
|
One sample per month
|
Total coliforms MPN and E coli MPN
|
c. When a single sample result from a groundwater source that requires a routine source water monitoring frequency of less than monthly indicates total coliforms in excess of 50 colonies/100 mL or the presence of E. coli, the owner shall collect one confirmation sample within seven calendar days after notification of the results.
d. The department may require that additional source water samples be collected and will establish the specific number of samples and the monitoring frequency.
12VAC5-590-380. Bacteriological quality compliance.
A. Analytical methodology. 1. The standard sample volume for the coliform test shall consist of 100 milliliters, regardless of the analytical method used. 2. Owners need The owner needs only to determine the presence or absence of total coliforms and E. coli; a determination of total coliform density is not required for routine bacteriological monitoring at entry points or distribution system locations.
3. The time from sample collection to initiation of test medium incubation shall not exceed 30 hours.
4. Owners are encouraged but not required to hold samples below 10oC during transit.
5. If water having residual chlorine (measured as free, combined, or total chlorine) is to be analyzed, sufficient sodium thiosulfate (Na2S2O3) shall be added to the sample bottle before sterilization to neutralize any residual chlorine in the water sample.
B. PMCLs for microbial contaminants.
1. A waterworks is in compliance with the PMCL for E. coli unless any of the conditions identified in this subdivision occur. A violation may pose an acute risk to public health and is a Tier 1 condition requiring public notification as described in 12VAC5-590-540 A 1 when:
a. A repeat sample following a total coliform-positive routine sample is E. coli positive;
b. A repeat sample following an E. coli-positive routine sample is total coliform positive;
c. The owner fails to take collect all required repeat samples following an E. coli-positive routine sample; or
d. The owner fails to test for E. coli when any repeat sample tests positive for total coliform.
2. Compliance shall be determined with the PMCL for E. coli for each monitoring period for which monitoring for total coliforms is required.
C. The best available technology (BAT), treatment techniques, or other means available for achieving compliance with the PMCL for E. coli shall be:
1. Protection of wells from contamination by coliforms by appropriate placement and, construction, and maintenance of the wells;
2. Maintenance of a disinfectant detectable residual disinfectant throughout the distribution system;
3. Proper maintenance of the distribution system including appropriate pipe replacement and repair procedures, water main flushing programs, proper operation and maintenance of storage tanks and reservoirs, continual maintenance of positive water pressure in all parts of the distribution system, and an approved cross connection cross-connection control program;
4. Filtration and disinfection of a surface water or surface influenced groundwater source, a GUDI source, or both; and
5. Disinfection of groundwater using strong oxidants such as chlorine, chlorine dioxide, or ozone.
D. A total coliform-positive result is indicative of a breakdown in the protective barriers and shall be cause for repeat monitoring and special follow-up action to locate and eliminate the cause of contamination.
1. For each routine sample found to be total coliform positive, the waterworks owner shall collect a set of three repeat samples within 24 hours of being notified of the positive result. The commissioner department may extend the 24-hour limit on a case-by-case basis. For groundwater waterworks systems, the requirements of 12VAC5-590-379 shall also apply, and all repeat samples must be analyzed for E. coli using one of the analytical methods in 40 CFR 141.402(c).
a. The owner shall collect at least one repeat sample from the sampling tap where the original total coliform-positive sample was taken collected, and at least one repeat sample at a tap within five service connections upstream and at least one repeat sample at a tap within five service connections downstream of the original sampling site. If a total coliform-positive sample is at the end of the distribution system or one service connection away from the end of the distribution system, the owner must still take collect all required repeat samples.
b. The owner shall collect an additional set of repeat samples if one or more repeat samples in the current set of repeat samples is total coliform positive. The owner shall collect the additional set of repeat samples within 24 hours of being notified of the positive results, unless the commissioner department extends the limit as provided in this section. The owner shall continue to collect additional sets of repeat samples until either total coliforms are not detected in one complete set of repeat samples or the owner determines that a coliform treatment technique trigger specified in 12VAC5-590-392 B has been exceeded as a result of a repeat sample being total coliform positive and notifies the appropriate ODW field office department. If a trigger identified in 12VAC5-590-392 B is exceeded as a result of a routine sample being total coliform positive, an then the owner is required to conduct only one round of repeat monitoring for each total coliform-positive routine sample.
c. If the owner collects a routine sample before learning the results of the previous routine sample, and the sample is taken collected within five service connections of the initial routine sample, then the owner may count the subsequent sample as a repeat sample when the initial sample results are found to be total coliform positive.
d. If one or more repeat samples taken collected at the monitoring location required for triggered source water monitoring are E. coli positive, then the waterworks owner has exceeded the E. coli PMCL and must comply with the groundwater system treatment technique requirements specified in 12VAC5-590-421.
e. If all repeat samples taken collected at the monitoring location required for triggered source water monitoring are E. coli negative, and a repeat sample taken collected at a monitoring location other than the one required for triggered source water monitoring is E. coli positive, then the waterworks owner has exceeded the E. coli PMCL. However, the owner is not required to collect five additional source water samples from the same source within 24 hours of learning the E. coli-positive result.
f. The waterworks owner shall collect all repeat samples on the same day, except the commissioner department may allow the owner of a waterworks with a single service connection to collect the required set of repeat samples over a three-day period or to collect a larger volume repeat sample in one or more sample containers of any size as long as the total volume collected is at least 300 ml.
g. If a repeat sample taken collected at the monitoring location required for triggered source water monitoring is E. coli positive coli-positive, then the waterworks owner has exceeded the E. coli PMCL and must collect five additional source water samples from the same source within 24 hours of learning the E. coli-positive result.
2. Results of all routine and repeat samples not invalidated by the commissioner department shall be used to determine compliance with the PMCL for E. coli and whether a treatment technique trigger specified in 12VAC5-590-392 B has been exceeded.
3. Special purpose Special-purpose samples, such as those taken collected to determine whether disinfection practices are sufficient following pipe placement, replacement, or repair, and samples taken collected before start-up of a seasonal waterworks, shall not be used to determine compliance. Repeat samples are not considered special purpose special-purpose samples.
E. A total coliform-positive sample invalidated under this paragraph subsection does not count towards toward meeting the minimum monitoring requirements of this section. To invalidate a total coliform-positive sample under this subsection, the written decision and rationale shall be reviewed evaluated, approved, and signed by the commissioner department. The commissioner department shall make this document available to EPA and the public. The written documentation shall state the specific cause of the total coliform-positive sample and what action the owner has taken, or will take, to correct this problem. The commissioner department shall not invalidate a total coliform-positive sample solely on the grounds that all repeat samples are total coliform negative.
1. The commissioner department may invalidate a total coliform positive sample if any of the following conditions are met:
a. The laboratory establishes that improper sample analysis caused the total coliform-positive result;
b. The commissioner department, on the basis of the results of repeat samples collected as required by subdivision D 1 of this section, determines that the total coliform-positive sample resulted from a domestic or other nondistribution system plumbing problem. The commissioner department cannot invalidate a sample on the basis of repeat sample results unless all repeat sample(s) samples collected at the same tap as the original total coliform-positive sample are also total coliform positive, and all repeat samples collected at a location other than the original tap are total coliform negative (e.g., the commissioner department cannot invalidate a total coliform-positive sample on the basis of repeat samples if all the repeat samples are total coliform negative, or if the waterworks has only one service connection); or
c. The commissioner department has substantial grounds to believe that a total coliform-positive result is due to a circumstance or condition that does not reflect water quality in the distribution system. In this case, the waterworks owner shall still collect all repeat samples required under subdivision D 1 of this section, and use them to determine whether a coliform treatment technique trigger in 12VAC5-590-392 B has been exceeded.
2. A laboratory must invalidate a sample because of sampling interference (i.e., turbid culture in absence of (i) gas production, or (ii) acid reaction; exhibition of confluent growth; or production of colonies too numerous to count). The waterworks owners owner shall collect a replacement sample from the same location within 24 hours, and have it analyzed for the presence of total coliforms. The waterworks owner must continue to resample within 24 hours and have the samples analyzed until they obtain a valid result is obtained. The commissioner department may waive the 24-hour time limit on a case-by-case basis.
F. Escherichia coli (E. coli).
1. If any a routine or, repeat sample, or replacement sample is total coliform positive, then the waterworks owner shall analyze that the total coliform-positive culture medium to determine if E. coli are present. If E. coli are present, then the waterworks owner shall notify the appropriate ODW field office department by the end of the day when the waterworks owner is notified of the test result, unless the ODW's field office department is closed, in which case the appropriate ODW field office department must be notified before the end of the next business day.
2. The commissioner department has the discretion to allow a waterworks an owner, on a case-by-case basis, to forgo E. coli testing on a total coliform-positive sample if the owner assumes that the total coliform-positive sample is E. coli positive. Accordingly, the owner must notify the appropriate ODW field office department as specified in subdivision F 1 of this subsection and the provisions of subdivision B 1 of this section apply.
G. Groundwater sources.
1. Groundwater sources shall be disinfected in accordance with 12VAC5-590-1000 when the total coliform geometric mean of 20 or more raw water samples measured by a method yielding a multiple-portion decimal-dilution (MPN) result is greater than three 12VAC5-590-421 A 1 d when the results of the source water monitoring samples specified in 12VAC5-590-430 B 2 or 12VAC5-590-840 K 1 a indicate a total coliform concentration (geometric mean) of the 20 samples to be greater than 3 colonies/100 mL but less than 100 colonies/100 mL. The value 1.0 shall be used to represent a negative zero coliform result in the calculation of the geometric mean.
2. Groundwater sources containing a total coliform geometric mean of 100 or more organisms per 100 milliliters or with more than 10% of these samples exceeding 100 organisms per 100 milliliters constitutes unacceptable contamination for disinfection treatment only source monitoring results conducted in accordance with 12VAC5-590-430 B 2 or 12VAC5-590-840 K 1 a that indicate a total coliform concentration equal to or greater than 100 colonies/100 ml constitutes contamination that is not treatable by single-barrier disinfection treatment alone.
3. Groundwater sources shall be disinfected in accordance the requirements of 12VAC5-590-1000 12VAC5-590-421 A 1 d when the source water quality contributes to the waterworks' failure to meet the bacteriological PMCL specified in subsection B of this section.
4. Groundwater sources shall be disinfected in accordance with 12VAC5-590-421 A 1 d when the results of source development samples specified in 12VAC5-590-840 B 11 indicate the presence of E. coli in two or more samples.
5. Groundwater sources shall be disinfected in accordance with 12VAC5-590-421 A 1 d when the results of raw water monitoring conducted in accordance with 12VAC5-590-425 indicate the presence of E. coli in two or more samples during any running six-month period.
4. If the results of the source water monitoring required by 12VAC5-590-379 C or 12VAC5-590-430 B 2 indicate the presence of E. coli in two or more samples collected during any running six-month period, then the owner shall:
a. Issue a Tier 1 public notice in accordance with 12VAC5-590-540 A 1.
b. Provide disinfection treatment to achieve a 4-log virus inactivation and removal as specified in 12VAC5-590-421 A 1 d.
c. Conduct compliance monitoring as specified in 12VAC5-590-421 B and 12VAC5-590-421 C.
5. If the results of the source water monitoring required in 12VAC5-590-379 C indicate total coliform concentration in excess of 50 colonies/100 mL in three or more samples collected during any running six-month period or the presence of E. coli in two or more samples collected during any running six-month period, then the source water shall be reevaluated for GUDI determination in accordance with 12VAC5-590-430.
6. The department may require that any groundwater source be disinfected in accordance with the requirements of 12VAC5-590-421 A 1 d.
H. Groundwater systems conducting source water monitoring as described in 12VAC5-590-379 shall determine the presence or absence of E. coli. All samples shall be analyzed [ by laboratories that have received certification by EPA or DCLS as specified ] in [ accordance with ] 12VAC5-590-440 [ by the ] Division of Consolidated Laboratory Services (DCLS) [ DCLS or by a laboratory certified by the DCLS ] for drinking water samples analyses.
12VAC5-590-382. Inorganic chemicals compliance.
A. When the results of sampling for antimony, arsenic, asbestos, barium, beryllium, cadmium, cyanide (as free cyanide), chromium, fluoride, mercury, nickel, selenium, or thallium exceed the applicable PMCL, the owner shall collect a confirmation sample at the same sampling point within two weeks of notification of the analytical results of the first sample. The fluoride PMCL applies only to community waterworks.
1. The results of the initial and confirmation samples shall be averaged to determine compliance with subsection A of this section. The department has the discretion to delete results of obvious sampling errors.
2. Compliance with the PMCLs for antimony, arsenic, asbestos, barium, beryllium, cadmium, cyanide (as free cyanide), chromium, fluoride, mercury, nickel, selenium, and thallium listed in Table 340.1 shall be determined based on the analytical results obtained at each sampling point.
a. For the owner of a waterworks that conducts monitoring more frequently than annually, compliance with the PMCL for antimony, arsenic, asbestos, barium, beryllium, cadmium, cyanide (as free cyanide), chromium, fluoride, mercury, nickel, selenium, or thallium is determined by an RAA at each sampling point. If the average at any sampling point is greater than the PMCL, then the waterworks is out of compliance. If any single sample would cause the annual average to be exceeded, then the waterworks is out of compliance immediately. A sample result below the MDL shall be calculated as zero for the purpose of determining the annual average. If the owner fails to collect the required number of samples, compliance (average concentration) shall be based on the total number of samples collected.
b. For the owner of a waterworks that monitors annually or less frequently, the waterworks is [ not ] out of compliance with the PMCL for antimony, arsenic, asbestos, barium, beryllium, cadmium, cyanide (as free cyanide), chromium, fluoride, mercury, nickel, selenium, or thallium if the average of the original sample and a confirmation sample of a contaminant at any sampling point is greater than the PMCL. If sample results for the owner monitoring annually or less frequently exceed the PMCL, the owner shall begin quarterly sampling. The owner shall not be considered in violation of the PMCL until one year of quarterly sampling has been completed and the RAA is exceeded. However, if the confirmation sample is not collected, the owner is in violation of the PMCL for antimony, arsenic, asbestos, barium, beryllium, cadmium, cyanide (as free cyanide), chromium, fluoride, mercury, nickel, selenium, or thallium. If the owner fails to collect the required number of samples, then compliance (average concentration) shall be based on the total number of samples collected.
B. Compliance with the PMCLs for nitrate and nitrite shall be determined based on the analytical results obtained at each sampling point. The waterworks is not out of compliance with the PMCL if the concentrations of these contaminants are equal to or below the PMCLs. Where nitrate or nitrite sample results exceed the PMCL, the owner shall collect a confirmation sample, from the same sampling point that exceeded the PMCL within 24 hours of the owner's receipt of the analytical results of the first sample. The results of the initial and confirmation sample shall be averaged to determine compliance. The owner unable to comply with the 24-hour sampling requirement shall immediately notify the consumers in the area served by the waterworks in accordance with 12VAC5-590-540 A 1. The owner exercising this option shall collect and analyze a confirmation sample within two weeks of notification of the analytical results of the first sample. The department may require more frequent monitoring. The department has the discretion to delete results of obvious sampling errors.
1. Nitrate nitrogen (NO3-N) levels not exceeding 20 mg/L may be allowed in a noncommunity waterworks if the owner:
a. Demonstrates to the satisfaction of the department that this water will not be available to children under six months of age;
b. Provides continuous posting of the fact that NO3-N levels exceed 10 mg/L and the potential health effects of exposure;
c. Notifies health officials annually of NO3-N levels that exceed 10 mg/L; and
d. The department shall determine that no adverse health effects will result.
2. Nitrite in water poses a significant health hazard. Water with nitrite-nitrogen concentrations over 1 mg/L should not be used for infant feedings.
C. Compliance with the SMCLs for aluminum, chloride, copper, corrosivity, fluoride, foaming agents, iron, manganese, silver, sulfate, or zinc shall be determined based on the analytical results obtained at each sampling point. When the result of a sample exceeds the applicable SMCL, the owner shall collect a confirmation sample at the same sampling point within two weeks of notification of the analytical results of the first sample. The results of the initial and confirmation samples shall be averaged to determine compliance. If the average concentration level of any of these constituents exceeds the SMCL, then the department shall determine whether treatment for the constituents can be accomplished or more suitable source waters are, or can be made, available. This determination shall be made as quickly as possible. If either of these alternatives is feasible, then corrective action shall be promptly implemented by the owner if deemed necessary by the department. Exceeding the fluoride SMCL requires annual public notice in accordance with 12VAC5-590-540 G.
12VAC5-590-383. Organic chemicals compliance.
A. When the results of sampling indicate positive results for contaminants listed in Table 340.2, the owner shall collect a confirmation sample at the same sampling point within two weeks of notification of the analytical results of the first sample.
B. The results of the initial and confirmation samples shall be averaged to determine waterworks compliance in accordance with subsection C of this section. The department has the discretion to delete results of obvious sampling errors.
C. Compliance with Table 340.2 shall be determined based on the analytical results obtained at each sampling point. A sample result below the detection limit shall be calculated as zero for the purposes of determining the annual average. If the owner fails to collect the required number of samples, then compliance (average concentration) shall be based on the total number of samples collected.
1. For the owner of a waterworks that conducts monitoring more frequently than annually, compliance is determined by an RAA of all samples collected at each sampling point. If the annual average of any sampling point is greater than the PMCL, then the waterworks is out of compliance. If the initial sample or a subsequent sample would cause the annual average to be exceeded, then the waterworks is out of compliance immediately. A sample result below the detection limit shall be calculated as zero for purposes of determining the annual average.
2. If the owner is conducting monitoring annually or less frequently, then the owner is not in violation if the average of the initial and confirmation samples is greater than the PMCL for that contaminant; however, the owner shall begin quarterly sampling. The owner will not be considered in violation of the PMCL until one year of quarterly sampling has been completed and the RAA is exceeded. If any sample will cause the RAA to exceed the PMCL at any sampling point, then the waterworks is immediately out of compliance with the PMCL.
12VAC5-590-384. Residual disinfectant, DBPs, and DBPPs compliance.
A. General requirements.
1. Where compliance is based on an RAA of monthly or quarterly samples or averages and the owner fails to monitor for TTHM, HAA5, or bromate, this failure to monitor shall be treated as a monitoring violation for the entire period covered by the annual average. Where compliance is based on an RAA of monthly or quarterly samples or averages and the owner's failure to monitor makes it impossible to determine compliance with MRDLs for chlorine and chloramines, this failure to monitor shall be treated as a monitoring violation for the entire period covered by the annual average.
2. All samples collected and analyzed under the provisions of this section shall be included in determining compliance, even if that number is greater than the minimum required.
3. The owner is in violation of the PMCL when the LRAA exceeds the PMCLs listed in Table 340.6 calculated based on four consecutive quarters of monitoring, or the LRAA calculated based on fewer than four quarters of data if the PMCL would be exceeded regardless of the monitoring results of subsequent quarters. The owner is in violation of the monitoring requirements for each quarter that a monitoring result would be used in calculating the LRAA if the owner fails to monitor.
B. Disinfection byproducts.
1. TTHM and HAA5.
a. The owner of a waterworks required to monitor quarterly shall calculate the LRAAs for TTHM and HAA5 using monitoring results collected under 12VAC5-590-374 F and determine that each LRAA does not exceed the PMCL in order to comply with the PMCLs listed in Table 340.6. If the owner fails to complete four consecutive quarters of monitoring, then the owner shall calculate compliance with the PMCL based on the average of the available data from the most recent four quarters. If the owner collects more than one sample per quarter at a monitoring location, then the owner shall average all samples collected in the quarter at that location to determine a quarterly average to be used in the LRAA calculation.
b. The owner of a waterworks required to monitor annually or less frequently shall determine that each sample collected is less than the PMCL in order to determine compliance with the PMCLs listed in Table 340.6. If any sample result exceeds the PMCL, then the owner shall comply with the requirements of 12VAC5–590-374 F 5. If no sample result exceeds the PMCL, then the sample result for each monitoring location is considered the LRAA for that monitoring location.
c. The owner is in violation of the monitoring requirements for each quarter that a monitoring result would be used in calculating an LRAA if the owner fails to monitor.
d. A waterworks has exceeded the operational evaluation level at any monitoring location where the sum of the two previous quarters' TTHM results plus twice the current quarter's TTHM result, divided by four to determine an average, exceeds 0.080 mg/L, or where the sum of the two previous quarters' HAA5 results plus twice the current quarter's HAA5 result, divided by four to determine an average, exceeds 0.060 mg/L.
(1) The owner of a waterworks that exceeds the operational evaluation level shall conduct an operational evaluation and submit a written report of the evaluation to the department on a form approved by the department no later than 90 days after being notified of the analytical result that caused the waterworks to exceed the operational evaluation level. The written report shall be made available to the public upon request.
(2) The operational evaluation report shall include an examination of the waterworks treatment and distribution operational practices, including source water conditions, storage tank operations, excess storage capacity, distribution system flushing, changes in source water or source water quality, and treatment changes or problems that may contribute to TTHM and HAA5 formation and what steps could be considered to minimize future exceedances.
(3) The owner may request and the department may allow the owner to limit the scope of the evaluation if the owner is able to identify the cause of the operational evaluation level exceedance. The request to limit the scope of the evaluation does not extend the schedule in subdivision B 1 d (1) of this section for submitting the written report. The department shall approve this limited scope of evaluation in writing, and the owner shall keep that approval with the completed report.
2. Bromate. Compliance shall be based on a running annual arithmetic average, computed quarterly, of monthly samples collected by the owner as prescribed by 12VAC5-590-374 H. For months in which the owner collects more than one sample, compliance is based on the average of all samples collected during the month. If the average result of the samples covering any consecutive four-quarter period exceeds the PMCL listed in Table 340.6, then the owner is in violation of the PMCL and shall notify the public pursuant to 12VAC5-590-540 A 2, in addition to reporting to the department pursuant to 12VAC5-590-530 and 12VAC5-590-531. If the owner fails to complete 12 consecutive months of monitoring, then compliance with the PMCL for the last four-quarter compliance period shall be based on the average of the available data.
3. Chlorite. Compliance shall be based on an arithmetic average of each three-sample set collected in the distribution system as prescribed by 12VAC5-590-374 G. If the arithmetic average of any three-sample set exceeds the PMCL listed in Table 340.6, then the owner is in violation of the PMCL and shall notify the public pursuant to 12VAC5-590-540 A 2, in addition to reporting to the department pursuant to 12VAC5-590-530 and 12VAC5-590-531.
C. Residual disinfectant.
1. Chlorine and chloramines.
a. Compliance shall be based on a running annual arithmetic average, computed quarterly, of monthly averages of all samples collected by the owner under 12VAC5-590-374 I 1 a. If the average covering any consecutive four-quarter period exceeds the MRDL listed in Table 340.7, then the owner is in violation of the MRDL and shall notify the public pursuant to 12VAC5-590-540 A 2, in addition to reporting to the department pursuant to 12VAC5-590-530 and 12VAC5-590-531.
b. In cases where the owner switches between the use of chlorine and chloramines for residual disinfection during the year, compliance shall be determined by including together all monitoring results of both chlorine and chloramines in calculating compliance. Reports submitted pursuant to 12VAC5-590-530 and 12VAC5-590-531 shall clearly indicate which residual disinfectant was analyzed for each sample.
c. Notwithstanding the MRDLs listed in Table 340.7, operators may increase the residual disinfectant levels of chlorine or chloramines in the distribution system to a level and for a time necessary to protect public health to address specific microbiological contamination problems caused by circumstances such as water main breaks in the distribution system, storm runoff events, source water contamination, or cross-connections.
2. Chlorine dioxide.
a. Acute violations. Compliance shall be based on consecutive daily samples collected by the owner under 12VAC5-590-374 I 2 a. If any daily sample collected at the entrance to the distribution system exceeds the MRDL listed in Table 340.7, and on the following day one or more of the three samples collected in the distribution system exceed the MRDL, then the owner is in violation of the MRDL and shall take immediate corrective action to lower the level of chlorine dioxide below the MRDL and shall notify the public pursuant to the procedures for Tier 1 conditions in 12VAC5-590-540 A 1 in addition to reporting to the department pursuant to 12VAC5-590-530 and 12VAC5-590-531. Failure to collect samples in the distribution system the day following an exceedance of the chlorine dioxide MRDL at the entrance to the distribution system shall also be considered an MRDL violation, and the owner shall notify the public of the violation in accordance with the provisions for Tier 1 conditions in 12VAC5-590-540 A 1 in addition to reporting to the department pursuant to 12VAC5-590-530 and 12VAC5-590-531.
b. Nonacute violations. Compliance shall be based on consecutive daily samples collected by the owner under 12VAC5-590-374 I 2 a. If any two consecutive daily samples collected at the entrance to the distribution system exceed the MRDL listed in Table 340.7 and all distribution system samples collected are below the MRDL, then the owner is in violation of the MRDL and shall take corrective action to lower the level of chlorine dioxide below the MRDL at the point of sampling and shall notify the public pursuant to the procedures for Tier 2 conditions in 12VAC5-590-540 A 2 in addition to reporting to the department pursuant to 12VAC5-590-530 and 12VAC5-590-531. Failure to monitor at the entrance to the distribution system the day following an exceedance of the chlorine dioxide MRDL at the entrance to the distribution system is also an MRDL violation, and the owner shall notify the public of the violation in accordance with the provisions for Tier 2 conditions in 12VAC5-590-540 A 2 in addition to reporting to the department pursuant to 12VAC5-590-530 and 12VAC5-590-531.
D. Disinfection byproduct precursors (DBPPs).
1. Compliance shall be determined as specified by 12VAC5-590-411 A 3.
2. For the owner required to meet Step 1 TOC removals, if the value calculated under 12VAC5-590-411 A 3 a (4) is less than 1.00, then the owner is in violation of the treatment technique requirements and shall notify the public pursuant to 12VAC5-590-540 A 2 in addition to reporting to the department pursuant to 12VAC5-590-530 and 12VAC5-590-531.
12VAC5-590-385. Lead and copper action level AL compliance.
A. The lead action level AL is exceeded if the concentration of lead in more than 10% of tap water samples collected during any monitoring period conducted in accordance with 12VAC5-590-375 B is greater than 0.015 mg/L (i.e., if the 90th percentile lead level is greater than 0.015 mg/L).
B. The copper action level AL is exceeded if the concentration of copper in more than 10% of tap water samples collected during any monitoring period conducted in accordance with 12VAC5-590-375 B is greater than 1.3 mg/L (i.e., if the 90th percentile copper level is greater than 1.3 mg/L).
C. The 90th percentile lead and copper levels shall be computed as follows:
1. The results of all lead or copper samples taken during a monitoring period shall be placed in ascending order from the sample with the lowest concentration to the sample with the highest concentration. Each sampling result shall be assigned a number, ascending by single integers beginning with the number 1 for the sample with the lowest contaminant level. The number assigned to the sample with the highest contaminant level shall be equal to the total number of samples taken.
2. The number of samples taken during the monitoring period shall be multiplied by 0.9.
3. The contaminant concentration in the numbered sample yielded by the calculation in subdivision C 2 of this section is the 90th percentile contaminant level.
4. For a waterworks serving fewer than 100 people that collect, and the owner collects five samples per monitoring period, the 90th percentile is computed by taking the average of the highest and second highest concentrations.
5. For an the owner that has been allowed by the commissioner department to collect fewer than five samples in accordance with 12VAC5-590-375 B 3, the sample result with the highest concentration is considered the 90th percentile value.
12VAC5-590-388. Radiological compliance.
A. MCLGs for radionuclides are listed in Table 546.1 of 12VAC5-590-546 B.
B. PMCLs for radionuclides are applicable to community waterworks only and are listed in Table 340.4. Compliance with PMCLs will be determined based on the analytical results obtained at each entry point. If the sample result at one entry point exceeds the PMCL, then the owner is in violation of the PMCL.
1. For the owner that is monitoring more than once per year, compliance with the PMCL is determined by an RAA of the analytical results at each entry point. If the average result at any entry point is greater than the PMCL, then the waterworks is out of compliance with the PMCL.
2. For the owner of a waterworks that monitors more than once per year, if any sample result will cause the RAA to exceed the PMCL at any entry point, then the waterworks is out of compliance with the PMCL immediately.
3. All samples collected and analyzed under the provisions 12VAC5-590-378 shall be included in determining compliance, even if that number is greater than the minimum required.
4. If the owner does not collect all required samples when compliance is based on an RAA result of quarterly samples, then compliance will be based on the RAA result of the samples collected.
5. If a sample result is less than the detection limit as specified in Table 378.1, then zero will be used to calculate the RAA unless a gross alpha particle activity result is being used instead of radium-226 or uranium. If the gross alpha particle activity result is less than the detection limit as specified in Table 378.1, then one half the detection limit will be used to calculate the RAA.
C. Radiological (gross alpha, combined radium-226 and radium-228, uranium, and man-made radioactivity).
1. Compliance with the radiological PMCLs shall be based on the RAA results. PMCLs are indicated in Table 340.4. Sampling for radiological analysis shall be in compliance with 12VAC5-590-378.
2. Compliance shall be determined by rounding off results to the same number of significant figures as the PMCL for the radionuclide in question.
D. If a PMCL for radioactivity listed in Table 340.4 is exceeded, then the owner shall give notice to the department pursuant to 12VAC5-590-530 and to the public as required by 12VAC5-590-540 A 2.
12VAC5-590-390. Chemical and physical quality Physical constituent compliance.
A. Necessary action for noncompliance.
1. Inorganic chemicals. See 12VAC5-590-530 B and 12VAC5-590-540.
2. Organic chemicals. See 12VAC5-590-530 B and 12VAC5-590-540.
3. Turbidity. See 12VAC5-590-530 B and 12VAC5-590-540.
A. Color, odor, pH, and total dissolved solids.
1. When the sampling results for color, odor, pH, or total dissolved solids exceed the applicable SMCL, the owner shall collect a confirmation sample at the same sampling site within two weeks of notification of the analytical results of the first sample.
2. The results of the initial and confirmation samples shall be averaged to determine compliance with 12VAC5-590-340 C. The department has the discretion to void results of obvious sampling errors.
4. 3. If the average concentration level of a substance of any contaminant of color, odor, pH, or total dissolved solids is greater than the Secondary Maximum Contaminant Level SMCL listed in Table 340.3, then the division will department shall determine whether treatment to remove the substance that contaminant can be accomplished or more suitable supplies of source water are, or can be made, available. This determination will be made as quickly as possible. If either of these alternatives is possible, corrective action shall be promptly taken by the owner if deemed necessary by the division.
B. Specific limits. No attempt has been made to prescribe specific limits for every contaminant that might enter a water supply or waterworks. Although the need exists for continued attention to the entry of chemical and physical substances into water, the limits are confined to substances recognized as being detrimental to the health or well-being of the consumer. Limits for innumerable substances would require an impossible burden of analytical examination. The specific limits included in these regulations are listed in Tables 2.2, 2.3, and 2.4. Turbidity in groundwater sources not required to filter shall not:
1. Interfere with disinfection throughout the distribution system;
2. Cause taste and odors upon disinfection; or
3. Cause consumers to question the safety of their drinking water.
12VAC5-590-391. Treatment technique requirements.
A. When it is not technically or economically feasible to monitor for a particular PMCL or a contaminant, one or more specific treatment techniques that lead to a reduction in the concentration level of that contaminant shall be required. The application of that treatment technique reduces the contaminant in question to a concentration level that achieves compliance with this chapter.
B. Failure to continuously maintain the treatment technique is a violation of this chapter and public notification in accordance with 12VAC5-590-540 A 2 is required.
12VAC5-590-392. Coliform treatment technique triggers and assessment requirements.
A. Assessments shall be conducted in accordance with subsections C, D, and E of this section after exceeding treatment technique triggers.
B. Treatment technique triggers.
1. Level 1 treatment technique triggers:
a. For owners the owner required to collect 40 or more samples per month, the number of total coliform-positive samples exceeds 5.0% of the number of samples collected for the month.
b. For owners the owner required to collect fewer than 40 samples per month, when there are two or more total coliform-positive samples in the same month.
c. The owner fails to collect every required repeat sample after any single total coliform-positive sample.
2. Level 2 treatment technique triggers:
a. An E. coli PMCL violation, as specified in 12VAC5-590-380 B 2.
b. A second Level 1 trigger occurs within a rolling 12-month period, unless the commissioner department has determined a likely reason for the first Level 1 treatment technique trigger and that the owner has corrected the problem.
C. Assessment requirements.
1. Level 1 and 2 assessments shall be conducted in order to identify the possible presence of sanitary defects and defects in the distribution system coliform monitoring practices. The owner shall be responsible for conducting Level 1 assessments. Level 2 assessments shall be conducted by the commissioner department.
2. When conducting Level 1 and Level 2 assessments, the assessor shall include:
a. A review An evaluation and identification of inadequacies in sample sites, sampling protocol, and sample processing;
b. A review An evaluation of atypical events that could affect distributed water quality or indicate that distributed water quality was impaired;
c. Evaluation An evaluation of changes in distribution system maintenance and operation that could affect distributed water quality, including water storage;
d. Evaluation An evaluation of source and treatment considerations that impact distributed water quality; and
e. Evaluation An evaluation of existing water quality monitoring data.
3. Level 1 assessment.
a. The owner shall complete the assessment and document the assessment on the Waterworks Level 1 Assessment form a form approved by the department. The owner shall submit the assessment form, as soon as practical, but within 30 days after the owner learns that a trigger in subdivision B 1 of this section has been exceeded.
b. If the commissioner reviews department evaluates the completed Level 1 assessment and determines that the assessment is not sufficient, including any proposed timetable for any corrective actions, then the commissioner department shall consult with the owner. If the commissioner department requires revisions after the consultation, then the owner shall submit a revised assessment form to the appropriate ODW field office department on an agreed upon schedule not to exceed 30 days from the date of consultation.
c. Upon completion and submission of the assessment form by the owner, the commissioner department shall determine if the owner has identified a likely cause for the Level 1 trigger and, if so, confirm that the owner has corrected the problem or has included a schedule acceptable to the commissioner department for correcting the problem.
4. Level 2 assessment.
a. ODW The department will complete the assessment and document the assessment on the Waterworks Level 2 Assessment form on a form approved by the department. ODW staff The department will consult with the owner during the assessment and complete the assessment within 30 days upon learning a that the waterworks has exceeded any trigger in subdivision B 2 of this section.
b. The commissioner department will send to the owner the completed assessment form, which will describe any detected sanitary defects, corrective actions completed or needed and, if needed, a timetable to complete the corrective actions. The owner will return the form within seven days with a signature that indicates concurrence with the listed actions needed and timetable to complete the corrective actions. If the owner does not concur with either an action or timetable to complete a corrective action, then the owner shall notify the commissioner department, complete consultation with the commissioner department, and develop a revised corrective action schedule. The owner shall submit the revised schedule to the commissioner department for review evaluation and approval within 30 days of the date of the consultation.
D. Corrective actions.
1. The owner shall correct sanitary defects found through either the Level 1 or the Level 2 assessment conducted under subsection C of this section.
2. The owner shall complete the corrective action or corrective actions in compliance with the timetable approved by the commissioner department in consultation with the owner. The owner shall notify the appropriate ODW field office department no later than seven days after each scheduled corrective action is completed.
E. Consultation.
1. At any time during the assessment or corrective action phase, either the owner or the commissioner department may request a consultation with the other party to determine the appropriate actions to be taken.
2. The owner may consult with the commissioner department on all relevant information that may impact the ability to comply with subsection D of this section.
F. Violations. Failure to conduct the required assessment or corrective actions in accordance with subsections C and D of this section, after exceeding a treatment technique trigger specified in subsection B of this section, is a treatment technique violation. The owner shall provide public notification as required under Tier 2 conditions specified in 12VAC5-590-540 A 2.
12VAC5-590-395. Surface water and GUDI sources, polymers, and recycle treatment techniques.
A. Surface water and GUDI source treatment techniques.
1. The filtration and disinfection provisions of this section are required treatment techniques for a waterworks supplied by a surface water source, a GUDI source, or both. These treatment technique requirements are in place of a PMCL for the following contaminants: Giardia lamblia, viruses, heterotrophic bacteria, Cryptosporidium, Legionella, and turbidity. A waterworks that uses a surface water source, a GUDI source, or both shall provide treatment of that source water that complies with these treatment technique requirements. See 12VAC5-590-401 for filtration log removal credits and required log inactivation for Cryptosporidium. See 12VAC5-590-500 for log removal credits and required log inactivation for Giardia lamblia and viruses. These treatment technique requirements consist of installing and properly operating water treatment processes that reliably achieve:
a. At least 99.9% (3-log) removal or inactivation of Giardia lamblia between a point where the source water is not subject to recontamination by surface water runoff and a point downstream before or at the first customer;
b. At least 99.99% (4-log) removal or inactivation of viruses between a point where the source water is not subject to recontamination by surface water runoff and a point downstream before or at the first customer; and
c. At least 99% (2-log) removal of Cryptosporidium between a point where the source water is not subject to recontamination by surface water runoff and a point downstream before or at the first customer.
2. A waterworks that uses a surface water source, a GUDI source, or both is considered to be in compliance with the requirements of subdivision A 1 of this section if it meets the following disinfection and filtration requirements:
a. Disinfection requirements.
(1) The disinfection treatment shall be sufficient to ensure that the total treatment processes of that waterworks achieve at least 99.9% (3-log) inactivation or removal of Giardia lamblia and at least 99.99% (4-log) inactivation or removal of viruses. If any physical process can achieve at least a 3-log removal of Giardia lamblia but cannot adequately remove pathogens, then the disinfection treatment shall provide a second treatment barrier for Giardia lamblia, Legionella, heterotrophic bacteria, and viruses. The disinfection treatment shall be sufficient to assure at least a 0.5 log inactivation of Giardia lamblia.
(2) The residual disinfectant concentration in the water entering the distribution system shall not be less than 0.2 mg/L for more than four hours.
(3) The residual disinfectant concentration in the distribution system, measured as total chlorine, free chlorine, combined chlorine, or chlorine dioxide, shall not be undetectable in more than 5% of the samples each month, for any two consecutive months that the waterworks serves water to the public. If the department determines that a waterworks is experiencing excessive coliform occurrences in its distribution system, then the department may require the owner to maintain minimum chlorine residual levels of 0.2 mg/L or monochloramine levels of 0.5 mg/L throughout the distribution system. Water in the distribution system with a heterotrophic bacteria concentration less than or equal to 500/mL, measured as HPC, is deemed to have a detectable residual disinfectant for the purposes of determining compliance with this requirement. Thus, the value "V," in percent, in the following formula shall not exceed 5% in one month, for any two consecutive months.
V = [(c + d + e) / (a + b)] X 100
where
a = number of instances where the residual disinfectant concentration is measured;
b = number of instances where the residual disinfectant concentration is not measured but HPC is measured;
c = number of instances where the residual disinfectant concentration is measured but not detected and no HPC is measured;
d = number of instances where no residual disinfectant concentration is detected and where the HPC is greater than 500/mL; and
e = number of instances where the residual disinfectant concentration is not measured and HPC is greater than 500/mL.
(4) The department may determine that the HPC compliance requirements of subdivision A 2 a (3) of this section do not apply based on site-specific considerations or if an owner has no means for having a sample transported and analyzed for HPC by a certified laboratory under the requisite time and temperature conditions and the waterworks is providing adequate disinfection in the distribution system.
b. Filtration requirements. A waterworks that uses a surface water source, a GUDI source, or both shall provide filtration treatment by using one of the following methods:
(1) Conventional filtration.
(a) Achieve a filtered water turbidity of less than or equal to 0.3 NTU in at least 95% of the measurements taken each month. Samples shall be representative of the waterworks' filtered water.
(b) The turbidity level of representative samples of a waterworks' filtered water shall at no time exceed one NTU, measured as specified in 12VAC5-590-440.
(c) A waterworks that uses lime softening may acidify representative samples before analysis using a protocol approved by the department.
(d) Water treatment plants utilizing conventional or direct filtration with gravity flow granular media filters are capable of producing filtered water with turbidity consistently less than 0.10 NTU. Therefore, for these types of water treatment plants, the operational goal for filter effluent turbidity for each filter, before any post-filtration chemical addition, shall be 0.10 NTU.
(2) Diatomaceous earth filtration.
(a) The turbidity level of representative samples of a waterworks' filtered water shall be less than or equal to one NTU in at least 95% of the measurements taken each month.
(b) The turbidity level of representative samples of a waterworks' filtered water shall at no time exceed five NTU.
(3) Slow sand filtration.
(a) The turbidity level of representative samples of a waterworks' filtered water shall be less than or equal to one NTU in at least 95% of the measurements taken each month, except that if the department determines there is no significant interference with disinfection at a higher turbidity level, then the department may substitute this higher turbidity limit for that waterworks.
(b) The turbidity level of representative samples of a waterworks' filtered water shall at no time exceed five NTU.
(4) Membrane filters, bag filters, and cartridge filters.
(a) The turbidity level of representative samples of a waterworks' filtered water shall be less than or equal to 0.3 NTU in at least 95% of the measurements taken each month, except that if the department determines there is no significant interference with disinfection at a higher turbidity level, then the department may substitute this higher turbidity limit for that waterworks.
(b) Water treatment plants utilizing membrane filtration are capable of producing filtered water with turbidity consistently less than 0.05 NTU. Therefore, for these types of water treatment plants, the operational goal for filter effluent turbidity for each filter, before any post-filtration chemical addition, is 0.05 NTU.
(c) The turbidity level of representative samples of a waterworks' filtered water shall at no time exceed one NTU.
(5) The owner may use a filtration technology not listed in this section if the owner demonstrates to the satisfaction of the department by full-scale, pilot plant, or challenge studies, or by other approved means that the alternative filtration technology, in combination with disinfection, will meet the requirements of this section.
3. Once the department has determined that a waterworks utilizes a surface water source, a GUDI source, or both (see 12VAC5-590-430), then filtration and disinfection treatments are required. The owner shall install and have in operation treatment units that meet the requirements described in subdivisions A 1 and A 2 of this section no later than 18 months following the department's determination. During the interim period, and until filtration and disinfection treatments are installed and in operation, the owner shall discontinue use of the surface water source, GUDI source, or both unless the source must remain in service because discontinuing the source is not a viable option, at which point the owner shall:
a. Issue a continuous boil water notice through the public notification procedure in 12VAC5-590-540 A 1 until the required filtration and disinfection treatments are installed and are in operation;
b. Provide disinfection treatment to achieve a 4-log inactivation of virus during the interim period before the filtration treatment is installed. Monitoring equipment shall be installed that will ensure compliance with this requirement; and
c. Increase bacteriological sampling frequency in the distribution system. For the owner required to collect routine distribution system bacteriological samples at a monthly frequency, the owner shall collect twice the number of samples required for that population each month. For the owner required to collect routine bacteriological samples at a quarterly frequency, the owner shall increase the sampling frequency to monthly.
B. Polymer treatment techniques.
1. The owner shall certify annually in writing to the department (using third-party or manufacturer's certification) that, when polymers containing acrylamide or epichlorohydrin are used by the waterworks, the combination (or product) of dose and monomer level does not exceed the following specified levels:
a. Acrylamide = 0.05% dosed at one ppm (or equivalent) of polymer.
b. Epichlorohydrin = 0.01% dosed at 20 ppm (or equivalent) of polymer.
2. Certifications may rely on the manufacturers or third parties as approved by the department.
C. Recycle treatment techniques.
1. If spent filter backwash water, thickener supernatant, or liquids from dewatering processes are recycled, in a waterworks supplied by a surface water source, a GUDI source, or both that employ conventional filtration or direct filtration treatment, then the waterworks is subject to the treatment technique requirement described in subsection A of this section.
2. Under this requirement, recycle flows shall be returned through all the processes of the treatment system or an alternative location approved by the department.
12VAC5-590-400. Radiological quality. (Repealed.)
The effects of human radiation exposure are viewed as harmful, and any unnecessary exposure to ionizing radiation should be avoided.
A. Maximum contaminant level goals for radionuclides are listed in subsection A of Table 2.5 of 12VAC5-590-440.
B. Maximum contaminant levels for radionuclides are applicable to community waterworks only and are listed in this section and subsection B of Table 2.5.
1. (Reserved.)
2. PMCL for combined radium-226 and radium-228. The primary maximum contaminant level for combined radium-226 and radium-228 is 5 pCi/L. The combined radium-226 and radium-228 value is determined by the addition of the results of the analysis for radium-226 and the analysis for radium-228.
3. PMCL for gross alpha particle activity (excluding radon and uranium). The primary maximum contaminant level for gross alpha particle activity (including radium-226 but excluding radon and uranium) is 15 pCi/L.
4. PMCL for uranium. The primary maximum contaminant level for uranium is 30 μg/l.
5. PMCL for beta particle and photon radioactivity.
a. The average annual concentration of beta particle and photon radioactivity from man-made radionuclides in drinking water must not produce an annual dose equivalent to the total body or any internal organ greater than 4 millirem/year (mrem/year).
b. Except for the radionuclides listed in schedule 1 of Table 2.5, the concentration of man-made radionuclides causing 4 mrem total body or organ dose equivalents must be calculated on the basis of 2 liter per day drinking water intake using the 168 hour data list in "Maximum Permissible Body Burdens and Maximum Permissible Concentrations of Radionuclides in Air and in Water for Occupational Exposure," NBX (National Bureau of Standards) Handbook 69 as amended August 1963, U.S. Department of Commerce. A copy of this document may be reviewed at the Virginia Department of Health Office of Drinking Water office in Richmond, Virginia. If two or more radionuclides are present, the sum of their annual dose equivalent to the total body or to any organ shall not exceed 4 mrem/year.
6. Compliance dates. Compliance dates for combined radium-226 and radium-228, gross alpha particle activity, gross beta particle and photon radioactivity, and uranium: community waterworks owners must comply with the PMCLs listed in subdivisions 2, 3, 4, and 5 of this subsection beginning December 8, 2003, and compliance shall be determined in accordance with the requirements of 12VAC5-590-370 D. Compliance with reporting requirements for the radionuclides under 12VAC5-590-545 and 12VAC5-590-540 is required on December 8, 2003.
12VAC5-590-401. Enhanced filtration and disinfection for Cryptosporidium treatment techniques.
A. A waterworks using a surface water source, a GUDI source, or both shall comply with the requirements of this section based on their population or if the waterworks is a wholesaler, based on the population of the largest waterworks in the combined distribution system.
B. The owner shall conduct an initial and a second round of source water monitoring for each water treatment plant that treats a surface water source, a GUDI source, or both. This monitoring may include sampling for Cryptosporidium, E. coli, and turbidity to determine what level, if any, of additional Cryptosporidium treatment is required.
1. Initial round of source water monitoring. The owner shall conduct the following monitoring on the schedule in subdivision B 3 of this section unless the monitoring avoidance criteria in subdivision B 4 of this section are met.
a. The owner of a waterworks serving at least 10,000 people shall sample the source water for Cryptosporidium, E. coli, and turbidity at least monthly for 24 months.
b. The owner of a waterworks serving fewer than 10,000 people:
(1) Shall sample the source water for E. coli at least once every two weeks for 12 months, or
(2) May avoid E. coli monitoring if the owner notifies the department that the owner will monitor for Cryptosporidium as described in subdivision B 1 c of this section. The owner shall notify the department no later than three months before the date at which the owner is otherwise required to start E. coli monitoring.
c. The owner of a waterworks serving fewer than 10,000 people shall sample the source water for Cryptosporidium at least twice per month for 12 months or at least monthly for 24 months if the owner meets one of the following, based on monitoring conducted under subdivision B 1 b of this section:
(1) For a waterworks using source water from a lake or reservoir, the annual mean E. coli concentration is greater than 10 E. coli/100 mL.
(2) For a waterworks using source water from flowing stream, the annual mean E. coli concentration is greater than 50 E. coli/100 mL.
(3) The waterworks does not conduct E. coli monitoring as described in subdivision B 1 b of this section.
(4) The waterworks using a GUDI source shall comply with the requirements of this subdivision B 1 c based on the E. coli level that applies to the nearest surface water body. If no surface water body is nearby, the waterworks shall comply based on the requirements that apply to a waterworks using source water from a lake or reservoir.
d. For the waterworks serving fewer than 10,000 people, the department may approve monitoring for an indicator other than E. coli under subdivision B 1 b (1) of this section. The department also may approve an alternative to the E. coli concentration in subdivision B 1 c (1), B 1 c (2), or B 1 c (4) of this section to trigger Cryptosporidium monitoring. This approval by the department shall be provided to the owner in writing and shall include the basis for the department's determination that the alternative indicator or trigger level will provide a more accurate identification of whether a waterworks will exceed the Bin 1 Cryptosporidium level in subdivision B 1 a of this section.
e. The waterworks may sample more frequently than required under this section if the sampling frequency is evenly spaced throughout the monitoring period.
2. Second round of source water monitoring. The owner shall conduct a second round of source water monitoring that meets the requirements for monitoring parameters, frequency, and duration described in subdivision B 1 of this section, unless the monitoring exemption criteria in subdivision B 4 of this section are met. The owner shall conduct this monitoring on the schedule in subdivision B 3 of this section.
3. Monitoring schedule. The owner shall begin the monitoring required in subdivisions B 1 and B 2 of this section no later than the month beginning with the date listed in Table 401.1:
Editor's Note: Tables 401.1 through 401.7 are not further amended from the proposed regulation, therefore they are not published. View the tables as proposed at 36:6 VA.R. 475-845 November 11, 2019.
4. Monitoring avoidance.
a. The owner is not required to conduct source water monitoring if the waterworks will provide a total of at least 5.5-log of treatment for Cryptosporidium, equivalent to meeting the treatment requirements of Bin 4 in subdivision D 2 of this section.
b. If the owner chooses to provide the level of treatment in subdivision B 4 a of this section, rather than start source water monitoring, then the owner shall notify the department in writing no later than the date the owner is otherwise required to submit a sampling schedule for monitoring under subdivision B 5 of this section. Alternatively, the owner may choose to stop sampling at any point after initiating monitoring if the owner notifies the department in writing that he will provide this level of treatment. The owner shall install and operate technologies to provide this level of treatment by the applicable treatment compliance date in subdivision D 3 of this section.
5. Sampling schedules.
a. The owner of a waterworks required to conduct source water monitoring in accordance with subsection B of this section shall submit a sampling schedule that specifies the calendar dates when the owner shall collect each required sample.
(1) The owner shall submit a sampling schedule to the department no later than three months before the applicable date listed in subdivision B 3 of this section for each round of required monitoring.
(2) If the department does not respond to the owner regarding the sampling schedule, then the owner shall sample at the reported schedule.
b. The owner shall collect samples within two days before or two days after the dates indicated in the sampling schedule (i.e., within a five-day period around the schedule date) unless one of the conditions of this subdivision b applies:
(1) If an extreme condition or situation exists that may pose danger to the sample collector or that cannot be avoided and causes the owner to be unable to sample in the scheduled five-day period, then the owner shall sample as close to the scheduled date as is feasible unless the department approves an alternative sampling date. The owner shall submit an explanation for the delayed sampling date to the department concurrent with the shipment of the sample to the laboratory.
(2) If the owner is unable to report a valid analytical result for a scheduled sampling date due to equipment failure, loss of or damage to the sample, failure to comply with the analytical method requirements, including the quality control requirements of 12VAC5-590-440, or the failure of an approved laboratory to analyze the sample, then the owner shall collect a replacement sample. The owner shall collect the replacement sample not later than 21 days after receiving information that an analytical result cannot be reported for the scheduled date unless the owner demonstrates that collecting a replacement sample within this timeframe is not feasible or the department approves an alternative resampling date. The owner shall submit an explanation for the delayed sampling date to the department concurrent with the shipment of the sample to the laboratory.
c. The owner of a waterworks that fails to meet the criteria of subdivision B 5 b of this section for any source water sample required under subsection B of this section shall revise the sampling schedule to add dates for collecting all missed samples. The owner shall submit the revised schedule to the department for approval before the owner begins collecting the missed samples.
6. Sampling locations.
a. The owner of a waterworks required to conduct source water monitoring under subsection B of this section shall collect samples for each water treatment plant that treats a surface water source, a GUDI source, or both. Where multiple water treatment plants draw source water from the same influent, such as the same pipe or intake, the department may approve one set of monitoring results to be used to satisfy the requirements of subsection B of this section for all water treatment plants.
b. The owner shall collect source water samples before chemical treatment, such as coagulants, oxidants, and disinfectants. However, the department may approve the collection of a source water sample after chemical treatment. To grant this approval, the department shall determine that collecting a sample before chemical treatment is not feasible for the owner and that the chemical treatment is unlikely to have a significant adverse effect on the analysis of the sample.
c. The owner of a waterworks that recycles filter backwash water shall collect source water samples before the point of filter backwash water addition.
d. Bank filtration.
(1) The owner that receives Cryptosporidium treatment credit for bank filtration under 12VAC5-590-395 A 2 b (1) shall collect source water samples from the surface water before bank filtration.
(2) The owner that uses bank filtration as pretreatment to a water treatment plant shall collect source water samples from the well (i.e., after bank filtration). The use of bank filtration during monitoring shall be consistent with routine operational practice. The owner collecting samples after a bank filtration process may not receive treatment credit for the bank filtration under subdivision E 4 c of this section.
e. Multiple sources. The owner of a waterworks that uses multiple source waters, including multiple surface water sources and blended surface water and groundwater sources, shall collect samples as specified in subdivision B 6 e (1) or B 6 e (2) of this section. The use of multiple source waters during monitoring shall be consistent with routine operational practice.
(1) If a sampling tap is available where the source waters are combined before treatment, then the owner shall collect samples from the tap.
(2) If a sampling tap is not available where the source waters are combined before treatment, then the owner shall collect samples at each source near the intake on the same day and shall follow either subdivision B 6 e (2) (a) or B 6 e (2) (b) of this section for sample analysis.
(a) The owner may composite samples from each source into one sample before analysis. The volume of sample from each source shall be weighted according to the proportion of the source water in the total water treatment plant flow at the time the sample is collected.
(b) The owner may choose to have samples analyzed from each source separately and calculate a weighted average of the analysis results for each sampling date. The weighted average shall be calculated by multiplying the analysis result for each source water by the fraction the source water contributed to the total water treatment plant flow at the time the sample was collected and then summing these values.
f. Additional requirements. The owner shall submit a description of each sampling location to the department at the same time as the sampling schedule required in subdivision B 3 of this section. This description shall address the position of the sampling location in relation to the waterworks' source waters and treatment processes, including pretreatment, points of chemical treatment, and filter backwash recycle. If the department does not respond to an owner regarding sampling location, then the owner shall sample at each reported location.
7. Analytical methods. All analytical methods shall be conducted in accordance with 12VAC5-590-440.
8. Approved laboratories.
a. Cryptosporidium. The owner shall have Cryptosporidium samples analyzed by a laboratory that has received reciprocal certification approved under the DCLS Laboratory Certification Program for Analysis of Cryptosporidium in Water.
b. E. coli. A laboratory certified by the DCLS for total coliform analysis under 12VAC5-590-440 is approved for E. coli analysis when the laboratory uses the same technique for E. coli that the laboratory uses under 12VAC5-590-440. Laboratories shall use methods for enumeration of E. coli in source water approved in 12VAC5-590-440.
c. Turbidity. Measurements of turbidity shall be made by a party approved by the department.
9. Reporting of the source water results shall be in accordance with 12VAC5-590-531.
10. The owner of a waterworks treating a surface water source, a GUDI source, or both, that operates for only part of the year shall conduct source water monitoring in accordance with this section, but with the following modifications:
a. The owner shall sample the source water only during the months that the waterworks operates unless the department specifies another monitoring period based on waterworks operating practices.
b. The owner of a waterworks that operates less than six months per year and that monitors for Cryptosporidium shall collect at least six Cryptosporidium samples per year during each of two years of monitoring. Samples shall be evenly spaced throughout the period the waterworks operates.
11. New sources.
a. The owner of a waterworks that begins using a surface water source, a GUDI source, or both, is required to begin monitoring under subdivision B 3 of this section and shall monitor the new source on a schedule approved by the department. Source water monitoring shall meet the requirements of this section. The owner shall also meet the bin classification and Cryptosporidium treatment requirements of subdivisions D 1 and D 2 of this section, for the new source on a schedule approved by the department.
b. The requirements of this section apply to a waterworks using a surface water source, a GUDI source, or both, that begins operation after the monitoring start date applicable to the size of the waterworks under subdivision B 3 of this section.
c. The owner shall begin a second round of source water monitoring no later than six years following the initial bin classification under subdivision D 1 of this section.
12. Failure to collect any source water sample required under this section in accordance with the sampling schedule, sampling location, analytical method, approved laboratory, and reporting requirements of subdivisions B 5 through B 9 of this section is a monitoring violation.
13. Grandparenting monitoring data. The owner may use [ grandparenting ] monitoring data collected before the applicable monitoring start date in subdivision B 3 of this section [ (grandparented data) ] to meet the initial source water monitoring requirements in subdivision B 1 of this section. Grandparented data may be substituted for an equivalent number of months at the end of the monitoring period. All data submitted under this subdivision B 13 shall meet the requirements in subdivisions B 13 a through B 13 h of this section and be approved by the department:
a. The owner may grandparent Cryptosporidium samples to meet the requirements of this section when the owner does not have corresponding E. coli and turbidity samples. The owner who grandparents Cryptosporidium samples without E. coli and turbidity samples is not required to collect E. coli and turbidity samples when the owner completes the requirements for Cryptosporidium monitoring under this section.
b. The analysis of E. coli samples shall meet the analytical method and approved laboratory requirements of subdivisions B 7 and B 8 of this section.
c. The analysis of Cryptosporidium samples shall meet the requirements of subdivision B 8 of this section.
d. The sampling location shall meet the conditions in subdivision B 6 of this section.
e. Cryptosporidium sample collection intervals may vary for the conditions specified in subdivisions B 5 b (1) and B 5 b (2) of this section if the owner provides documentation of the condition when reporting monitoring results.
(1) The department may approve grandparenting of previously collected data where there are time gaps in the sampling frequency if the owner conducts additional monitoring the department specifies to ensure that the data used to comply with the initial source water monitoring requirements of subsection B of this section are seasonally representative and unbiased.
(2) The owner may grandparent previously collected data where the sampling frequency within each month varied. If the Cryptosporidium sampling frequency varied, then the owner shall follow the monthly averaging procedure in subdivision D 1 a (5) of this section when calculating the bin classification for a filtered waterworks.
f. The owner of a waterworks that requests to grandparent previously collected monitoring results shall report the following information by the applicable dates listed in the following subdivisions. The owner shall report this information to the department.
(1) The owner shall report the intent to submit previously collected monitoring results for grandparenting. This report shall specify the number of previously collected results the owner shall submit, the dates of the first and last sample, and whether an owner shall conduct additional source water monitoring to meet the requirements in subsection B of this section. The owner shall report this information no later than the date the sampling schedule listed in subdivision B 3 of this section is required.
(2) The owner shall report previously collected monitoring results for grandparenting no later than two months after the applicable date listed in subdivision B 3 of this section.
(a) For each sample result, the owner shall report the applicable data elements in 12VAC5-590-531 A 5.
(b) The owner shall certify that the reported monitoring results include all results the waterworks generated during the time period beginning with the first reported result and ending with the final reported result. This applies to samples that were collected from the sampling location specified for source water monitoring under subdivision B 1 of this section, not spiked, and analyzed using the laboratory's routine process for the analytical methods listed in this section.
(c) The owner shall certify that the samples were representative of a waterworks' source waters and the source waters have not changed. The owner shall report a description of each sampling location, which shall address the position of the sampling location in relation to the waterworks' source waters and treatment processes, including points of chemical addition and filter backwash recycle.
(d) For Cryptosporidium samples, the laboratory that analyzed the samples shall provide a letter certifying that the quality control criteria specified in the methods listed in subdivision B 8 of this section were met for each sample batch associated with the reported results. Alternatively, the laboratory may provide bench sheets and sample examination report forms for each field, matrix spike, initial precision and recovery (IPR), ongoing precision and recovery (OPR), and method blank sample associated with the reported results.
g. If the department determines that a previously collected data set submitted for grandparenting was generated during source water conditions that were not normal for the waterworks, such as a drought, the department may disapprove the data. Alternatively, the department may approve the previously collected data if the owner reports additional source water monitoring data, as determined by the department, to ensure that the data set used under subdivision D 1 of this section represents average source water conditions for the waterworks.
h. If the owner submits previously collected data that fully meets the number of samples required for initial source water monitoring under subdivision B 1 of this section and some of the data are rejected due to not meeting the requirements of this section, then the owner shall conduct additional monitoring to replace rejected data on a schedule approved by the department. The owner is not required to begin this additional monitoring until two months after notification that data have been rejected and additional monitoring is necessary.
C. The owner of a waterworks that plans to make a significant change to the disinfection practice shall develop disinfection profiles and calculate disinfection benchmarks as described in 12VAC5-590-500.
1. The owner shall notify the department before changing the disinfection practice and shall include in this notice the following information:
a. A completed disinfection profile and disinfection benchmark for Giardia lamblia and viruses;
b. A description of the proposed change in disinfection practice; and
c. An analysis of how the proposed change will affect the current level of disinfection.
2. Significant changes to the disinfection practice are defined as follows:
a. Changes to the point of disinfection;
b. Changes to any disinfectant used in the water treatment plant;
c. Changes to the disinfection process; or
d. Any other modification identified by the department as a significant change to disinfection practice.
D. The owner shall determine the Cryptosporidium treatment bin classification as described in subdivision D 1 of this section and provide additional treatment for Cryptosporidium, if required, as described in subdivision D 2 of this section. The owner shall implement Cryptosporidium treatment according to the schedule in subdivision D 3 of this section.
1. Bin classification for waterworks.
a. Following completion of the initial round of source water monitoring required under subdivision B 1 of this section, the owner shall calculate an initial Cryptosporidium bin concentration for each water treatment plant for which monitoring was required. Calculation of the bin concentration shall use the Cryptosporidium results reported under subdivision B 1 of this section and shall follow these procedures:
(1) For the owner who collects a total of at least 48 samples, the bin concentration is equal to the arithmetic mean of all sample concentrations.
(2) For the owner who collects a total of at least 24 samples, but not more than 47 samples, the bin concentration is equal to the highest arithmetic mean of all sample concentrations in any 12 consecutive months during which Cryptosporidium samples were collected.
(3) For the owner of a waterworks that serves fewer than 10,000 people and monitors for Cryptosporidium for only one year (i.e., collect 24 samples in 12 months), the bin concentration is equal to the arithmetic mean of all sample concentrations.
(4) For water treatment plants that operate only part of the year and that monitor fewer than 12 months per year under subdivision B 1 of this section, the bin concentration is equal to the highest arithmetic mean of all sample concentrations during any year of Cryptosporidium monitoring.
(5) If the monthly Cryptosporidium sampling frequency varies, then the owner shall first calculate a monthly average for each month of monitoring. The owner shall then use these monthly average concentrations, rather than individual sample concentrations, in the applicable calculation for bin classification in subdivisions D 1 a (1) through D 1 a (4) of this section.
b. The owner shall determine the initial bin classification from Table 401.2 using the Cryptosporidium bin concentration calculated under subdivision D 1 a of this section:
c. Following completion of the second round of source water monitoring required under subdivision B 2 of this section, the owner shall recalculate the Cryptosporidium bin concentration using the Cryptosporidium results reported under subdivision B 2 of this section and following the procedures in subdivisions D 1 a (1) through D 1 a (4) of this section. The owner shall then redetermine the bin classification using this bin concentration and Table 401.3.
d. Reporting of bin classifications.
(1) The owner shall report the initial bin classification under subdivision D 1 b of this section to the department for approval no later than six months after the waterworks is required to complete the initial source water monitoring based on the schedule in subdivision B 3 of this section.
(2) The owner shall report the bin classification under subdivision D 1 c of this section to the department for approval no later than six months after the owner is required to complete the second round of source water monitoring based on the schedule in subdivision D 1 a (3) of this section.
(3) The bin classification report to the department shall include a summary of source water monitoring data and the calculation procedure used to determine bin classification.
e. Failure to comply with the conditions of subdivision D 1 d of this section is a violation of the treatment technique requirement.
2. Waterworks additional Cryptosporidium treatment requirements.
a. A waterworks shall provide the level of additional treatment for Cryptosporidium specified in this subdivision based on the bin classification as determined under subdivision D 1 of this section and according to the schedule in subdivision D 3 b of this section.
b. Additional treatment.
(1) The owner shall use one or more of the treatment and management options listed in subsection E of this section, termed the microbial toolbox, to comply with the additional Cryptosporidium treatment required in subdivision D 2 a of this section.
(2) A waterworks classified in Bin 3 and Bin 4 shall achieve at least 1-log of the additional Cryptosporidium treatment required under subdivision D 2 a of this section using either one or a combination of the following: (i) bag filters, (ii) bank filtration, (iii) cartridge filters, (iv) chlorine dioxide, (v) membranes, (vi) ozone, or (vii) UV as described in subdivisions E 3 through E 7 of this section.
c. Failure by a waterworks in any month to achieve treatment credit by meeting criteria in subdivisions E 3 through E 7 of this section for microbial toolbox options that is at least equal to the level of treatment required in subdivision D 2 a of this section is a violation of the treatment technique requirement.
d. If the department determines during a sanitary survey or an equivalent source water assessment that after an owner completed the monitoring conducted under subdivision B 1 or B 2 of this section, significant changes occurred in the waterworks watershed that could lead to increased contamination of the source water by Cryptosporidium, then the owner shall take actions specified by the department to address the contamination. These actions may include additional source water monitoring or implementing microbial toolbox options listed in subdivision E 2 of this section.
3. Schedule for compliance with Cryptosporidium treatment requirements.
a. Following the initial bin classification in accordance with subdivision D 1 b of this section, the owner shall provide the level of treatment for Cryptosporidium required under subdivision D 2 of this section according to the schedule in subdivision D 3 b of this section.
b. If the bin classification for a filtered waterworks changes following the second round of source water monitoring, as determined under subdivision D 1 c of this section, then the owner shall provide the level of treatment for Cryptosporidium required under subdivision D 2 of this section on a schedule approved by the department.
E. The owner of a waterworks required to provide additional treatment for Cryptosporidium shall implement microbial toolbox options that are designed and operated as described in subdivisions E 1 through E 7 of this section.
1. The owner receives the treatment credits listed in Table 401.4 by meeting the conditions for microbial toolbox options described in subdivisions E 3 through E 7 of this section. The owner shall apply these treatment credits to meet the treatment requirements in subdivision D 2 of this section.
2. Microbial Toolbox Summary Table: Options, Treatment Credits and Criteria.
3. Source toolbox components.
a. Reserved.
b. Alternative source.
(1) The owner may conduct source water monitoring that reflects a different intake location (either in the same source or for an alternate source) or a different procedure for the timing or level of withdrawal from the source (alternative source water monitoring). If the department approves, then the owner may determine the bin classification under subdivision D 1 of this section based on the alternative source water monitoring results.
(2) If the owner conducts alternative source water monitoring under subdivision E 3 b (1) of this section, then the owner shall also monitor the current water treatment plant intake concurrently as described in subsection B of this section. "Plant intake" means the works or structures at the head of a conduit through which source water is diverted (e.g., river or lake) into the water treatment plant.
(3) Alternative source water monitoring under subdivision E 3 b (1) of this section shall meet the requirements for source water monitoring to determine bin classification, as described in subdivisions B 1 through B 13 of this section. The owner shall report the alternative source water monitoring results to the department, along with supporting information documenting the operating conditions under which the samples were collected.
(4) If the owner determines the bin classification under subdivision D 1 of this section using alternative source water monitoring results that reflect a different intake location or a different procedure for managing the timing or level of withdrawal from the source, then the owner shall relocate the intake or permanently adopt the withdrawal procedure, as applicable, no later than the applicable treatment compliance date in subdivision D 3 of this section.
4. Prefiltration treatment toolbox components.
a. Presedimentation. The owner receives 0.5-log Cryptosporidium treatment credit for a presedimentation basin during any month the process meets the following criteria:
(1) The presedimentation basin shall be in continuous operation and shall treat the entire water treatment plant flow at a waterworks using a surface water source, a GUDI source, or both.
(2) A coagulant shall be continuously added to the presedimentation basin.
(3) The presedimentation basin shall achieve the performance criteria in either of the following:
(a) Demonstrates at least 0.5-log mean reduction of influent turbidity. This reduction shall be determined using daily turbidity measurements in the presedimentation process influent and effluent and shall be calculated as follows: log10 (monthly mean of daily influent turbidity) - log10 (monthly mean of daily effluent turbidity).
(b) Complies with the performance criteria approved by the department that demonstrate at least 0.5-log mean removal of micron-sized particulate material through the presedimentation process.
b. Two-stage lime softening. The owner receives an additional 0.5-log Cryptosporidium treatment credit for a two-stage lime softening plant if chemical addition and hardness precipitation occur in two separate and sequential softening stages before filtration. Both softening stages shall treat the entire plant flow taken from a surface water source, a GUDI source, or both.
c. Bank filtration. The owner receives Cryptosporidium treatment credit for bank filtration that serves as pretreatment to a water filtration plant by meeting the criteria in this subdivision. The owner using bank filtration upon beginning source water monitoring under subdivision B 1 of this section shall collect samples as described in subdivision B 6 d of this section and is not eligible for this credit.
(1) Wells with a groundwater flow path of at least 25 feet receive 0.5-log treatment credit; and wells with a groundwater flow path of at least 50 feet receive 1.0-log treatment credit. The groundwater flow path shall be determined as specified in subdivision E 4 c (4) of this section.
(2) Only wells in granular aquifers are eligible for treatment credit. Granular aquifers are those comprised of sand, clay, silt, rock fragments, pebbles or larger particles, and minor cement. The owner shall characterize the aquifer at the well site to determine aquifer properties. The owner shall extract a core from the aquifer and demonstrate that in at least 90% of the core length, grains less than 1.0 mm in diameter constitute at least 10% of the core material.
(3) Only horizontal and vertical wells are eligible for treatment credit.
(4) For vertical wells, the groundwater flow path is the measured distance from the edge of the surface water body under high flow conditions (determined by the 100-year flood elevation boundary or by the floodway, as defined in Federal Emergency Management Agency flood hazard maps) to the well screen. For horizontal wells, the groundwater flow path is the measured distance from the bed of the river under normal flow conditions to the closest horizontal well lateral screen.
(5) The owner shall monitor each wellhead for turbidity at least once every four hours while the bank filtration process is in operation. If monthly average turbidity levels, based on daily maximum values in the well, exceed 1 NTU, the owner shall report this result to the department and conduct an assessment within 30 days to determine the cause of the high turbidity levels in the well. If the department determines that microbial removal has been compromised, the department may revoke treatment credit until the owner implements corrective actions approved by the department to remediate the problem.
(6) Springs and infiltration galleries are not eligible for treatment credit under this section.
(7) Bank filtration demonstration of performance. The department may approve Cryptosporidium treatment credit for bank filtration based on a demonstration-of-performance study that meets the criteria in this subdivision. This treatment credit may be greater than 1.0-log and may be awarded to bank filtration that does not meet the criteria in subdivisions E 4 c (1) through E 4 c (5) of this section.
(a) The study shall follow a protocol approved by the department and shall involve the collection of data on the removal of Cryptosporidium or a surrogate for Cryptosporidium and related hydrogeologic and water quality parameters during the full range of operating conditions.
(b) The study shall include sampling both from any production well and from monitoring wells that are screened and located along the shortest flow path between the surface water source and the production well.
5. Treatment performance toolbox components.
a. Combined filter performance. The owner using conventional filtration treatment or direct filtration treatment receives an additional 0.5-log Cryptosporidium treatment credit during any month the waterworks meets the criteria in this subdivision. Combined filter effluent (CFE) turbidity shall be less than or equal to 0.15 NTU in at least 95% of the measurements. Turbidity shall be measured as described in 12VAC5-590-376 B.
b. Individual filter performance. The owner using conventional filtration treatment or direct filtration treatment receives 0.5-log Cryptosporidium treatment credit, which can be in addition to the 0.5-log credit under subdivision E 5 a of this section, during any month the waterworks meets the criteria in this subdivision. Compliance with these criteria shall be based on individual filter turbidity monitoring as described in 12VAC5-590-376 B.
(1) The filtered water turbidity for each individual filter shall be less than or equal to 0.15 NTU in at least 95% of the measurements recorded each month.
(2) No individual filter may have a measured turbidity greater than 0.3 NTU in two consecutive measurements collected 15 minutes apart.
(3) The owner that has received treatment credit for individual filter performance and fails to meet the requirements of subdivision E 5 b (1) or E 5 b (2) of this section during any month does not receive a treatment technique violation under subdivision D 2 c of this section if the department determines the following:
(a) The failure was due to unusual and short-term circumstances that could not reasonably be prevented through optimizing water treatment plant design, operation, and maintenance.
(b) The waterworks has experienced no more than two failures in any calendar year.
6. Additional filtration toolbox components.
a. Bag and cartridge filters. The owner receives Cryptosporidium treatment credit of up to 2.0-log for individual bag or cartridge filters and up to 2.5-log for bag or cartridge filters operated in series by meeting the criteria in subdivisions E 6 a (1) through E 6 a (10) of this section. To be eligible for this credit, the owner shall report the results of challenge testing that meets the requirements of subdivisions E 6 a (2) through E 6 a (9) of this section to the department. The filters shall treat the entire water treatment plant flow taken from a surface water source, a GUDI source, or both.
(1) The Cryptosporidium treatment credit awarded to bag or cartridge filters shall be based on the removal efficiency demonstrated during challenge testing that is conducted according to the criteria in subdivisions E 6 a (2) through E 6 a (9) of this section. A factor of safety equal to 1-log for individual bag or cartridge filters and 0.5-log for bag or cartridge filters in series shall be applied to challenge testing results to determine removal credit. The owner may use the results from challenge testing conducted before January 5, 2006, if the prior testing was consistent with the criteria specified in subdivisions E 6 a (2) through E 6 a (9) of this section.
(2) Challenge testing shall be performed on full-scale bag or cartridge filters, and the associated filter housing or pressure vessel, that are identical in material and construction to the filters and housings the waterworks will use for removal of Cryptosporidium. Bag or cartridge filters shall be challenge tested in the same configuration that the waterworks will use, either as individual filters or as a series configuration of filters.
(3) Challenge testing shall be conducted using Cryptosporidium or a surrogate that is removed no more efficiently than Cryptosporidium. The microorganism or surrogate used during challenge testing is referred to as the challenge particulate. The concentration of the challenge particulate shall be determined using a method capable of discreetly quantifying the specific microorganism or surrogate used in the test; gross measurements such as turbidity shall not be used.
(4) The maximum feed water concentration that can be used during a challenge test shall be based on the detection limit of the challenge particulate in the filtrate (i.e., filtrate detection limit) and shall be calculated using the following equation:
Maximum Feed Concentration = 1 x 104 x (Filtrate Detection Limit)
(5) Challenge testing shall be conducted at the maximum design flow rate for the filter as specified by the manufacturer.
(6) Each filter evaluated shall be tested for a duration sufficient to reach 100% of the terminal pressure drop that establishes the maximum pressure drop under which the filter may be used to comply with the requirements of this subdivision E 6.
(7) Removal efficiency of a filter shall be determined from the results of the challenge test and expressed in terms of log removal values using the following equation:
LRV = LOG10(Cf) - LOG10(Cp),
where LRV = log removal value demonstrated during challenge testing;
Cf = the feed concentration measured during the challenge test; and
Cp = the filtrate concentration measured during the challenge test.
In applying this equation, the same units shall be used for the feed and filtrate concentrations. If the challenge particulate is not detected in the filtrate, then the term Cp shall be set equal to the detection limit.
(8) Each filter tested shall be challenged with the challenge particulate during three periods over the filtration cycle: within two hours of start-up of a new filter; when the pressure drop is between 45% and 55% of the terminal pressure drop; and at the end of the cycle after the pressure drop has reached 100% of the terminal pressure drop. An LRV shall be calculated for each of these challenge periods for each filter tested. The LRV for the filter (LRV filter) shall be assigned the value of the minimum LRV observed during the three challenge periods for that filter.
(9) If fewer than 20 filters are tested, then the overall removal efficiency for the filter product line shall be set equal to the lowest LRV filter among the filters tested. If 20 or more filters are tested, then the overall removal efficiency for the filter product line shall be set equal to the 10th percentile of the set of LRV filter values for the various filters tested. The percentile is defined by (i/(n+1)), where i is the rank of n individual data points ordered lowest to highest. If necessary, the 10th percentile may be calculated using linear interpolation.
(10) If a previously tested filter is modified in a manner that could change the removal efficiency of the filter product line, then challenge testing to demonstrate the removal efficiency of the modified filter shall be conducted and submitted to the department.
b. Membrane filtration.
(1) The owner receives Cryptosporidium treatment credit for membrane filtration that meets the criteria of this subdivision E 6 b. Membrane cartridge filters that meet the definition of membrane filtration in 12VAC5-590-10 are eligible for this credit. The level of treatment credit the owner receives is equal to the lower of the values determined as follows:
(a) The removal efficiency demonstrated during challenge testing conducted under the conditions in subdivision E 6 b (2) of this section.
(b) The maximum removal efficiency that can be verified through direct integrity testing used with the membrane filtration process under the conditions in subdivision E 6 b (3) of this section.
(2) Challenge Testing. The membrane used by the waterworks shall undergo challenge testing to evaluate removal efficiency and the owner shall report the results of the challenge testing to the department. Challenge testing shall be conducted according to the criteria in subdivisions E 6 b (2) (a) through E 6 b (2) (g) of this section. The owner may use data from challenge testing conducted before January 5, 2006, if the prior testing was consistent with the following criteria:
(a) Challenge testing shall be conducted on either a full-scale membrane module, identical in material and construction to the membrane modules used in the waterworks treatment facility, or a smaller-scale membrane module, identical in material and similar in construction to the full-scale module. A module is defined as the smallest component of a membrane unit in which a specific membrane surface area is housed in a device with a filtrate outlet structure.
(b) Challenge testing shall be conducted using Cryptosporidium or a surrogate that is removed no more efficiently than Cryptosporidium. The organism or surrogate used during challenge testing is referred to as the challenge particulate. The concentration of the challenge particulate, in both the feed and filtrate water, shall be determined using a method capable of discretely quantifying the specific challenge particulate used in the test; gross measurements such as turbidity shall not be used.
(c) The maximum feed water concentration that can be used during a challenge test is based on the detection limit of the challenge particulate in the filtrate and shall be determined according to the following equation:
Maximum Feed Concentration = 3.16 x 106 x (Filtrate Detection Limit)
(d) Challenge testing shall be conducted under representative hydraulic conditions at the maximum design flux and maximum design process recovery specified by the manufacturer for the membrane module. Flux is defined as the throughput of a pressure-driven membrane process expressed as flow per unit of membrane area. Recovery is defined as the volumetric percent of feed water that is converted to filtrate over the course of an operating cycle uninterrupted by events such as chemical cleaning or a solids removal process (i.e., backwashing).
(e) Removal efficiency of a membrane module shall be calculated from the challenge test results and expressed as a log removal value according to the following equation:
LRV = LOG10(Cf) - LOG10(Cp),
where LRV = log removal value demonstrated during the challenge test;
Cf = the feed concentration measured during the challenge test; and
Cp = the filtrate concentration measured during the challenge test.
Equivalent units shall be used for the feed and filtrate concentrations. If the challenge particulate is not detected in the filtrate, then the term Cp is set equal to the detection limit for the purpose of calculating the LRV. An LRV shall be calculated for each membrane module evaluated during the challenge test.
(f) The removal efficiency of a membrane filtration process demonstrated during challenge testing shall be expressed as a log removal value (LRVC-Test). If fewer than 20 modules are tested, then LRVC-Test is equal to the lowest of the representative LRVs among the modules tested. If 20 or more modules are tested, then LRVC-Test is equal to the 10th percentile of the representative LRVs among the modules tested. The percentile is defined by (i/(n+1)), where i is the rank of n individual data points ordered lowest to highest. If necessary, the 10th percentile may be calculated using linear interpolation.
(g) The challenge test shall establish a QCRV for a nondestructive performance test that demonstrates the Cryptosporidium removal capability of the membrane filtration module. This performance test shall be applied to each production membrane module used by the waterworks that was not directly challenge tested to verify Cryptosporidium removal capability. Production modules that do not meet the established QCRV are not eligible for the treatment credit demonstrated during the challenge test.
(h) If a previously tested membrane is modified in a manner that could change the removal efficiency of the membrane or the applicability of the nondestructive performance test and associated QCRV, then additional challenge testing to demonstrate the removal efficiency of, and determine a new QCRV for, the modified membrane shall be conducted and submitted to the department.
(3) Direct integrity testing. The owner shall conduct direct integrity testing in a manner that demonstrates a removal efficiency equal to or greater than the removal credit awarded to the membrane filtration process and meets the requirements described in subdivisions E 6 b (3) (a) through E 6 b (3) (f) of this section. A direct integrity test is defined as a physical test applied to a membrane unit to identify and isolate integrity breaches (i.e., one or more leaks that could result in contamination of the filtrate).
(a) The direct integrity test shall be independently applied to each membrane unit in service. A membrane unit is defined as a group of membrane modules that share common valving that allows the unit to be isolated from the rest of the waterworks for the purpose of integrity testing or other maintenance.
(b) The direct integrity method shall have a resolution of three micrometers or less, where resolution is defined as the size of the smallest integrity breach that contributes to a response from the direct integrity test.
(c) The direct integrity test shall have a sensitivity sufficient to verify the log treatment credit awarded to the membrane filtration process by the department, where sensitivity is defined as the maximum log removal value that can be reliably verified by a direct integrity test. Sensitivity shall be determined using the approach in either of the following as applicable to the type of direct integrity test the waterworks uses:
(i) For direct integrity tests that use an applied pressure or vacuum, the direct integrity test sensitivity shall be calculated according to the following equation:
LRVDIT = LOG10(Qp /(VCF x Qbreach)),
where LRVDIT = the sensitivity of the direct integrity test;
Qp = total design filtrate flow from the membrane unit;
Qbreach = flow of water from an integrity breach associated with the smallest integrity test response that can be reliably measured; and
VCF = volumetric concentration factor.
The volumetric concentration factor is the ratio of the suspended solids concentration on the high-pressure side of the membrane relative to that in the feed water.
(ii) For direct integrity tests that use a particulate or molecular marker, the direct integrity test sensitivity shall be calculated according to the following equation:
LRVDIT = LOG10(Cf) - LOG10(Cp),
where LRVDIT = the sensitivity of the direct integrity test;
Cf = the typical feed concentration of the marker used in the test; and
Cp = the filtrate concentration of the marker from an integral membrane unit.
(d) The owner shall establish a control limit within the sensitivity limits of the direct integrity test that is indicative of an integral membrane unit capable of meeting the removal credit awarded by the department.
(e) If the result of a direct integrity test exceeds the control limit established under subdivision E 6 b (3) (d) of this section, then the owner shall remove the membrane unit from service. The owner shall conduct a direct integrity test to verify any repairs, and may return the membrane unit to service only if the direct integrity test is within the established control limit.
(f) The owner shall conduct direct integrity testing on each membrane unit at a frequency of not less than once each day that the membrane unit is in operation. The department may approve less frequent testing based on demonstrated process reliability, the use of multiple barriers effective for Cryptosporidium, or reliable process safeguards.
(4) Indirect integrity monitoring. The owner shall conduct continuous indirect integrity monitoring on each membrane unit according to the criteria in subdivisions E 6 b (4) (a) through E 6 b (4) (e). Indirect integrity monitoring is defined as monitoring some aspect of filtrate water quality that is indicative of the removal of particulate matter. The owner that implements continuous direct integrity testing of membrane units in accordance with the criteria in subdivisions E 6 b (3) (a) through E 6 b (3) (f) of this section is not subject to the requirements for continuous indirect integrity monitoring. The owner shall submit a monthly report to the department summarizing all continuous indirect integrity monitoring results triggering direct integrity testing and the corrective action that was taken in each case.
(a) Unless the department approves an alternative parameter, continuous indirect integrity monitoring shall include continuous filtrate turbidity monitoring.
(b) Continuous monitoring shall be conducted at a frequency of no less than once every 15 minutes.
(c) Continuous monitoring shall be separately conducted on each membrane unit.
(d) If indirect integrity monitoring includes turbidity and if the filtrate turbidity readings are above 0.15 NTU for a period greater than 15 minutes (i.e., two consecutive 15-minute readings above 0.15 NTU), direct integrity testing shall immediately be performed on the associated membrane unit as specified in subdivisions E 6 b (3) (a) through E 6 b (3) (f) of this section.
(e) If indirect integrity monitoring includes an alternative parameter approved by the department and if the alternative parameter exceeds a control limit approved by the department for a period greater than 15 minutes, then direct integrity testing shall immediately be performed on the associated membrane units as specified in subdivisions E 6 b (3) (a) through E 6 b (3) (f) of this section.
c. Second stage filtration. The owner receives 0.5-log Cryptosporidium treatment credit for a separate second stage of filtration that consists of sand, dual media, GAC, or other fine grain media following granular media filtration if approved by the department. To be eligible for this credit, the first stage of filtration shall be preceded by a coagulation step and both filtration stages shall treat the entire water treatment treatment plant flow taken from a surface water source, a GUDI source, or both. A cap, such as GAC, on a single stage of filtration is not eligible for this credit. The department shall approve the treatment credit based on an assessment of the design characteristics of the filtration process.
d. Slow sand filtration as secondary filter. The owner is eligible to receive 2.5-log Cryptosporidium treatment credit for a slow sand filtration process that follows a separate stage of filtration if both filtration stages treat the entire water treatment plant flow taken from a surface water source, a GUDI source, or both and no residual disinfectant is present in the influent water to the slow sand filtration process. The department shall approve the treatment credit based on an assessment of the design characteristics of the filtration process. This subdivision does not apply to treatment credit awarded to slow sand filtration used as a primary filtration process.
7. Inactivation toolbox components.
a. Calculation of CT values.
(1) CT is the product of the disinfectant contact time (T, in minutes) and disinfectant concentration (C, in milligrams per liter). The owner of a waterworks with treatment credit for chlorine dioxide or ozone under subdivision E 7 b of this section shall calculate CT at least once each day, with both C and T measured during peak hourly flow in accordance with the procedure listed in 12VAC5-590-500.
(2) A waterworks with several disinfection segments in sequence may calculate CT for each segment, where a disinfection segment is defined as a treatment unit process with a measurable residual disinfectant level and a liquid volume. Under this approach, the owner shall add the Cryptosporidium CT values in each segment to determine the total CT for the treatment plant.
b. CT values for chlorine dioxide and ozone.
(1) The owner receives the Cryptosporidium treatment credit listed in Table 401.5 by meeting the corresponding chlorine dioxide CT value for the applicable water temperature, as described in subdivision E 7 a of this section.
(2) The owner receives the Cryptosporidium treatment credit listed in Table 401.6 by meeting the corresponding ozone CT values for the applicable water temperature, as described in subdivision E 7 a of this section.
c. UV light. The owner receives Cryptosporidium, Giardia lamblia, and virus treatment credits for UV light reactors by achieving the corresponding UV dose values shown in subdivision E 7 c (1) of this section. The owner shall validate and monitor UV reactors as described in subdivisions E 7 c (2) and E 7 c (3) of this section to demonstrate that they are achieving a particular UV dose value for treatment credit.
(1) UV dose table. The treatment credits listed in Table 401.7 are for UV light at a wavelength of 254 nm as produced by a low-pressure mercury vapor lamp. To receive treatment credit for other lamp types, the owner shall demonstrate an equivalent germicidal dose through reactor validation testing as described in subdivision E 7 c (2) of this section. The UV dose values listed in Table 401.7 are applicable only to post-filter applications of UV in filtered waterworks.
(2) Reactor validation testing. The owner shall use UV reactors that have undergone validation testing to determine the operating conditions under which the reactor delivers the UV dose required in subdivision E 7 c (1) of this section (i.e., validated operating conditions). These operating conditions shall include flow rate, UV intensity as measured by a UV sensor, and UV lamp status.
(a) When determining validated operating conditions, the owner shall account for the following factors: (i) UV absorbance of the water; (ii) lamp fouling and aging; (iii) measurement uncertainty of online sensors; (iv) UV dose distributions arising from the velocity profiles through the reactor; (v) failure of UV lamps or other critical waterworks components; and (vi) inlet and outlet piping or channel configurations of the UV reactor.
(b) Validation testing shall include the following: full-scale testing of a reactor that conforms uniformly to the UV reactors used by the waterworks and inactivation of a test microorganism whose dose-response characteristics have been quantified with a low-pressure mercury vapor lamp.
(c) UV reactor validation testing shall be in accordance with EPA's recommended validation protocol for UV reactors, as described in EPA's "Ultraviolet Disinfection Guidance Manual for the Final Long Term 2 Enhanced Surface Water Treatment Rule," November 2006, EPA Office of Water. Alternative protocols may be considered for approval by the department on a case-by-case basis.
(d) Validation testing, whether onsite or offsite, shall be performed by a third party independent of the UV reactor manufacturer and the owner to ensure that validation testing and data analysis are conducted in a technically sound manner without bias.
(e) To receive credit for lamp types other than low-pressure types, the owner shall demonstrate an equivalent germicidal dose through reactor validation testing.
(f) A validation report shall be submitted and approved by the department to receive disinfection credit.
(3) UV reactor monitoring.
(a) The owner shall monitor the UV reactors to determine if the reactors are operating within validated conditions as determined under subdivision E 7 c (2) of this section. This monitoring shall include UV intensity as measured by a UV sensor, flow rate, lamp status, and other parameters the department designates based on UV reactor operation. The owner shall verify the calibration of UV sensors and shall recalibrate sensors in accordance with a protocol approved by the department.
(b) To receive treatment credit for UV light, the owner shall treat at least 95% of the water delivered to the public during each month by the UV reactors operating within validated conditions for the required UV dose as described in subdivisions E 7 c (1) and E 7 c (2) of this section. The owner shall demonstrate compliance with this condition by the monitoring required under subdivision E 7 c (3) (a) of this section.
F. The owner shall comply with the applicable recordkeeping and reporting requirements described in 12VAC5-590-530, 12VAC5-590-531, 12VAC5-590-550, and 12VAC5-590-570.
12VAC5-590-405. Lead and copper treatment techniques.
A. Lead and copper corrosion control techniques.
1. Corrosion control treatment requirements. The owners owner of all a community and nontransient noncommunity waterworks waterworks or a NTNC shall install and operate optimum corrosion control treatment by completing the corrosion control treatment requirements described below which are applicable to such owners these waterworks under subdivision A 2 of this section.
a. Owner's proposal regarding corrosion control treatment. Based upon the results of lead and copper tap monitoring and water quality parameter monitoring, the owners owner of a small and or a medium waterworks exceeding the lead or copper action level AL shall propose installation of one or more of the corrosion control treatments listed in subdivision A 1 c (1) of this section that the owner believes constitutes optimal corrosion control for that waterworks. The commissioner department may require the owner to conduct additional water quality parameter monitoring in accordance with 12VAC5-590-375 C 2 to assist the commissioner department in reviewing evaluating the proposal.
b. Applicability of studies of corrosion control treatment (applicable to small and medium waterworks). The commissioner department may require the owner of any a small or a medium waterworks that exceeds the lead or copper action level AL to perform corrosion control studies under subdivision A 1 c of this section to identify optimal corrosion control treatment for the waterworks.
c. Corrosion control studies.
(1) The owner of any a waterworks required by the commissioner department to perform corrosion control studies shall evaluate the effectiveness of each of the following treatments, and, if appropriate, combinations of the following treatments to identify the optimal corrosion control treatment for that waterworks:
(a) Alkalinity and pH adjustment;
(b) Calcium hardness adjustment; and
(c) The addition of a phosphate phosphate-based or silicate based silicate-based corrosion inhibitor at a concentration sufficient to maintain an effective corrosion inhibitor residual concentration in all test tap samples, such that a passivating film is formed on the interior walls of the pipe.
(2) The owner shall evaluate each of the corrosion control treatments using either pipe rig/loop rig or loop tests, metal coupon tests, partial-system tests, or analyses based on documented analogous treatments with other waterworks of similar size, water chemistry, and distribution system configuration.
(3) The owner shall measure the following water quality parameters in any tests conducted under subdivision A 1 c of this section before and after evaluating the corrosion control treatments listed above in subdivision A 1 c (1) of this section:
(a) Lead;
(b) Copper;
(c) pH;
(d) Alkalinity;
(e) Calcium;
(f) Conductivity;
(g) Orthophosphate (when an inhibitor containing a phosphate compound is used);
(h) Silicate (when an inhibitor containing a silicate compound is used); and
(i) Water temperature.
(4) The owner shall identify all chemical or physical constraints that limit or prohibit the use of a particular corrosion control treatment and document such constraints with at least one of the following:
(a) Data and documentation showing that a particular corrosion control treatment has adversely affected other water treatment processes when used by another waterworks with comparable water quality characteristics; or
(b) Data and documentation demonstrating that the owner has previously attempted to evaluate a particular corrosion control treatment and has found that the treatment is ineffective or adversely affects other water quality treatment processes.
(5) The owner shall evaluate the effect of the chemicals used for corrosion control treatment on other water quality treatment processes.
(6) On the basis of an analysis of the data generated during each evaluation, the owner shall propose in writing to the district engineer in writing, department that the treatment option that resulting from the corrosion control studies indicate constitutes optimal corrosion control treatment for that waterworks. The owner shall provide a rationale for its the recommendation along with all supporting documentation specified in subdivisions A 1 c (1) through A 1 c (5) of this section.
d. Approval of optimal corrosion control treatment.
(1) Based upon consideration of available information including, where applicable, studies performed under subdivision A 1 c of this section and an the owner's proposed treatment alternative, the commissioner department shall either approve the corrosion control treatment option recommended by the owner, or designate alternative corrosion control treatment or treatments from among those listed in subdivision A 1 c (1) of this section. When approving optimal treatment, the commissioner department shall consider the effects that additional corrosion control treatment will have on water quality parameters and on other water quality treatment processes.
(2) The commissioner department shall notify the owner of his the determination on optimal corrosion control treatment in writing and explain the basis for this determination. If the commissioner department requests additional information to aid a review an evaluation, then the owner shall provide the information.
e. Installation of optimal corrosion control. Each The owner shall properly install and operate throughout the waterworks the optimal corrosion control treatment approved by the commissioner department under subdivision A 1 d of this section. Also see 12VAC5-590-190 A construction permit is required before installation of any treatment in accordance with 12VAC5-590-200.
f. Commissioner's review The department's evaluation of treatment and specification of the optimal water quality control parameters. shall consist of the following:
(1) The commissioner department shall evaluate the results of all lead and copper tap samples and water quality parameter samples submitted by the owner and determine whether the owner has properly installed and operated the optimal corrosion control treatment approved by the commissioner department under subdivision A 1 d of this section. Upon reviewing evaluating the results of tap water and water quality parameter monitoring by the owner, both before and after the owner installs optimal corrosion control treatment, the commissioner department shall designate:
(a) A minimum value or a range of values for pH measured at each entry point to the distribution system;
(b) A minimum pH value, measured in all tap samples. Such The value shall be equal to or greater than 7.0, unless the commissioner department determines that meeting a pH level of 7.0 is not technologically feasible or is not necessary for the owner to optimize corrosion control;
(c) If a corrosion inhibitor is used, then a minimum concentration or a range of concentrations for the inhibitor, measured at each entry point to the distribution system and in all tap samples, that the commissioner department determines is necessary to form a passivating film on the interior walls of the pipes of the distribution system;
(d) If alkalinity is adjusted as part of the optimal corrosion control treatment, then a minimum concentration or a range of concentrations for alkalinity, measured at each entry point to the distribution system and in all tap samples; or
(e) If calcium carbonate stabilization is used as part of the corrosion control, then a minimum concentration or a range of concentrations for calcium, measured in all tap samples.
(2) The values for the applicable water quality control parameters listed above in subdivision A 1 c (3) of this section shall be those that the commissioner department determines to reflect optimal corrosion control treatment for the waterworks. The commissioner department may designate values for additional water quality control parameters determined by the commissioner department to reflect optimal corrosion control for the waterworks. The commissioner department shall notify the owner in writing of these determinations and explain the basis for his the decisions.
g. Continued operation and monitoring. The owners owner of all a waterworks optimizing corrosion control shall continue to operate and maintain optimal corrosion control treatment, including maintaining water quality parameters at or above minimum values or within ranges designated by the commissioner department under subdivision A 1 f of this section as verified by all samples collected under 12VAC5-590-375 C 4 through,12VAC5-590-375 C 5, and 12VAC5-590-375 C 6. Compliance with the requirements of this subdivision shall be determined every six months, as specified under 12VAC5-590-375 C 4. The owner of a waterworks is out of compliance with the requirements of this subdivision for a six-month period if excursions occur for any commissioner-specified department-specified parameter on more than nine days during the period. An excursion occurs whenever the daily value for one or more of the water quality parameters measured at a sampling location is below the minimum value or outside the range designated by the commissioner department. Daily values shall be calculated as follows. The commissioner department has discretion to delete results of obvious sampling errors from this calculation. Daily values shall be calculated as follows:
(1) On days when more than one measurement for the water quality parameter is collected at the sampling location, the daily value shall be the average of all results collected during the day regardless of whether they are collected through continuous monitoring, grab sampling, or a combination of both.
(2) On days when only one measurement for the water quality parameter is collected at the sampling location, the daily value shall be the result of that measurement.
(3) On days when no measurement is collected for the water quality parameter at the sampling location, the daily value shall be the daily value calculated on the most recent day on which the water quality parameter was measured at the sample site.
h. Modification of the commissioner's department's treatment decisions. Upon his own the department's initiative or in response to a request by an owner or other interested party, the commissioner department may modify his the determination of the optimal corrosion control treatment under subdivision A 1 d of this section or optimal water quality control parameters under subdivision A 1 f of this section. A request for modification by an owner or other interested party shall be in writing, explain why the modification is appropriate, and provide supporting documentation. The commissioner department may modify the determination where it is concluded that such the change is necessary to ensure that the waterworks continues to optimize corrosion control treatment. A revised determination shall be made in writing, set forth the new treatment requirements, explain the basis for the commissioner's department's decision, and provide an implementation schedule for completing the treatment modifications.
2. Corrosion control treatment steps.
a. Owners The owner shall complete the applicable corrosion control treatment requirements described in subdivision A 1 of this section by the deadlines established in this subdivision.
(1) The owner of a large waterworks (serving > greater than 50,000 persons) shall complete the corrosion control treatment steps specified in subdivision A 2 d of this section, unless the owner is deemed to have optimized corrosion control under subdivision A 2 b (2) or subdivision A 2 b (3) of this section.
(2) The owner of a small waterworks (serving ≤ fewer than or equal to 3300 persons) and or a medium waterworks (serving > greater than 3,300 and ≤ fewer than or equal to 50,000 persons) shall complete the corrosion control treatment steps specified in subdivision A 2 e of this section, unless the owner is deemed to have optimized corrosion control under subdivisions A 2 b (1) through A 2 b (3) of this section.
b. An The owner is deemed to have optimized corrosion control and is not required to complete the applicable corrosion control treatment steps identified in this subdivision if the waterworks satisfies one of the criteria specified in subdivisions A 2 b (1) through A 2 b (3) of this section. Any such The owner deemed to have optimized corrosion control under this subdivision, and which has to have treatment in place, shall continue to operate and maintain optimal corrosion control treatment and meet any requirements that the commissioner department determines appropriate to ensure optimal corrosion control treatment is maintained.
(1) The owner of a small or a medium waterworks is deemed to have optimized corrosion control if the waterworks meets the lead and copper action levels ALs during each of two consecutive six-month monitoring periods conducted in accordance with 12VAC5-590-375.
(2) Any The owner may be deemed by the commissioner department to have optimized corrosion control treatment if the owner demonstrates to the satisfaction of the commissioner department that the owner has conducted activities equivalent to the corrosion control steps applicable to such the waterworks under this section. If the commissioner department makes this determination, then the owner shall be provided with a written notice explaining the basis for the decision and the notice shall specify the water quality control parameters representing optimal corrosion control in accordance with subdivision A 1 f of this section. Waterworks owners The owner deemed to have optimized corrosion control under this subdivision shall operate in compliance with the commissioner designated department designated optimal water quality control parameters in accordance with subdivision A 1 g and continue to conduct lead and copper tap and water quality parameter sampling in accordance with 12VAC5-590-375 B 4 c and 12VAC5-590-375 C 4, respectively. The owner shall provide the commissioner department with the following information in order to support a determination under this subdivision:
(a) The results of all test samples collected for each of the water quality parameters in subdivision A 1 c (3) of this section;
(b) A report explaining the test methods used by the owner to evaluate the corrosion control treatments listed in subdivision A 1 c (1) of this section, the results of all tests conducted, and the basis for the owner's selection of optimal corrosion control treatment;
(c) A report explaining how corrosion control has been installed and how it is being maintained to insure minimal lead and copper concentrations at consumers' taps; and
(d) The results of tap water samples collected in accordance with 12VAC5-590-375 B at least once every six months for one year after corrosion control treatment has been installed.
(3) Any A waterworks is deemed to have optimized corrosion control if the owner submits results of tap water monitoring conducted in accordance with 12VAC5-590-375 B and source water monitoring conducted in accordance with 12VAC5-590-375 D that demonstrates for two consecutive six-month monitoring periods that the difference between the 90th percentile tap water lead level, computed under 12VAC5-590-385 C, and the highest source water lead concentration is less than the PQL for lead (0.005 mg/L).
(a) Any The owner that submits monitoring results indicating that the highest source water lead level is below the method detection limit MDL may also be deemed to have optimized corrosion control under this subdivision if the 90th percentile tap water lead level is less than or equal to the PQL for lead (0.005 mg/L) for two consecutive six-month monitoring periods.
(b) Any The owner deemed to have optimized corrosion control under this subdivision shall continue monitoring for lead and copper at the tap no less frequently than once every three calendar years using the reduced number of sites specified in 12VAC5-590-375 B 3 and collecting the samples at times and locations specified in 12VAC5-590-375 B 4 d (4).
(c) Any The owner deemed to have optimized corrosion control pursuant to this subdivision shall notify the district engineer department in writing pursuant to 12VAC5-590-530 F 1 c 12VAC5-590-532 B 3 of any upcoming long-term change in treatment or addition of a new water source water as described in that subdivision 12VAC5-590-532 B 3. The commissioner must review department shall evaluate and approve the addition of a new source water source or long-term change in water treatment before it is implemented by the owner. The commissioner department may require the owner of any such a waterworks to conduct additional monitoring or to take other actions the commissioner department deems appropriate to ensure that minimum levels of corrosion control are being maintained in the distribution system.
(d) An The owner is not deemed to have optimized corrosion control under this subdivision, and shall implement corrosion control treatment specified in subdivision A 2 b (3) (e) of this section, unless the copper action level AL is met.
(e) The owner of a waterworks triggered into corrosion control because the waterworks no longer is no longer deemed to have optimized corrosion control under this subsection shall implement corrosion control treatment in accordance with the deadlines in subdivision A 2 e of this section. The owner of any such a large waterworks shall adhere to the schedule specified in subdivision A 2 e of this section for medium-size systems a medium waterworks, with the time period for completing each step being triggered by the date the owner is no longer deemed to have optimized corrosion control treatment under this subsection.
c. The owner of any a small or a medium waterworks that is required to complete the corrosion control steps due to the exceedance of the lead or copper action level AL may cease completing the treatment steps whenever the waterworks meets both action levels ALs during each of two consecutive six-month monitoring periods conducted pursuant to 12VAC5-590-375 B 4 a and submits the results to the district engineer department. If any such a waterworks thereafter exceeds the lead or copper action level AL during any monitoring period, the owner shall recommence completion of the applicable treatment steps, beginning with the first treatment step which that was not previously completed in its entirety. The commissioner department may require the owner to repeat treatment steps previously completed where the commissioner department determines that this is necessary to properly implement the treatment requirements of this section. The commissioner department shall notify the owner in writing of such a the determination and explain the basis for his the decision. The requirement for the owner of any a small or a medium waterworks to implement corrosion control treatment steps in accordance with subdivision A 2 e of this section (including waterworks deemed to have optimized corrosion control under subdivision A 2 b (1) of this section) is triggered whenever any a small or a medium waterworks exceeds the lead or copper action level AL.
d. Treatment steps and deadlines for large waterworks. Except as provided in subdivisions A 2 b (2) and A 2 b (3) of this section, owners the owner of a large waterworks shall complete the following corrosion control treatment steps (described in the referenced portions of subdivision A 1 of this section, 12VAC5-590-375 B, and 12VAC5-590-375 C).
(1) Step 1: The owner shall conduct initial monitoring (12VAC5-590-375 B 4 a and 12VAC5-590-375 C 2) during two consecutive six-month monitoring periods by a date specified by the commissioner department.
(2) Step 2: The owner shall complete corrosion control studies (subdivision A 1 c of this section) and submit the study and recommendations to the commissioner department no later than 18 months after the date that initial monitoring is completed as specified in Step 1.
(3) Step 3: The commissioner department shall approve optimal corrosion control treatment (subdivision A 1 d) d of this section) no later than 12 months following receipt of the corrosion control study required in Step 2.
(4) Step 4: The owner shall install optimal corrosion control treatment (subdivision A 1 e) e of this section) no later than 24 months following the commissioner's department's approval of optimal corrosion control treatment specified in Step 3 (See 12VAC5-590-200).
(5) Step 5: The owner shall complete follow-up sampling (12VAC5-590-375 B 4 b and 12VAC5-590-375 C 3) no later than 12 months following the installation of optimal corrosion control treatment specified in Step 4.
(6) Step 6: The commissioner department shall review evaluate the installation of treatment and designate optimal water quality control parameters (subdivision A 1 f) f of this section) no later than six months following completion of follow-up sampling specified in Step 5.
(7) Step 7: The owner shall operate the waterworks in compliance with the commissioner-specified department-specified optimal water quality control parameters (subdivision A 1 g) g of this section) and continue to conduct tap sampling (12VAC5-590-375 B 4 c and 12VAC5-590-375 C 4).
e. Treatment steps and deadlines for small and medium waterworks. Except as provided in subdivision A 2 b of this section, owners the owner of a small and or a medium waterworks shall complete the following corrosion control treatment steps (described in the referenced portions of subdivision A 1 of this section, 12VAC5-590-375 B, and 12VAC5-590-375 C).:
(1) Step 1: The owner shall conduct initial tap sampling (12VAC5-590-375 B 4 a and 12VAC5-590-375 C 2) until the waterworks either exceeds the lead or copper action level AL or becomes eligible for reduced monitoring under 12VAC5-590-375 B 4 d. The owner of a waterworks exceeding the lead or copper action level AL shall propose optimal corrosion control treatment (subdivision A 1 a of this section) within six months after the end of the monitoring period during which it exceeds one of the action levels ALs.
(2) Step 2: Within 12 months after the end of the monitoring period during which a waterworks exceeds the lead or copper action level AL, the commissioner department may require the owner to perform corrosion control studies (subdivision A 1 b of this section). If the commissioner department does not require the owner to perform such these studies, the commissioner department shall specify optimal corrosion control treatment (subdivision A 1 d of this section) within the following timeframes:
(a) For a medium waterworks, within 18 months after the end of the monitoring period during which such the waterworks exceeds the lead or copper action level AL.
(b) For a small waterworks, within 24 months after the end of the monitoring period during which such the waterworks exceeds the lead or copper action level AL.
(3) Step 3: If the commissioner department requires an the owner to perform corrosion control studies under Step 2 subdivision A 2 e (2) of this section, then the owner shall complete the studies (subdivision A 1 c of this section) and submit the study and recommendations to the commissioner department within 18 months after the commissioner department requires that such the studies be conducted.
(4) Step 4: If the waterworks owner has performed corrosion control studies under Step 2 subdivision A 2 e (2) of this section, then the commissioner department shall designate optimal corrosion control treatment (subdivision A 1 d of this section) within six months after completion of Step 3 the provisions of subdivision A 2 e (3) of this section.
(5) Step 5: The owner shall install optimal corrosion control treatment (subdivision A 1 e of this section) within 24 months after the commissioner department designates such treatment. See A construction permit is required before installation of any treatment, in accordance with 12VAC5-590-200.
(6) Step 6: The owner shall complete follow-up sampling (12VAC5-590-375 B 4 b and 12VAC5-590-375 C 3) within 36 months after the commissioner department designates optimal corrosion control treatment.
(7) Step 7: The commissioner department shall review evaluate the owner's installation of treatment and designate optimal water quality control parameters (subdivision A 1 f of this section) within six months after completion of Step 6 the provisions of subdivision A 2 e (6) of this section.
(8) Step 8: The owner shall operate the waterworks in compliance with the commissioner designated department-designated optimal water quality control parameters (subdivision A 1 g of this section) and continue to conduct tap sampling (12VAC5-590-375 B 4 c and 12VAC5-590-375 C 4).
B. Water supply (source water) Source water treatment technique requirements for lead and copper. The owner of any a waterworks exceeding the lead or copper action level AL shall complete the applicable water supply source water monitoring and treatment requirements (described in the referenced portions of subdivision B 2 of this section, and in 12VAC5-590-375 B and [ 12VAC5-590-375 ] D) by the following deadlines.:
1. Deadlines for completing source water supply treatment steps.
a. Step 1: The owner of a waterworks exceeding the lead or copper action level AL shall complete lead and copper source water supply monitoring (12VAC5-590-375 D 2) and make submit a treatment proposal to the district engineer department (subdivision B 2 a of this section) no later than 180 days after the end of the monitoring period during which the lead or copper action level AL was exceeded.
b. Step 2: The commissioner department shall make a determination regarding the need for source water supply treatment (subdivision B 2 b of this section) within six months after submission of monitoring results under Step 1 subdivision B 1 a of this section.
c. Step 3: If the commissioner department requires installation of source water supply treatment, then the owner shall install the treatment (subdivision B 3 of this section) within 24 months after completion of Step 2 subdivision B 1 b of this section.
d. Step 4: The owner shall complete follow-up tap water monitoring (12VAC5-590-375 B 4 b) and source water supply lead and copper monitoring (12VAC5-590-375 D 3) within 36 months after completion of Step 2 subdivision B 1 b.
e. Step 5: The commissioner department shall review evaluate the owner's installation and operation of the source water supply treatment and specify maximum permissible source water supply lead and copper levels (subdivision B 4 of this section) within six months after completion of Step 4 subdivision B 1 d of this section.
f. Step 6: The owner shall operate the waterworks in compliance with the commissioner-specified department-specified maximum permissible source water lead and copper water supply levels (subdivision B 4 of this section) and continue source water supply monitoring (12VAC5-590-375 D 4).
2. Description of source water supply treatment requirements.
a. Waterworks treatment recommendation. The owner of any a waterworks which that exceeds the lead or copper action level AL shall propose in writing to the district engineer, department the installation and operation of one of the source water supply treatments listed in subdivision B 2 b of this section. An The owner may propose that no treatment be installed based upon a demonstration that source water supply treatment is not necessary to minimize lead and copper levels at users' consumer taps.
b. Commissioner's Department's determination regarding source water supply treatment. The commissioner department shall complete an evaluation of the results of all source water supply samples submitted by the owner to determine whether source water supply treatment is necessary to minimize lead or copper levels in water delivered to users' consumer taps. If the commissioner department determines that treatment is needed, then the commissioner department shall either require installation and operation of the source water supply treatment recommended by the owner or require the installation and operation of another source water supply treatment from among the following: (i) ion exchange, reverse osmosis (ii) RO, (iii) lime softening, or (iv) coagulation/filtration coagulation or filtration. If the commissioner department requests additional information to aid in the review evaluation, then the owner shall provide the information by the date specified by the commissioner department in the request. The commissioner department shall notify the owner in writing of the determination and set forth the basis for the decision.
3. Installation of source water supply treatment. Each The owner shall properly install and operate the source water supply treatment designated by the commissioner department under subdivision B 2 b of this section.
4. Commissioner's review The department's evaluation of source water supply treatment and specification of maximum permissible source water supply lead and copper levels. The commissioner department shall review evaluate the source water supply samples taken collected by the owner both before and after the owner installs source water supply treatment, and determine whether the owner has properly installed and operated the source water supply treatment designated by the commissioner department. Based upon the review evaluation, the commissioner department shall designate the maximum permissible lead and copper concentrations for finished water entering the distribution system. Such The levels shall reflect the contaminant removal capability of the treatment properly operated and maintained. The commissioner department shall notify the owner in writing and explain the basis for the decision.
5. Continued operation and maintenance. Each The waterworks shall be operated to maintain lead and copper levels below the maximum permissible concentrations designated by the commissioner department at each sampling point monitored in accordance with 12VAC5-590-375 D. The waterworks is out of compliance with this subdivision [ A B ] 5 if the level of lead or copper at any sampling point is greater than the maximum permissible concentration designated by the commissioner department.
6. Modification of the commissioner's department's treatment decisions. Upon his own the department's initiative or in response to a request by an owner or other interested party, the commissioner department may modify his the determination of the source water supply treatment under subdivision B 2 b of this section, or may modify the maximum permissible lead and copper concentrations for finished water entering the distribution system under subdivision B 4 of this section. A request for modification by an owner or other interested party shall be in writing, explain why the modification is appropriate, and provide supporting documentation. The commissioner department may modify the determination where he concludes the conclusion is made that such the change is necessary to ensure that the waterworks continues to minimize lead and copper concentrations in water supplies source waters. A revised determination shall be made in writing, set forth the new treatment requirements, explain the basis for the commissioner's department's decision, and provide an implementation schedule for completing the treatment modifications.
C. Lead service line replacement treatment technique requirements:
1. Owners The owner of a waterworks that fail fails to meet the lead action level AL in tap samples taken collected pursuant to 12VAC5-590-375 B 4 b, after installing corrosion control or source water supply treatment (whichever sampling occurs later), shall replace lead service lines in accordance with the requirements of this section. If a waterworks the owner is in violation of subdivision A 2 of this section or subsection B of this section for failure to install source water supply or corrosion control treatment, then the commissioner department may require the owner to commence lead service line replacement under this section after the date by which the owner was required to conduct monitoring under 12VAC5-590-375 B 4 b has passed.
2. An The owner shall replace annually at least 7.0% of the initial number of lead service lines in its distribution system. The initial number of lead service lines is the number of lead lines in place at the time the replacement program begins. The owner shall identify the initial number of lead service lines in its distribution system based upon a materials evaluation, including the evaluation required under 12VAC5-590-375 B 1. The first year of lead service line replacement shall begin on the first day following the end of the monitoring period in which the lead action level AL was exceeded under subdivision C 1 of this subsection section. If monitoring is required annually or less frequently, then the end of the monitoring period is September 30 of the calendar year in which the sampling occurs. If the commissioner department has established an alternate monitoring period, then the end of the monitoring period will be the last day of that period.
3. The owner of any a waterworks resuming a lead service line replacement program after the cessation of the lead service line replacement program as allowed by subdivision C 7 of this section shall update the inventory of lead service lines to include those sites that were previously determined not to require replacement through the sampling provision under subdivision C 4 of this section. The owner shall then divide the updated number of remaining lead service lines by the number of remaining years in the program to determine the number of lines that must be replaced per year (7.0% lead service line replacement is based on a 15-year replacement program; so, for example, owners the owner resuming lead service line replacement after previously conducting two years of replacement would divide the updated inventory by 13). For those owners that have the owner that has completed a 15-year lead service line replacement program, the commissioner department will determine a schedule for replacing or retesting lines that were previously tested out under the replacement program when the waterworks re-exceeds the lead action level AL.
4. An The owner is not required to replace an individual lead service line if the lead concentration in all service line samples from that line, taken collected pursuant to 12VAC5-590-375 B 2 c, is less than or equal to 0.015 mg/L.
5. An The owner shall replace that portion of the lead service line that is owned by the waterworks. In cases where the waterworks owner does not own the entire lead service line, the waterworks owner shall notify the building owner, or the building owner's authorized agent, that the waterworks owner will replace that portion of the service line that is owned by the waterworks and shall offer to replace the building owner's portion of the line. The waterworks owner is not required to bear the cost of replacing the building owner's portion of the service line, nor is the waterworks owner required to replace the building owner's portion where the waterworks owner chooses not to pay the cost of replacing the building owner's portion of the line, or where replacing the building owner's portion would be precluded by state, local, or common law. A waterworks The owner that does not replace the entire length of the service line also shall complete the following tasks.:
a. At least 45 days prior to before commencing with the partial replacement of a lead service line, the waterworks owner shall provide notice to the resident or residents of all buildings served by the line explaining that they may experience a temporary increase of lead levels in their the drinking water, along with guidance on measures consumers can take to minimize their exposure to lead. The commissioner department may allow the waterworks owner to provide notice under the previous sentence less than 45 days prior to before commencing partial lead service line replacement where such the replacement is in conjunction with emergency repairs. In addition, the waterworks owner shall inform the each resident or residents served by the lead service line that the waterworks owner will, at the waterworks owner's expense, collect a sample from each partially-replaced partially replaced lead service line that is representative of the water in the service line for analysis of lead content, as prescribed in 12VAC5-590-375 B 2 c, within 72 hours after the completion of the partial replacement of the lead service line. The waterworks owner shall collect the sample and report the results of the analysis to the building owner and each resident or residents served by the service line within three business days of receiving the results. Mailed notices post-marked within three business days of receiving the results shall be considered on time.
b. The waterworks owner shall provide the information required by subdivision C 5 a of this section to the residents of individual dwellings by mail or by other methods approved by the commissioner department. In instances where multi-family dwellings are served by the service line, the waterworks owner shall have the option to post the information at a conspicuous location.
6. The commissioner department shall require an the owner to replace lead service lines on a shorter schedule than that required by this subsection, taking into account the number of lead service lines in the waterworks, where such a shorter replacement schedule is feasible. The commissioner department shall make this determination in writing and notify the owner of the findings within six months after the waterworks is triggered into lead service line replacement based on monitoring referenced in subdivision C 1 of this section.
7. Any The owner may cease replacing lead service lines whenever first draw first-draw tap samples collected pursuant to 12VAC5-590-375 B 2 b meet the lead action level AL during each of two consecutive six-month monitoring periods and the owner submits the results to the district engineer department. If the first draw first-draw tap samples collected in any such a waterworks thereafter exceeds exceed the lead action level AL, then the owner shall recommence replacing lead service lines, pursuant to subdivision C 3 of this section.
8. To demonstrate compliance with subdivisions C 1 through C 5 of this section, an owner shall report to the district engineer department the information specified in 12VAC5-590-530 F 5 12VAC5-590-532.
D. Lead public education requirements. The waterworks owner shall deliver a consumer notice of lead tap water monitoring results to all persons served by the water system waterworks at sites that are tested in accordance with subdivision D 4 of this section. The owner of a waterworks that exceeds the lead action level AL based on tap water samples collected in accordance with 12VAC5-590-375 B shall deliver the public education materials contained in subdivisions subdivision D 1 of this section in accordance with the requirements in subdivision D 2 of this section. The owner of a waterworks that exceeds the lead action level AL shall sample the tap water of any customer who requests it in accordance with subdivision D 3 of this section.
1. Content of written materials. The owner shall include the following text in all of the printed materials distributed through the lead public education program.:
a. Community waterworks and nontransient noncommunity waterworks NTNCs. Owners The owner of community waterworks or nontransient noncommunity waterworks a NTNC shall include the following elements in printed materials (e.g., brochures and pamphlets) in the same order as listed below in this subdivision [ D 1 ] a. In addition, the language specified in subdivisions D 1 a (1) through and D 1 a (2) and in subdivision D 1 a (6) of this section shall be included in materials, exactly as written, except for the text in brackets for which the waterworks owner shall include system-specific information. Any additional information presented by the owner shall be consistent with the information below in this subdivision [ D 1 ] a and be in plain language that can be understood by the general public. The commissioner department may require the waterworks owner to obtain approval of the content of written material prior to before delivery.
(1) IMPORTANT INFORMATION ABOUT LEAD IN YOUR DRINKING WATER. [INSERT NAME OF WATERWORKS] "(Insert name of waterworks) found elevated levels of lead in drinking water in some homes/buildings homes or buildings. Lead can cause serious health problems, especially for pregnant women and young children. Please read this information closely to see what you can do to reduce lead in your drinking water."
(2) Health effects of lead. "Lead can cause serious health problems if too much enters your body from drinking water or other sources. It can cause damage to the brain and kidneys, and can interfere with the production of red blood cells that carry oxygen to all parts of your body. The greatest risk of lead exposure is to infants, young children, and pregnant women. Scientists have linked the effects of lead on the brain with lowered IQ in children. Adults with kidney problems and high blood pressure can be affected by low levels of lead more than healthy adults. Lead is stored in the bones, and it can be released later in life. During pregnancy, the child receives lead from the mother's bones, which may affect brain development."
(3) Sources of lead.
(a) Explain what lead is.
(b) Explain possible sources of lead in drinking water and how lead enters drinking water. Include information on home/building home or building materials and services lines that may contain lead.
(c) Discuss other important sources of lead exposure in addition to drinking water (e.g., paint).
(4) Discuss the steps the consumer can take to reduce their exposure to lead in drinking water.
(a) Encourage running the water to flush out the lead.
(b) Explain concerns with using hot water from the tap and specifically caution against the use of hot water for preparing baby formula.
(c) Explain that boiling water does not reduce lead levels.
(d) Discuss other options consumers can take to reduce exposure to lead in drinking water, such as alternative sources or treatment of water.
(e) Suggest that parents have their child's blood tested for lead.
(5) Explain why there are elevated levels of lead in the waterworks' drinking water (if known) and what the waterworks owner is doing to reduce the lead levels in homes/buildings homes and buildings.
(6) "For more information call us at [INSERT WATERWORKS OWNER'S CONTACT PHONE NUMBER], or [IF APPLICABLE] (Insert owner's contact phone number), or if applicable, visit our website at [INSERT WATERWORKS' WEBSITE HERE] (Insert waterworks' website URL here). For more information on reducing lead exposure around your home/building home or building and the health effects of lead, visit EPA's website at http://www.epa.gov/lead or contact your health care provider."
b. In addition to including the elements specified in subdivision D 1 a of this section, the owners owner of a community waterworks shall:
(1) Tell consumers how to get their water tested.
(2) Discuss lead in plumbing components and the difference between low lead and lead free. "Lead free" means (i) when used with respect to solders and flux refers to solders and flux containing not more than 0.2% lead, and (ii) when used with respect to pipes, pipe fittings, plumbing fittings, and plumbing fixtures refers to the weighted average of wetted surfaces of pipes, pipe fittings, plumbing fittings, and plumbing fixtures containing not more than 0.25% lead.
2. Delivery of public education materials.
a. The owner of any a waterworks serving a large proportion of non-English speaking consumers, as determined by the commissioner department, shall include in all public education materials information in the appropriate language(s) languages regarding the importance of the notice or contain a telephone number or address where persons served may contact the water system waterworks to obtain a translated copy of the public education materials or to request assistance in the appropriate language.
b. The owner of a community waterworks that exceeds the lead action level AL on the basis of tap water samples collected in accordance with 12VAC5-590-375 B, and that is not already conducting public education tasks, shall conduct the public education tasks under this subdivision within 60 days after the end of the monitoring period in which the exceedance occurred. For a waterworks that are is required to conduct monitoring annually or less frequently, the end of the monitoring period is September 30 of the calendar year in which the sampling occurs, or, if the commissioner department has established an alternate monitoring period, the last day of that period. These public education tasks include:
(1) Deliver Delivering printed materials meeting the content requirements of subdivision D 1 of this section to all bill paying customers.
(2) Contact Contacting customers who are most at risk by delivering education materials that meet the content requirements of subdivision D 1 of this section to the local health department even if they are not located within the water system's waterworks service area, along with an informational notice that encourages distribution to all the organization's potentially affected customers or community water system's users waterworks consumers. The waterworks owner shall contact the local health department directly by phone or in person. The local health department may provide a specific list of additional community based organizations serving target populations, which may include organizations outside the service area of the water system waterworks. If such these lists are provided, then the waterworks owner shall deliver education materials that meet the content requirements of subdivision D 1 of this section to all organizations on the provided lists.
(3) Contact Contacting customers who are most at risk by delivering materials that meet the content requirements of subdivision D 1 of this section to the following organizations that are located within the water system's waterworks service area, along with an informational notice that encourages distribution to all the organization's potentially affected customers or community water system's waterworks users: (i) public and private schools or school boards; (ii) Women, Infants and Children (WIC) and Head Start programs; (iii) public and private hospitals and medical clinics; (iv) pediatricians; (v) family planning clinics; and (vi) local welfare agencies.
(4) Make a good faith effort to locate the following organizations within the service area and deliver materials that meet the content requirements of subdivision D 1 of this section to them, along with an informational notice that encourages distribution to all potentially affected customers or users consumers. The good faith effort to contact at-risk customers may include requesting a specific contact list of these organizations from the local health department, even if the agencies are not located within the water system's waterworks service area: (i) licensed childcare centers;, (ii) public and private preschools;, and (iii) obstetricians-gynecologists and midwives.
(5) No less often than quarterly, provide providing information on or in each water bill as long as the waterworks exceeds the action level AL for lead. The message on the water bill shall include the following statement exactly as written except for the text in brackets for which the owner shall include system-specific information: [INSERT NAME OF WATERWORKS] "(Insert name of waterworks) found high levels of lead in drinking water in some homes. Lead can cause serious health problems. For more information please call [INSERT NAME OF WATERWORKS] or visit [IF APPLICABLE INSERT WATERWORKS' WEBSITE] (insert name of waterworks) or (if applicable) visit our website at (insert waterworks website URL here)". The message or delivery mechanism can be modified in consultation with the commissioner department; specifically, the commissioner department may allow a separate mailing of public education materials to customers if the waterworks owner cannot place the information on water bills.
(6) Post Posting materials meeting the content requirements of subdivision D 1 of this section on the waterworks' waterworks website if the waterworks serves a population greater than 100,000 persons.
(7) Submit Submitting a press release to newspapers, television, and radio stations.
(8) In addition to the delivery requirements contained in subdivisions D 2 b (1) through D 2 b (7) of this section, the owners of owner of a waterworks exceeding the lead action level AL shall implement at least three activities from one or more of the following categories: (i) public service announcements;, (ii) paid advertisements;, (iii) public area informational displays;, (iv) e-mails emails to customers;, (v) public meetings;, (vi) household deliveries;, (vii) targeted individual customer contact;, (viii) direct material distribution to all multi-family homes and institutions;, and (ix) other methods approved by the commissioner department. The educational content and selection of these activities shall be determined in consultation with the district engineer department.
(9) As long as a community water system waterworks exceeds the lead action level AL, the waterworks owner shall repeat the following public education activities:
(a) The owner of a community water system owner waterworks shall repeat the tasks contained in subdivisions D 2 b (1) through, D 2 b (2), D 2 b (3), and D 2 b (8) of this section every 12 months.
(b) The owner of a community water system owner waterworks shall repeat tasks contained in subdivision D 2 b (5) of this section with each billing cycle.
(c) The owner of a community water system waterworks serving a population greater than 100,000 shall post and retain the material on a publicly accessible website pursuant to subdivision D 2 b (6) of this section.
(d) The owner of a community water system owner waterworks shall repeat the task in subdivision D 2 b (7) of this section twice every 12 months on a schedule agreed upon with the commissioner department.
(10) The commissioner department may allow the public education activities described in subdivision D 2 b of this section to extend beyond the 60-day requirement if needed for implementation purposes on a case-by-case basis; however, this extension must be approved in writing by the commissioner department in advance of the 60-day deadline.
c. The owner of a nontransient noncommunity waterworks NTNC that exceeds the lead action level AL on the basis of tap water samples collected in accordance with 12VAC5-590-375 B, and that is not already conducting public education tasks, shall conduct the public education tasks under this subdivision within 60 days after the end of the monitoring period in which the exceedance occurred. For a waterworks that are is required to conduct monitoring annually or less frequently, the end of the monitoring period is September 30 of the calendar year in which the sampling occurs, or, if the commissioner department has established an alternate monitoring period, the last day of that period. These public education tasks include:
(1) Post Posting informational posters containing all of the public education elements contained in subdivision D 1 of this section in a public place or common area in each of the buildings served by the waterworks; and
(2) Distribute Distributing informational pamphlets or brochures on lead in drinking water containing all of the public education elements in subdivision D 1 of this section to each person served by the nontransient noncommunity waterworks NTNC. The commissioner department may allow the owner to utilize electronic transmission in lieu instead of or combined with printed materials as long as it achieves at least the same coverage.
(3) The owner of a nontransient noncommunity waterworks NTNC shall repeat the tasks contained in subdivisions D 2 c (1) through and D 2 c (2) of this section at least once during each calendar year in which the waterworks exceeds the lead action level AL.
(4) The commissioner department may allow the public education activities described in subdivision D 2 c of this section to extend beyond the 60-day requirement if needed for implementation purposes on a case-by-case basis; however, this extension must be approved in writing by the commissioner department in advance of the 60-day deadline.
d. An The owner may discontinue delivery of public education materials if the waterworks has met the lead action level AL during the most recent six-month monitoring period conducted pursuant to 12VAC5-590-375 B. The owner shall recommence public education in accordance with this subsection if the waterworks subsequently exceeds the lead action level AL during any monitoring period.
e. The owner of a community waterworks may apply to the district engineer, department, in writing, (unless the commissioner department has waived the requirement for prior approval) to use only the text specified in subdivision D 1 a of this section in lieu instead of the text in subdivisions D 1 a through and D 1 b of this section and to perform the tasks listed in subdivisions D 2 c (1) through and D 2 c (2) of this section in lieu instead of the tasks in subdivisions D 2 b (1) through D 2 b (9) of this section if:
(1) The waterworks serves a facility, such as a prison or a hospital, where the population served is not capable of or is prevented from making improvements to plumbing or installing POU treatment devices; and
(2) The owner provides water as part of the cost of services provided and does not separately charge for water consumption.
f. The owner of a community waterworks serving 3,300 or fewer people may limit certain aspects their of the public education programs as follows:
(1) With respect to the requirements of subdivision D 2 b (8) of this section, the owner of a waterworks serving 3,300 or fewer people shall implement at least one of the activities listed in that subdivision.
(2) With respect to the requirements of subdivision D 2 b (2) of this section, the owner of a waterworks serving 3,300 or fewer people may limit the distribution of the public education materials required under that subdivision to facilities and organizations served by the waterworks that are most likely to be visited regularly by pregnant women and children.
(3) With respect to the requirements of subdivision D 2 b (7) of this section, the commissioner department may waive this requirement for systems waterworks serving 3,300 or fewer persons as long as the owner distributes notices to every household served by the waterworks.
3. Supplemental monitoring and notification of results. The owner of a waterworks that fails to meet the lead action level AL on the basis of tap samples collected in accordance with 12VAC5-590-375 B shall offer to sample the tap water of any customer who requests it. The owner is not required to pay for collecting or analyzing the sample, nor is the owner required to collect and analyze the sample itself.
4. Notification of results. The owners of all owner of a community and nontransient noncommunity waterworks or a NTNC shall provide a notice of the individual tap results from lead tap water monitoring carried out under the requirements of 12VAC5-590-375 B to the persons served by the waterworks at the specific sampling site from which the sample was taken collected (e.g., the occupants of the residence or buildings where the tap was tested).
a. Timing of notification. An The owner shall provide this consumer notice as soon as practical, but no later than 30 days after the owner learns of the tap monitoring results.
b. Content. The consumer notice shall include the results of lead tap water monitoring for the tap that was tested, an explanation of the health effects of lead, list steps consumers can take to reduce exposure to lead in drinking water, and contact information for the waterworks. The notice shall also provide the maximum contaminant level goal MCLG and the action level AL for lead and the definitions for these two terms from 12VAC5-590-10.
c. Delivery. The consumer notice shall be provided to persons served at the tap that was tested, either by postal mail or by another method approved by the commissioner department. For example, the owner of a nontransient noncommunity waterworks NTNC may post the results on a bulletin board in the facility to allow users consumers to review the information. The owner shall provide the notice to customers at sample taps tested, including consumers who do not receive water bills.
EDITOR'S NOTE: The proposed repeal of 12VAC5-590-410 was adopted as final. View the entire repealed section at 36:6 VA.R. 475-845 November 11, 2019.
12VAC5-590-411. Disinfection byproduct precursors, disinfection byproducts, and maximum residual disinfection level treatment techniques.
A. Treatment technique for control of DBPPs.
1. Applicability.
a. The owner of a community waterworks or a NTNC shall comply with treatment techniques for the control of DBPPs.
b. A waterworks that uses a surface water source, a GUDI source, or both using conventional filtration treatment shall operate with enhanced coagulation or enhanced softening to achieve the TOC percentage removal levels specified in subdivision A 2 of this section unless the waterworks meets at least one of the alternative compliance criteria listed in subdivision A 1 c or A 1 d of this section.
c. Alternative compliance criteria for enhanced coagulation and enhanced softening waterworks. A waterworks that uses a surface water source, a GUDI source, or both provided with conventional filtration treatment may use the alternative compliance criteria in subdivisions A 1 c (1) through A 1 c (6) of this section to comply with this section instead of complying with subdivision A 2 of this section. The owner shall comply with monitoring requirements in 12VAC5-590-374 I.
(1) The waterworks' source water TOC level is less than 2.0 mg/L, calculated quarterly as an RAA.
(2) The waterworks' treated water TOC level is less than 2.0 mg/L, calculated quarterly as an RAA.
(3) The waterworks' source water TOC level is less than 4.0 mg/L, calculated quarterly as an RAA; the source water alkalinity is greater than 60 mg/L (as CaCO3), calculated quarterly as an RAA; and no TTHM and HAA5 LRAAs are greater than 0.040 mg/L and 0.030 mg/L, respectively.
(4) No TTHM and HAA5 LRAAs are greater than 0.040 mg/L and 0.030 mg/L, respectively, and the waterworks uses only chlorine for primary disinfection and maintains a residual in the distribution system.
(5) The waterworks' source water SUVA, before any treatment and measured monthly, is less than or equal to 2.0 liters per milligram-meter (L/mg-m), calculated quarterly as an RAA.
(6) The waterworks' finished water SUVA, measured monthly, is less than or equal to 2.0 L/mg-m, calculated quarterly as an RAA.
d. Additional alternative compliance criteria for softening waterworks. A waterworks practicing enhanced softening that cannot achieve the TOC removals required by subdivision A 2 b of this section may use the alternative compliance criteria in subdivisions A 1 c (1) and A 1 c (2) instead of complying with subdivision A 2 of this section. A waterworks shall comply with monitoring requirements in 12VAC5-590-374 [ I J ].
(1) Softening that results in lowering the treated water alkalinity to less than 60 mg/L (as CaCO3), measured monthly and calculated quarterly as an RAA.
(2) Softening that results in removing at least 10 mg/L of magnesium hardness (as CaCO3), measured monthly and calculated quarterly as an RAA.
2. Enhanced coagulation and enhanced softening performance requirements.
a. A waterworks shall achieve the percentage reduction of TOC specified in subdivision A 2 b of this section between the source water and the CFE, unless the department approves an owner's request for alternate minimum TOC removal (Step 2) requirements under subdivision A 2 c of this section.
Required Step 1 TOC reductions, indicated in Table 411.1, are based upon specified source water parameters. A waterworks practicing softening is required to meet the Step 1 TOC reductions in the far-right column (source water alkalinity greater than 120 mg/L) for the specified source water TOC.
b. [ Step 1 Required removal of TOC by "Enhanced Coagulation and Enhanced Precipitative Softening Guidance Manual," May 1999, EPA Office of Water. Required Step 1 TOC reductions are indicated in Table 411.1, Required Percentage Removals of TOC. ]
TABLE 411.1 Required Percentage Removals of TOCa,b
|
SOURCE WATER TOC, mg/L
|
SOURCE WATER ALKALINITY, mg/L as CaCO3
|
0 - 60
|
>60 - 120
|
>120c
|
>2.0 - 4.0
|
35.0%
|
25.0%
|
15.0%
|
>4.0 - 8.0
|
45.0%
|
35.0%
|
25.0%
|
>8.0
|
50.0%
|
40.0%
|
30.0%
|
aA waterworks meeting at least one of the conditions in subdivisions A 1 c (1) through A 1 c (6) of this section is not required to operate with enhanced coagulation.
bA waterworks utilizing softening and meeting one of the alternative compliance criteria in subdivision A 1 d of this section is not required to operate with enhanced softening.
cA waterworks practicing softening shall meet the TOC removal requirements in this column.
|
c. A waterworks that uses a surface water source, a GUDI source, or both with conventional treatment that cannot achieve the Step 1 TOC removals required by subdivision A 2 b due to water quality parameters or operational constraints shall apply to the department within three months of failure to achieve the TOC removals required by subdivision A 2 b of this section for approval of alternative minimum TOC (Step 2) removal requirements submitted by the owner. If the department approves the alternative minimum TOC removal (Step 2) requirements, then the department may make those requirements retroactive for the purposes of determining compliance. Until the department approves the alternate minimum TOC removal (Step 2) requirements, the waterworks shall meet the Step 1 TOC removals contained in subdivision A 2 b of this section.
d. Alternate minimum TOC removal (Step 2) requirements. Applications made to the department by the owner of a waterworks using enhanced coagulation for approval of alternative minimum TOC removal (Step 2) requirements under subdivision A 2 c of this section shall include, at a minimum, results of bench-scale or pilot-scale testing conducted under subdivision A 2 d (1) of this section. The submitted bench-scale or pilot-scale testing shall be used to determine the alternate enhanced coagulation level.
(1) Alternate enhanced coagulation level is defined as coagulation at a coagulant dose and pH as determined by the method described in subdivisions A 2 d (1) through A 2 d (5) of this section so that an incremental addition of 10 mg/L of alum (or equivalent amount of ferric salt) results in a TOC removal of equal to or less than 0.3 mg/L. The percentage removal of TOC at this point on the "TOC removal versus coagulant dose" curve is then defined as the minimum TOC removal required for the waterworks. Once approved by the department, this minimum requirement supersedes the minimum TOC removal requirements listed in Table 411.1. This requirement shall be effective until the department approves a new value based on the results of a new bench-scale and pilot-scale test. Failure to achieve the alternative minimum TOC removal levels set by the department is a violation of this section.
(2) Bench-scale or pilot-scale testing of enhanced coagulation shall be conducted by using representative water samples and adding 10 mg/L increments of alum (or equivalent amounts of ferric salt) until the pH is reduced to a level less than or equal to the enhanced coagulation Step 2 target pH shown in Table 411.2.
|
TABLE 411.2 Enhanced Coagulation
|
|
ALKALINITY (mg/L as CaCO3)
|
TARGET pH
|
|
0 - 60
|
5.5
|
|
>60 -120
|
6.3
|
|
>120 - 240
|
7.0
|
|
>240
|
7.5
|
(3) For source waters with alkalinities of less than 60 mg/L for which addition of small amounts of alum or equivalent addition of iron coagulant drives the pH below 5.5 before significant TOC removal occurs, the waterworks shall add necessary chemicals to maintain the pH between 5.3 and 5.7 in samples until the TOC removal of 0.3 mg/L per 10 mg/L alum added (or equivalent addition of iron coagulant) is reached.
(4) The waterworks may operate at any coagulant dose or pH necessary (consistent with other sections of this chapter) to achieve the minimum TOC percentage removal approved under subdivision A 2 c of this section.
(5) If the TOC removal is consistently less than 0.3 mg/L of TOC per 10 mg/L of incremental alum dose at all dosages of alum (or equivalent addition of iron coagulant), then the water is deemed to contain TOC not amenable to enhanced coagulation. The owner may then apply to the department for a waiver of enhanced coagulation requirements.
3. Compliance calculations.
a. A waterworks that uses a surface water source, a GUDI source, or both other than those identified in subdivision A 1 b or A 1 c of this section shall comply with requirements contained in subdivision A 2 b or A 2 c of this section. The owner shall calculate compliance quarterly, beginning after the waterworks has collected 12 months of data, by determining an annual average using the following method:
(1) Determine actual monthly TOC percentage removal, equal to:
[1-(treated water TOC/source water TOC)] X 100.
(2) Determine the required monthly TOC percentage removal (from either Table 411.1 or from subdivision A 2 c of this section).
(3) Divide the value in subdivision A 3 a (1) of this section by the value in subdivision A 3 a (2) of this section.
(4) Add together the results of subdivision A 3 a (3) of this section for the last 12 months and divide by 12.
(5) If the value calculated in subdivision A 3 a (4) of this section is less than 1.00, then the waterworks is not in compliance with the TOC percentage removal requirements.
b. The owner may use the provisions in subdivisions A 3 b (1) through A 3 b (5) of this section instead of the calculations in subdivisions A 3 a (1) through A 3 a (5) of this section to determine compliance with TOC percentage removal requirements.
(1) In any month that the waterworks' treated or source water TOC level is less than 2.0 mg/L, the waterworks may assign a monthly value of 1.0 (instead of the value calculated in subdivision A 3 a (3) of this section) when calculating compliance under the provisions of subdivision A 3 a of this section.
(2) In any month that a waterworks practicing softening removes at least 10 mg/L of magnesium hardness (as CaCO3), the waterworks may assign a monthly value of 1.0 (instead of the value calculated in subdivision A 3 a (3) of this section) when calculating compliance under the provisions of subdivision A 3 a of this section.
(3) In any month that the waterworks source water SUVA before any treatment is equal to or less than 2.0 L/mg-m, the waterworks may assign a monthly value of 1.0 (instead of the value calculated in subdivision A 3 a (3) of this section) when calculating compliance under the provisions of subdivision A 3 a of this section.
(4) In any month that the waterworks finished water SUVA is equal to or less than 2.0 L/mg-m, the waterworks may assign a monthly value of 1.0 (instead of the value calculated in subdivision A 3 a (3) of this section) when calculating compliance under the provisions of subdivision A 3 a of this section.
(5) In any month that the waterworks practicing enhanced softening lowers the alkalinity below 60 mg/L (as CaCO3), the waterworks may assign a monthly value of 1.0 (instead of the value calculated in subdivision A 3 a (3) of this section) when calculating compliance under the provisions of subdivision A 3 a of this section.
c. A waterworks that uses a surface water source, a GUDI source, or both and uses conventional treatment may also comply with the requirements of this section by meeting the criteria in subdivision A 1 b or A 1 c of this section.
4. Enhanced coagulation or enhanced softening is the treatment technique required to control the level of DBP precursors in water treatment and distribution system for a waterworks using a surface water source, a GUDI source, or both and using conventional treatment.
B. The BAT, treatment techniques, or other means available for achieving compliance with the PMCLs for DBPs shown in Table 340.6 are listed in this subsection:
1. The BAT, treatment techniques, or other means available for achieving compliance with the PMCLs for bromate and chlorite:
|
DISINFECTION BYPRODUCT
|
BEST AVAILABLE TECHNOLOGY
|
|
Bromate
|
Control of ozone treatment process to reduce production of bromate
|
|
Chlorite
|
Control of treatment processes to reduce disinfectant demand and control of disinfection treatment processes to reduce disinfectant levels
|
2. The BAT, treatment techniques, or other means available for achieving compliance with the RAA PMCLs for TTHM and HAA5:
|
DISINFECTION BYPRODUCT
|
BEST AVAILABLE TECHNOLOGY
|
|
TTHM and HAA5
|
Enhanced coagulation or enhanced softening or GAC10, with chlorine as the primary and residual disinfectant
|
3. The BAT, treatment techniques, or other means available for achieving compliance with the LRAA PMCLs for TTHM and HAA5 for a waterworks that disinfects its source water:
|
DISINFECTION BYPRODUCT
|
BEST AVAILABLE TECHNOLOGY
|
|
TTHM and HAA5
|
Enhanced coagulation or enhanced softening, plus GAC10; or NF with a molecular weight cutoff fewer than or equal to 1,000 Daltons; or GAC20
|
4. The BAT, treatment techniques, or other means available for achieving compliance with the LRAA MCLs for TTHM and HAA5 for a a consecutive waterworks and applies only to the disinfected water that a consecutive waterworks buys or otherwise receives:
|
DISINFECTION BYPRODUCT
|
BEST AVAILABLE TECHNOLOGY
|
|
TTHM and HAA5
|
A waterworks serving equal to or greater than 10,000 people: Improved distribution system and storage tank management to reduce residence time, plus the use of chloramines for residual disinfectant maintenance
A waterworks serving fewer than 10,000 people: Improved distribution system and storage tank management to reduce residence time
|
C. The BAT, treatment techniques, or other means available for achieving compliance with the MRDLs identified in Table 340.7 are the controls of treatment processes to reduce disinfectant demand and controls of disinfection treatment processes to reduce disinfectant levels.
12VAC5-590-415. Uncovered finished water storage.
A. A waterworks with uncovered finished water storage facilities shall comply with the requirements to cover the facility as described in this section.
B. The owner shall immediately notify the department of the use of each uncovered finished water storage facility.
C. All uncovered finished water storage facilities shall be covered in compliance with a schedule approved by the department.
D. Failure to comply with the requirements of this section is a violation of the treatment technique requirement.
Editor's Note: The proposed repeal of 12VAC5-590-420 was adopted as final. View the entire repealed section at 36:6 VA.R. 475-845 November 11, 2019.
12VAC5-590-421. Groundwater system treatment techniques.
A. Owners The owner of a groundwater systems system that (i) have has a confirmed E. coli contamination as described in 12VAC5-590-379 B or (ii) have has been notified in writing of a significant deficiency as described in 12VAC5-590-350 D shall meet the requirements of this section. Failure to meet any requirement of this section after the applicable time period specified is a treatment technique violation.
1. Owners of groundwater systems meeting either one of the conditions in clause (i) or (ii) above The owner shall implement one or more of the following corrective actions:
a. Correct all significant deficiencies;
b. Provide an alternate source of water;
c. Eliminate the source of contamination; or
d. Provide treatment of the groundwater source that reliably achieves at least 4-log treatment of viruses before or at the first consumer customer.
2. Unless the ODW department directs the groundwater system owner to implement a specific corrective action, the groundwater system owner shall consult with the ODW department regarding the appropriate corrective action within 30 days of receiving written notification from the commissioner department or the laboratory. This consultation may take the form of a telephone conversation, electronic mail email, meeting, or other mechanism agreed to by the ODW department.
3. Within 45 days of receiving this notification, the groundwater system owner shall submit a written Corrective Action Plan corrective action plan (CAP) to the commissioner department that satisfactorily addresses the deficiency. The CAP shall include a schedule for completing individual actions, and it shall include one or more of the corrective actions in subdivision A 1 of this section. Approval of the CAP by the commissioner department constitutes an approved CAP.
4. Within 120 days of receiving written notification from the commissioner department or the laboratory, the groundwater system owner shall either:
a. Have a completed corrective action actions in accordance with the commissioner-approved department approved CAP including commissioner-specified department specified interim measures; or
b. Be in compliance with a commissioner-approved department approved CAP and schedule subject to the conditions specified in subdivisions 4 b 1 and 2 of this subsection.
(1) Any subsequent modifications to a commissioner-approved department approved CAP and schedule shall also be approved by the commissioner department.
(2) If the commissioner department specifies interim measures for protection of the public health pending the commissioner's department's approval of the CAP and schedule or pending completion of the CAP, then the groundwater system owner shall comply with these interim measures as well as with any schedule specified by the commissioner department.
5. When a significant deficiency is identified at a waterworks that uses both a groundwater and a surface water or a GUDI source, the owner shall comply with this section unless the commissioner department has determined that the significant deficiency is in a portion of the distribution system that is served solely by the surface water or a the GUDI source.
B. Owners The owner of a groundwater systems system that provide provides at least 4-log treatment of viruses before or at the first customer shall conduct compliance monitoring to demonstrate treatment effectiveness in accordance with subsection C of this section. The owner shall also conduct source water monitoring in accordance with 12VAC5-590-379 C.
1. Existing groundwater sources. A groundwater system that is not required to meet the source water monitoring requirements of 12VAC5-590-379 for any groundwater source(s) because the owner has been notified by the ODW that the groundwater system provides at least 4-log treatment of viruses before or at the first customer for any groundwater source(s) shall comply with the following:
a. The groundwater system owner shall have written approval from the ODW that the groundwater system provides at least 4-log treatment of viruses before or at the first customer served by the groundwater source.
b. The groundwater system owner shall conduct compliance monitoring as required by subsection C of this section within 30 days of placing the source in service.
2. New groundwater sources. A groundwater system owner that places a new groundwater source into service shall meet the requirements of subdivisions 1 a and b of this subsection and conduct raw water monitoring in accordance with 12VAC5-590-425. The groundwater system owner shall provide engineering, operational, or other information as required by the ODW department to complete a determination of virus treatment effectiveness.
C. The owner of a groundwater system subject to the requirements of subsection B of this section that provides at least 4-log treatment of viruses shall monitor the effectiveness and reliability of treatment for that groundwater source before or at the first customer as follows:
1. Chemical disinfection.
a. The owner of a groundwater system that serves greater than 3,300 people shall continuously monitor and record the residual disinfectant concentration using analytical methods specified in 40 CFR 141.74 (a)(2) 12VAC5-590-440 at a location approved by the ODW department and shall record the lowest residual disinfectant concentration each day that water from the groundwater source is served to the public. The groundwater system owner shall maintain at least the ODW-determined department-determined residual disinfectant concentration every day the groundwater system serves water from the groundwater source to the public. If there is a failure in the continuous monitoring equipment, the groundwater system owner shall conduct grab sampling every four hours until the continuous monitoring equipment is returned to service. The system shall resume continuous residual disinfectant monitoring within 14 days.
b. The owner of a groundwater system that serves 3,300 or fewer people shall monitor the residual disinfectant concentration using analytical methods specified in 40 CFR 141.74 (a)(2) 12VAC5-590-440 at a location approved by the ODW department and record the residual disinfection concentration each day that water from the groundwater source is served to the public. The groundwater system owner shall maintain the ODW-determined department-determined residual disinfectant concentration every day the groundwater system serves water from the groundwater source to the public. The groundwater system owner shall take collect a daily grab sample during the hour of peak flow or at another time specified by the ODW department. If any daily grab sample measurement falls below the ODW-determined department-determined residual disinfectant concentration, the groundwater system owner shall take collect follow-up samples every four hours until the residual disinfectant concentration is restored to the ODW-determined department-determined level. A The owner of a groundwater system that serves 3,300 or fewer people may monitor continuously to meet the requirements of this subsection.
c. When the disinfection treatment is required based on confirmed E. coli contamination in the source water, the requirements in this section apply. When the disinfection treatment is required for any other reason or provided voluntarily by the owner, the department will determine the frequency of residual disinfectant monitoring.
c. d. Failure to maintain the ODW-specified department-specified minimum residual disinfectant concentration for a period of more than four hours is a violation of the treatment technique requirement.
2. A The owner of a groundwater system owner that uses an ODW-approved a department-approved alternative treatment to meet the requirements of this section by providing at least 4-log treatment of viruses before or at the first customer shall:
a. Monitor the alternative treatment in accordance with all ODW-specified department-specified monitoring requirements; and
b. Operate the alternative treatment in accordance with all ODW-specified department-specified compliance requirements necessary to achieve at least 4-log treatment of viruses.
3. Failure to meet the monitoring requirements of subsection C of this section is a violation and requires the groundwater system owner to provide public notification as required in 12VAC5-590-540 A 3.
D. Discontinuing compliance monitoring or treatment.
1. A groundwater system The owner may discontinue compliance monitoring if the ODW department determines and documents in writing that compliance monitoring is no longer necessary for that groundwater source. Owners The owner of a groundwater systems that have ODW has department approval to discontinue compliance monitoring shall be subject to the triggered source water monitoring requirements of 12VAC5-590-379 B 1.
2. A The owner of a groundwater system owner that is discontinuing compliance monitoring is still subject to the requirements of 12VAC5-590-380 G.
3. Owners of waterworks with groundwater sources that have The owner that has been required by the commissioner department to provide at least 4-log treatment of viruses shall not discontinue treatment or monitoring.
Editor's Note: The proposed repeal of 12VAC5-590-425 was adopted at final. View the entire repealed section at 36:6 VA.R. 475-845 November 11, 2019.
12VAC5-590-430. Determination of surface water influence of groundwater sources.
All waterworks' A. A groundwater sources source utilized by a waterworks such as, including wells, springs, and infiltration galleries, shall be evaluated by the division to determine surface water influence department and a determination of surface water influence shall be made by the department. The waterworks owner shall provide to the division department all necessary information to make this determination in accordance with the following three-step procedure described in subsection B of this section.
B. The groundwater source shall be evaluated and subjected to all the criteria in a stepwise fashion. Once the department has made a determination with regard to surface water influence has been made, it is not necessary to continue to the next step:
1. Step one - 1. Evaluation of source history, construction, and location.
a. The source is not surface influenced if the division has previously determined that disinfection treatment is not required (see 12VAC5-590-380 G). b. The source is surface influenced under the direct influence of surface water if it has been directly associated with a biological waterborne disease outbreak such a Giardiasis, or if it has been directly associated with chemical contamination from the surface.
c. For all sources consisting of a spring, infiltration gallery, wells located in Karstian geology, or not classified as either 12VAC5-590-430 A 1 or 2 the determination shall proceed to step two.
b. The source is under the direct influence of surface water if there are any demonstrated or known direct connections between the source to surface water via surface water bodies, sinkholes, troughs, drainage ways, or other geologic features.
c. The source is under the direct influence of surface water if a sanitary survey reveals, or there is other evidence to indicate, that surface water is directly entering the source.
d. If the department has not determined that the source is influenced by surface water based upon the criteria in subdivisions B 1 a, B 1 b, and B 1 c of this section, then the source evaluation proceeds to Step 2.
2. Step two - source physiology and geology 2. Microbiological water quality.
a. The source is not surface influenced if it consists of a properly constructed Class I or Class II well in non-Karstian geologic provinces of the state, with no history of turbidity fluctuations, and that have been determined by the division to be adequately treated by disinfection alone (12VAC5-590-380 G).
b. The source is surface influenced if a sanitary survey reveals that surface water may directly enter the source either through structural defects or through nearby surface water bodies, sinkholes, troughs, drainage ways, or other suspect geological features.
c. The determination for sources consisting of a spring, infiltration gallery, wells located in Karstian geology or otherwise not classified under 12VAC5-590-430 B 1 or 2 shall proceed to step three.
a. The owner shall collect a series of bacteriological samples directly from the source before any treatment. The specific number of samples to be collected, the sampling frequency, and the duration of sampling shall be determined by the department.
(1) At a minimum, a series of 20 samples collected on a weekly frequency is required. Sample collection may be adjusted within the week to collect samples immediately following rainfall events, whenever possible.
(2) All bacteriological analyses shall be performed [ by laboratories that have received certification by EPA or DCLS as specified ] in [ accordance with ] 12VAC5-590-440 [ by the DCLS or by a laboratory certified by the DCLS ] for drinking water samples and by a test method that will yield both total coliform concentration and E. coli concentration.
(3) The department may utilize bacteriological results from source water samples collected in accordance with 12VAC5-590-379 C if the sample results cover at least a 20-week period that includes multiple significant rainfall events for this Step 2 evaluation.
b. The total coliform concentration sample results shall be evaluated as follows:
(1) If the results of the total coliform concentration samples indicate three or more samples with total coliform greater than 100 colonies/100 ml, then the source evaluation proceeds to Step 3.
(2) If the results of the total coliform concentration samples indicate a geometric mean equal to or greater than 100 colonies/100 ml, then the requirements of 12VAC5-590-380 G 2 will apply.
c. The E. coli concentration samples shall be evaluated as follows:
(1) If the results of the E. coli concentration samples indicate greater than or equal to five E. coli per 100 ml in three or more samples, then the source evaluation proceeds to Step 3.
(2) If the results of the E. coli concentration samples indicate the presence of E. coli in five or more samples, then the source evaluation proceeds to Step 3.
3. Step three - water quality 3. Additional water quality monitoring.
a. The source is not surface influenced if the total coliform concentrations of the raw water as measured by the multiple-portion decimal-dilution (MPN) method is less than 100 organisms/100 mL based on a geometric mean of 20 or more samples over a period of six months with no more than 10% of these samples exceeding 100 organisms/100 mL; and having no record or confirmed fecal coliform contamination.
b. The source is surface influenced if:
(1) The source turbidity, temperature, pH, or conductivity fluctuate following climatic events or fluctuate relative to nearby surface bodies of water, or
(2) The source exhibits the presence of diatoms, rotifers, coccidia, plant debris, insect parts, or Giardia cysts as identified by particulate analysis.
a. The owner shall prepare and submit a written source water monitoring plan to the department for approval detailing additional water quality samples to be collected directly from the source before any treatment and if applicable from a nearby surface water source. The monitoring plan shall include the following:
(1) The specific parameters to be monitored.
(2) The monitoring frequency for each parameter.
(3) The duration of monitoring.
b. The source water monitoring plan shall include microscopic particulate analysis (MPA).
(1) A minimum of four source water MPA tests is required, two to be conducted during a wet period and two to be conducted during a dry period. All MPA tests shall be collected at least 60 days apart.
(2) All MPA tests shall be performed by a laboratory approved by the department and shall include both Giardia lamblia and Cryptosporidium.
(3) All MPA testing and reporting of results shall be in accordance with EPA "Consensus Method for Determining Groundwaters Under the Direct Influence of Surface Water Using Microscopic Particulate Analysis (MPA)," dated October 1992, Environmental Services Division.
c. The source water monitoring plan shall include monitoring of the physical parameters such as temperature, pH, turbidity, conductivity, and other parameters.
(1) If a surface water source is located near the groundwater source being evaluated, then monitoring of the nearby surface water source is required using the same physical parameters and frequency as the groundwater source.
(2) Records of rainfall and other climatological events shall be maintained and reported with the physical parameter results.
d. The owner shall provide the department with all of the monitoring results required in the approved monitoring plan. Results of all MPA tests shall be reported within 10 days of receipt by the owner. If any MPA result indicates the presence of Giardia lamblia or Cryptosporidium, then the owner shall notify the department within 24 hours of receipt. The results of the physical parameter monitoring shall be provided along with applicable rainfall or climatological data to the department in a summary report.
e. The additional water quality monitoring results shall be evaluated as follows:
(1) The source is under the direct influence of surface water if any single MPA test result indicates a score of equal to or greater than 20.
(2) The source is under the direct influence of surface water if any two MPA test results indicate a score of equal to or greater than 15.
(3) The source is under the direct influence of surface water if the results of physical parameter monitoring indicate a correlation between fluctuations in the groundwater source in direct response to a rainfall or other climatological event.
(4) The source is under the direct influence of surface water if the results of physical parameter monitoring indicate a direct correlation between the groundwater source being evaluated and the physical parameters of a nearby surface water source.
(5) The source is a groundwater source and is not under the direct influence of surface water if (i) all MPA test results indicate a score of equal to or less than 9, (ii) there are no fluctuations in source water monitored physical parameters in direct response to a rainfall or other climatological event, and (iii) there is no direct correlation in the monitored physical parameters between the groundwater source being evaluated and a nearby surface water source.
f. If the department has not determined that the source is under the direct influence of surface water based upon the criteria in subdivisions B 3 e (1) through B 3 e (4) of this section, and if at least one of the MPA test results indicate a score of greater than 9 but less than 15, then the department shall evaluate all available water quality monitoring data, source construction, location, geology, and any other relevant factors, and to determine that either:
(1) The source is a groundwater source and is not under the direct influence of surface water; or
(2) The source is at risk and requires continued source water monitoring as prescribed by the department.
C. If the source is subject to the requirements of subdivision B 3 of this section, then the owner shall perform the following interim measures until the department has made a final GUDI determination:
1. Provide disinfection treatment to achieve a 4-log inactivation of virus in accordance with 12VAC5-590-421 A 1 d;
2. Conduct compliance monitoring in accordance with 12VAC5-590-421 C 1;
3. If the disinfection treatment required in subdivision C 1 of this section has to be installed, then the owner shall issue a public notice in accordance with 12VAC5-590-540 A 1 advising consumers to boil the water before using it for human consumption. The boil water notice shall remain in effect until the disinfection treatment is installed and in operation; and
4. The department may require that the owner perform additional interim measures if deemed necessary to protect public health.
D. If the total coliform concentration criteria in subdivision B 2 b of this section or the E. coli concentration criteria in subdivision B 2 c of this section are exceeded or if the department has declared the source to be GUDI, then the owner may propose mitigation measures, a plan to correct deficiencies, or both.
1. Any proposed mitigation measures or corrective actions must be detailed in a report submitted to the department for approval. The report shall be prepared by a professional engineer licensed in Virginia, a professional geologist licensed in Virginia, or other licensed professional approved by the department. The report shall include:
a. A description of the proposed mitigation or corrective action activities such as the repair of structural defects, elimination of sources of contamination in proximity to the source, implementation of source water protection measures, or other mitigation or corrective action activities.
b. Specific milestones and milestone completion dates.
c. A follow-up source water monitoring plan to be implemented upon completion of the mitigation measures or of the corrective actions.
2. If the source must remain in operation during the period of time that the mitigation or corrective action activities are implemented and evaluated, then the department may require that the owner implement the interim measures described in 12VAC5-590-395 A 3 or subdivisions C 1 through C 4 of this section.
3. A final summary report detailing the mitigation measures, the corrective actions, or both that are completed; the results of the follow-up monitoring; conclusions; recommendations; and all other supporting data shall be submitted to the department for approval.
a. The final summary report shall be prepared by a professional engineer licensed in Virginia, a professional geologist licensed in Virginia, or other licensed professional approved by the department.
b. Upon evaluation of the final report and supporting data, the department will make a GUDI determination.
E. For any source previously determined to be a groundwater source and not under the direct influence of surface water, the department may:
1. Require that the source be reevaluated in accordance with procedures contained in this section; or
2. Waive any additional reevaluation under this section.
12VAC5-590-440. Analytical methods.
A. All drinking water analyses for compliance [ purposes with PMCLs and SMCLs or ALs ] shall have been be performed by analytical methods that are consistent with current U.S. Environmental Protection Agency EPA regulations found at 40 CFR Part 141 and 40 CFR Part 143 [ as well as 40 CFR Part 136, if applicable ]. Laboratories Standards for laboratories seeking certification to perform drinking water analyses shall comply with all are found in the Regulation for the Certification of Laboratories Analyzing Drinking Water (1VAC30-41) and [ other applicable ] regulations [ for the Accreditation for Commercial Environmental Laboratories (1VAC30-46) ] promulgated by the Department of General Services, Division of Consolidated Laboratory Services [ , ] [ and the ] DCLS.
B. For the purposes of determining compliance, the department will only accept results from samples that have been [ collected, ] handled, processed, and documented in accordance with the Regulation for the Certification of Laboratories Analyzing Drinking Water (1VAC30-41) [ and regulations for the Accreditation for Commercial Environmental Laboratories (1VAC30-46) ].
C. Testing for alkalinity, calcium, conductivity, disinfectant residual disinfectant, orthophosphate, pH, silica, temperature, [ bromide, ] and turbidity, TOC, DOC, SUVA, and [ UV254 UV254 ] for compliance purposes may be performed by any person or party acceptable to the commissioner department in accordance with methods specified in 40 CFR Part 141.
Editor's Note: Tables of 12VAC5-590-440 stricken in the proposed regulation are not further amended, therefore they are not published. View the tables as proposed at 36:6 VA.R. 475-845 November 11, 2019.
Article 3
Operation of Waterworks
12VAC5-590-450. General. Facility and personnel management..
Waterworks operation comprises the constant operation oversight and management of the facilities and personnel. Consideration must shall be given to such factors as competent the competency of personnel; standards of water quality, including drinking water standards,; water treatment plant maintenance and cleanliness,; analytical laboratory control,; and the operation and maintenance of plant equipment, plant records and safety the facilities, including water treatment plant equipment, distribution system equipment, and piping. As the degree of complexity of water treatment the waterworks increases, so does the expertise and skill required to produce a high quality water also increases of the operating staff.
Editor's Note: The proposed repeal of 12VAC5-590-460 was adopted in the final. View the repealed text at 36:6 VA.R. 475-845 November 11, 2019.
12VAC5-590-461. Classification of waterworks, operator requirements, and operator attendance.
A. Classification of waterworks. All community and NTNC waterworks, including consecutive waterworks, fitting the classification protocol in this subsection shall be designated as classified waterworks. The [ commissioner department ] retains the discretion to assign the classification of the waterworks or treatment facility either higher or lower. Those community and NTNC waterworks failing to fall within one of the classifications listed in this subsection shall be designated an unclassified waterworks unless specified otherwise by the [ commissioner department ]. Normally, a TNC waterworks shall not be classified and shall not be required to have an operator unless the [ commissioner department ] determines that it is necessary to ensure satisfactory operation of the installed treatment. If a waterworks consists of multiple treatment facilities, then these facilities may be individually classified for the purpose of determining the operator requirements.
1. Class 1 means:
a. A waterworks or a water treatment plant serving 50,000 or more persons, or having a water treatment plant capacity of 5.0 MGD or more and employing conventional filtration or chemical coagulation in combination with membrane filtration; or
b. A waterworks designated by the [ commissioner department ] to be a Class 1 waterworks.
2. Class 2 means:
a. A waterworks or a water treatment plant serving 5,000 or more persons but fewer than 50,000 persons or having a water treatment plant capacity of 0.5 MGD or more but less than 5.0 MGD, whichever range applies, and employing rapid rate conventional filtration (see 12VAC5-590-874) or chemical coagulation in combination with membrane filtration;
b. A waterworks or a water treatment plant serving fewer than 50,000 persons or having a water treatment plant capacity of less than 5.0 MGD and employing high rate conventional filtration (see 12VAC5-590-874); or
c. A waterworks designated by the [ commissioner department ] to be a Class 2 waterworks.
3. Class 3 means:
a. A waterworks or a water treatment plant serving fewer than 5,000 persons or having a water treatment plant capacity less than 0.5 MGD, whichever is greater, and employing conventional filtration or chemical coagulation in combination with membrane filtration;
b. A waterworks or a water treatment plant serving 5,000 or more persons or having a water treatment plant capacity of 0.5 MGD or more, whichever is greater, and employing one or more of the following: disinfection other than with hypochlorination, caustic soda feed, iron and manganese removal, ion exchange, slow sand filtration, aeration, rechlorination other than with hypochlorination, activated carbon contactors, membrane or other filtration technologies without chemical coagulation, and fluoridation with a saturator or acid feed;
c. A waterworks or a water treatment plant employing fluoridation with other than a saturator not considered a Class 1 or Class 2 waterworks; or
d. A waterworks designated by the [ commissioner department ] to be a Class 3 waterworks.
4. Class 4 means:
a. A waterworks or a water treatment plant serving fewer than 5,000 persons or having a water treatment plant capacity of less than 0.5 MGD and employing one or more of the following: disinfection other than with hypochlorination, caustic soda feed, iron and manganese removal, ion exchange, slow sand filtration, aeration, rechlorination other than with hypochlorination, activated carbon contactors, membrane or other filtration technologies without chemical coagulation, and fluoridation with a saturator; or
b. A waterworks designated by the [ commissioner department ] to be a Class 4 waterworks.
5. Class 5 means:
a. A waterworks serving 400 or more persons that:
(1) Provides no treatment; or
(2) Employs one or more of the following treatment processes:
(a) Hypochlorination for disinfection;
(b) Corrosion control with calcite or magnesium oxide contactors or solution feed except with caustic soda; or
(c) Sequestration by solution feed.
b. A waterworks designated by the [ commissioner department ] to be a Class 5 waterworks.
6. Class 6 means:
a. A waterworks serving fewer than 400 persons that:
(1) Provides no treatment; or
(2) Employs one or more of the following treatment processes:
(a) Hypochlorination for disinfection;
(b) Corrosion control with calcite or magnesium oxide contactors or solution feed except with caustic soda; or
(c) Sequestration by solution feed.
b. A [ waterwork waterworks ] is designated by the [ commissioner department ] to be a Class 6 waterworks.
B. Operator requirements. The operation of all waterworks must rest in the hands of qualified staff. The number and qualifications of persons constituting the operating staff at a waterworks depend principally upon the capacity of the waterworks, the number of persons served by the waterworks, and the complexity of the treatment process or processes. If a classified waterworks or water treatment plant is without a required operator, then the owner shall notify the department as soon as practical but no later than 24 hours of such an occurrence.
1. The operator attendance requirements specified in subsection C of this section are a minimum to protect the health of the consumer and safety of the operating staff. The department may increase the required operating attendance when appropriate to protect human health.
2. A classified waterworks shall be operated by an operator having a valid license issued by the Commonwealth of Virginia (18VAC160-30-90) with a classification equal to or higher than the classification of the waterworks or water treatment plant being operated. (See definition of operator in 12VAC5-590-10).
3. Operators are not required at unclassified waterworks.
C. Minimum operator attendance at classified waterworks. For the purpose of this section and 12VAC5-590-570, all classified waterworks or individual water treatment plants shall maintain the minimum operator attendance as follows:
1. Class 1. The waterworks shall have a minimum of two operating staff in attendance whenever the water treatment plant is in operation; at least one of the operating staff must be an operator.
2. Class 2. The waterworks shall have a minimum of one operator in attendance whenever the water treatment plant is in operation.
3. Class 3. The waterworks employing conventional filtration or chemical coagulation in combination with membrane filtration shall have a minimum of one operator in attendance whenever the water treatment plant is in operation. All other treatment facilities may have operator attendance similar to a Class 4 waterworks.
4. Class 4. The waterworks shall be attended by an operator at least three days per week, except that water treatment plants employing membrane filters treating surface water sources or GUDI sources shall be attended by an operator daily. The attendance shall be for sufficient time to perform the necessary operations, monitoring, and maintenance.
5. Class 5 and Class 6.
a. Where no treatment is provided, the waterworks shall be attended by an operator at least twice a month.
b. When treatment is provided, the waterworks shall be attended by an operator at least once per week.
c. The attendance shall be for sufficient time to perform the necessary operations, monitoring, and maintenance.
D. Operator attendance alternatives.
1. Increased staffing attendance may be required by the [ commissioner department ] on a case-by-case basis to protect public health.
2. Reduced operator attendance for Class 3 through Class 6 waterworks may be considered by the [ commissioner department ] on a case-by-case basis.
3. When requiring increased operator attendance or considering reduced operator attendance the [ commissioner department ] will consider the following criteria, including:
a. Operational history;
b. Type of treatment;
c. Facility capacity and hours of operation;
d. Population served;
e. Type and reliability of remote monitoring controls, alarms, and communications;
f. Reliable staff communications; and
g. Emergency response plans and procedures.
12VAC5-590-470. Waterworks appearance condition.
The general appearance and state of cleanliness of a waterworks can greatly influence the attitude of the public toward a utility and can actually promote public health. A community without confidence in its public water supply with often resort to the use of water from questionable or polluted sources; therefore, the The waterworks must shall be maintained in a clean and orderly condition to achieve this goal.
12VAC5-590-475. Removal of wells from service.
A. Temporary inactivation.
1. A water well temporarily inactivated shall be sealed with a watertight cap or wellhead seal.
2. The well shall be maintained so that it will not be a source or channel for contamination during temporary inactivation.
3. The wellhead shall be visually inspected and observations documented to verify adequate sanitary integrity on a quarterly basis.
4. The well lot shall be maintained.
B. Permanent abandonment.
1. Well abandonment shall be supervised by a certified water well systems provider.
2. All well abandonments shall be documented on a Uniform Water Well Completion Report, Form GW-2, and submitted to the department within 30 days of completing the physical abandonment.
3. Groundwater wells that are abandoned shall be sealed by methods that will restore to the fullest extent possible the controlling geological conditions that existed before the wells were constructed.
4. Casing and screen materials may be salvaged.
5. The well shall be checked from land surface to the entire depth of the well before it is sealed to ascertain freedom from obstructions that may interfere with sealing operations. Effort shall be made to remove or clear any obstacles that may prohibit sealing by grouting the complete well depth.
6. The well shall be thoroughly chlorinated before sealing.
7. Bored wells and uncased wells shall be backfilled with clean fill to the water level. A two-foot-thick bentonite grout plug shall be placed immediately above the water level. Clean fill shall be placed on top of the bentonite grout plug and brought up to at least five feet from the ground surface. The top five feet of the well casing, if present, shall be removed from the bore hole. If an open annular space is present around the well casing, then the annular space shall be filled with bentonite grout to the maximum depth possible, but less than or equal to 20 feet. A one-foot-thick cement or bentonite grout plug that completely fills the bore void space shall be placed a minimum of five feet from the ground surface. As an alternative, bored wells and uncased wells may be completely filled with concrete, sand-cement, bentonite-cement, or neat cement grout to within a minimum of five feet from the ground surface by introduction through a pipe initially extending to the bottom of the well. The pipe shall be raised but remain submerged in grout or concrete as the well is filled. The remaining space shall be filled with clean fill that is mounded a minimum of one foot above the surrounding ground surface.
8. Non-bored wells constructed in unconsolidated formations shall be completely filled with concrete, sand-cement, bentonite-cement, or neat cement grout to within a minimum of five feet from the ground surface by introduction through a pipe initially extending to the bottom of the well. The pipe shall be raised but remain submerged in grout or concrete as the well is filled. The remaining space shall be filled with clean fill that is mounded a minimum of one foot above the surrounding ground surface.
9. Wells constructed in consolidated rock formations or that penetrate zones of consolidated rock may be filled with sand or gravel opposite the zones of consolidated rock. The top of the sand or gravel fill shall be at least five feet below the top of the consolidated rock and at least 20 feet below land surface. The remainder of the well shall be filled with concrete, sand-cement, bentonite-cement, or neat cement grout to within a minimum of five feet from the ground surface by introduction through a pipe initially extending to the bottom of the well. The pipe shall be raised but remain submerged in grout or concrete as the well is filled. The remaining space shall be filled with clean fill that is mounded a minimum of one foot above the surrounding ground surface.
10. The location of the well shall be permanently documented for future reference.
12VAC5-590-476. Reactivation of wells.
A. The owner shall notify the department of the intent to reactivate a well.
B. Before bringing the well into service, the well shall be pumped to waste (purged) for a minimum of five well volumes but for not less than 30 minutes. The purged well water shall be discharged in a manner so that it will not return to the well, directly or indirectly, during the pumping period.
C. After the well is pumped, water quality samples shall be collected. If the well has been inactive for less than one year, then two samples shall be collected at least 30 minutes apart and tested for the presence of E. coli. If the well has been inactive for one or more years, then it shall be tested for total coliform density (MPN), nitrate, and, if determined by the department, inorganics, VOCs, SOCs, and radionuclides. Satisfactory test results shall be obtained before placing the well in service.
D. A well yield and drawdown test may be required by the department before bringing the well into service. The test shall be performed in accordance with 12VAC5-590-840 H, as applicable.
E. A well may be activated for emergency use before receipt of satisfactory monitoring results, even if public health and safety are unknowns and may be at risk, as determined by the department. However, in these circumstances, a special water advisory shall be approved by the department and issued by the waterworks at the same time the well is activated.
12VAC5-590-480. Analytical laboratory control Operational control testing and monitoring.
A. Analyses Water analyses and tests performed at waterworks are made conducted for four main purposes: (i) to ensure compliance; (ii) to control water treatment plant operation,; (iii) to record water treatment plant performance,; and (iv) to improve plant performance, and to undertake fundamental research of value to the plant and to the profession in general provide information for improving water treatment plant performance. Tests designed to control operation should shall present evidence that:
1. The water has been properly prepared for each major key step in the treatment process; 2. Each key process, such as mixing, coagulation, sedimentation, filtration, softening, iron and manganese removal, disinfection, and taste and odor control has proceeded according to plan, is effective; and
3. 2. The finished product is clean, is free from objectionable taste or and odor, is free from undesirable chemical characteristics, and is safe for human consumption.
B. Laboratory analyses shall conform with the most current edition available of Standard Methods for the Examination of Water and Wastewater published by the American Public Health Association, the American Water Works Association, and the Water Pollution Control Federation, or analytical methods approved by the division Testing for regulatory compliance purposes shall use an EPA-approved analytical method found in 40 CFR Parts 141 and 143. Instruments used for operational control purposes must be calibrated in accordance with manufacturer instructions. Calibrations shall be documented in a manner acceptable to the department.
C. Ample laboratory space shall be provided for all required laboratory analyses as specified in 12VAC5-590-760.
1. Chemical. The analyses listed below are the minimum required. Additional testing may be required by the division.
a. Waterworks utilizing treatment for turbidity removal shall provide equipment for the analysis of pH, alkalinity, hardness, turbidity, water temperature and coagulation dosage. An electric pH meter must be provided; however, a color comparator may be used as a back-up unit. Turbidities must be determined by the use of a nephelometer. Minimum equipment for coagulation control shall be a multiple jar stirring machine.
b. Waterworks providing softening only and utilizing chemical precipitation shall provide equipment for analysis of pH utilizing an electric pH meter, alkalinity, hardness, water temperature, and chemical dosage for precipitation utilizing a multiple jar stirring machine.
c. Waterworks providing iron and manganese removal by chemical precipitation shall provide equipment for analysis of pH, alkalinity, iron, manganese, and water temperature.
d. Waterworks providing fluoridation shall provide equipment for analysis of the fluoride ion concentration and water temperature.
e. Waterworks providing chlorination or rechlorination shall provide equipment for the analysis of chlorine residual and temperature.
f. Waterworks providing iron and manganese removal by ion exchange and or softening by ion exchange shall provide equipment for the analysis of iron and manganese, or hardness.
2. Bacteriological. Only results of bacteriological analyses performed by the Division of Consolidated Laboratory Services, or by laboratories and laboratory personnel certified by the Division of Consolidated Laboratory Services will be acceptable.
a. The number and frequency of bacteriological sampling shall comply with Article 1 of Part II. Additional analyses may be necessary when deemed so by the division.
b. Waterworks having a rated capacity of 3.0 mgd or more or serving an equivalent of 30,000 persons or more shall provide laboratory space and equipment for routine bacteriological analysis.
c. Bacteriological sampling in accordance with Article 1 of Part II is required by all waterworks.
D. Required waterworks onsite laboratory analyses. The analyses listed in this subsection are the minimum required. Additional testing may be required by the department.
1. The owner of a waterworks employing chemical coagulation or lime softening in combination with any filtration treatment for turbidity removal or TOC reduction shall provide equipment for the analysis of pH, alkalinity, hardness, turbidity, water temperature, and coagulant dosage. A calibrated electric pH meter must be provided; however, a color comparator may be used as a backup unit. Turbidities must be determined by the use of a calibrated turbidimeter.
2. The owner of a waterworks employing membrane filtration without chemical coagulation or lime softening shall provide equipment for the analysis of turbidity and temperature. Turbidities shall be determined by the use of a calibrated turbidimeter.
3. The owner of a waterworks employing softening only and utilizing chemical precipitation shall provide equipment for the analysis of pH utilizing a calibrated electric pH meter, alkalinity, hardness, water temperature, and chemical dosage for precipitation utilizing a multiple jar stirring machine.
4. The owner of a waterworks employing iron and manganese removal by chemical precipitation shall provide equipment for the analysis of pH, alkalinity, iron, manganese, and water temperature.
5. The owner of a waterworks employing fluoridation shall provide equipment for the analysis of the fluoride ion concentration and water temperature.
6. The owner of a waterworks employing chlorination, rechlorination, chloramination, or rechloramination shall provide equipment for the analysis of the appropriate chlorine residual measurement and temperature.
7. The owner of a waterworks employing iron and manganese removal by ion exchange or softening by ion exchange shall provide equipment for the analysis of iron and manganese.
E. Process control instruments, monitors, gauges, and controllers, including reading, recording, and alarm features, required in Part III, Manual of Practice [ (12VAC590-640 (12VAC5-590-640 ] et seq.), shall be maintained fully operational and calibrated in accordance with the manufacturer instructions.
1. The owner of a waterworks employing UV for inactivation credit shall perform UV sensor calibration checks. Calibrations and instrument checks shall be documented in a manner acceptable to the department. All UV sensors shall be calibrated with a reference UV sensor at least monthly. It is also recommended that offline and standby sensors be calibrated at the same time. At least one reference sensor for calibration of online sensors shall be provided. The reference UV sensor shall be calibrated at least yearly at a qualified facility, usually the manufacturer. Ultraviolet transmittance (UVT) analyzer calibration is required when used as a control instrument. The UVT analyzer shall be calibrated at least weekly by comparing online measurements to a benchtop spectrophotometer that is calibrated in accordance with manufacturer instructions. Instead of an online UVT analyzer, a benchtop spectrophotometer may be utilized to determine UV transmittance at least every four hours.
2. The owner of a waterworks employing ozone for inactivation credit shall perform calibration checks on continuous, online ozone residual monitors at least [ weekly during peak hourly flow ]. Inactivation credits for a multiple chamber contactor shall be based on only the chambers that have a measured ozone residual greater than 0.02 mg/L or higher, depending on residual analysis instrumentation.
12VAC5-590-490. Adequate treatment.
A. Adequate treatment is any one or any combination of the controlled processes of coagulation, sedimentation, absorption, filtration, disinfection, or other processes that produce a water consistently meeting the requirements of this chapter. The concept of adequate treatment also includes processes that are appropriate to (i) the source of supply water; (ii) waterworks that are of adequate capacity to meet maximum demands without creating health hazards, and that are located, designed, and constructed to eliminate or prevent cross connections cross-connections; and (iii) the conscientious operation by well-trained and competent personnel whose qualifications are commensurate with the responsibilities of the position and acceptable to the division department.
B. All A waterworks shall provide adequate treatment and pure when required and in accordance with 12VAC5-590-680 to ensure the production of potable water.
12VAC5-590-500. Disinfection by chlorination criteria, determination of CT, disinfection profiles, and disinfection benchmarks for Giardia and virus inactivation.
A. All water supplies derived from A waterworks utilizing surface water sources or GUDI sources, in whole or in part, shall be disinfected in accordance with subsection C of this section and 12VAC5-590-1000 until June 29, 1993. It is recommended that a chlorine residual be maintained. Beginning June 29, 1993, every owner of a waterworks shallcomply with the disinfection requirements of 12VAC5-590-420.
B. Owners of waterworks utilizing surface waters as a water supply shall practice prechlorination. The requirement for prechlorination may be waived by the commissioner when warranted.
C. Owners of waterworks utilizing groundwater as a water supply that has been determined by the commissioner to be under the direct influence of surface water, as provided in 12VAC5-590-430, will be required to disinfect. If the commissioner determines that the groundwater supply is surface influenced, the owner shall provide disinfection during the interim before filtration is installed in accordance with 12VAC5-590-420 B 2 f. If filtration is installed prior to June 29, 1993, the owner shall comply with the disinfection requirements of 12VAC5-590-1000 until June 29, 1993. By June 29, 1993, all owners of waterworks using a groundwater source determined to be under the direct influence of surface water shall comply with the disinfection requirements of 12VAC5-590-420.
D. Owners B. The owner of a groundwater systems system subject to the requirements of 12VAC5-590-421 A 1 d shall provide a primary disinfection treatment by means of one of the following:
1. A residual disinfectant residual concentration (C) and contact time (T) to achieve a 4-log removal or inactivation of viruses. CT shall be calculated in accordance with Appendix L subsections C and D of this section, which contains contain information on calculation methods and contact tank baffling factors.
2. UV treatment to achieve a 4-log removal or inactivation of viruses. Log inactivation shall be determined in accordance with 12VAC5-590-401 E 7 c. A secondary disinfection residual in the distribution system may be required by the department.
E. Disinfection profile data and disinfection benchmark data.
1. The owner of any waterworks that has disinfection profile data shall retain this data in graphic form, as a spreadsheet, or in some other format acceptable to the commissioner for review as part of sanitary surveys conducted by the commissioner. Appendix L lists the procedure for developing a disinfection profile.
2. Disinfection benchmarking.
a. The owner of any waterworks that has developed a disinfection profile and that decides to make a significant change to its disinfection practice shall consult with the commissioner prior to making such change. Significant changes to disinfection practice are:
(1) Changes to the point of disinfection;
(2) Changes to the disinfectants used in the treatment plant;
(3) Changes to the disinfection process; and
(4) Any other modification identified by the commissioner.
b. The owner of any waterworks that is modifying its disinfection practice shall calculate its disinfection benchmark using the following procedure:
(1) For each year of profiling data collected, the owner shall determine the lowest average monthly Giardia lamblia inactivation in each year of profiling data. The owner shall determine the average Giardia lamblia inactivation for each calendar month for each year of profiling data by dividing the sum of daily (or weekly) Giardia lamblia inactivation by the number of values calculated for that month.
(2) The disinfection benchmark is the lowest monthly average value (for waterworks with one year of profiling data) or average of lowest monthly average values (for waterworks with more than one year of profiling data) of the monthly logs of Giardia lamblia inactivation in each year of profiling data.
(3) The owner of a waterworks that uses either chloramines or ozone for primary disinfection shall also calculate the disinfection benchmark for viruses using a method approved by the commissioner.
c. The owner shall submit the following information to the commissioner as part of the waterworks' consultation process.
(1) A description of the proposed change;
(2) The disinfection profile for Giardia lamblia (and, if necessary, viruses) and benchmark listed in subdivision E 2 b of this section;
(3) An analysis of how the proposed change will affect the current levels of disinfection; and
(4) Any additional information to justify the change.
C. Disinfection criteria.
1. An owner of a waterworks utilizing surface water sources, in whole or in part, or GUDI sources shall provide a minimum 3-log (99.9%) removal of Giardia cysts and a 4-log (99.99%) removal of viruses, respectively.
2. Additional inactivation levels that must be achieved by disinfection shall be in accordance with Table 500.1 for waterworks employing the filtration processes listed.
Editor's Note: Tables 500.1 through 500.15 are not further amended from the proposed regulation, therefore they are not published. View the tables as proposed at 36:6 VA.R. 475-845 November 11, 2019.
D. A disinfection profile shall be developed in accordance with the procedures in subdivisions D 1, D 2, and D 3.
1. The owner shall monitor at least weekly for a period of 12 consecutive months to determine the total log inactivation for Giardia lamblia and viruses. If an owner monitors more frequently, then the monitoring frequency shall be evenly spaced. An owner of a waterworks that operates for fewer than 12 months per year shall monitor weekly during the period of operation.
2. The owner of a waterworks with a single point of disinfectant application before the entrance to the distribution system or with more than one point of disinfectant application shall conduct the monitoring in subdivisions D 2 a through D 2 e of this section.
a. For a waterworks using a disinfectant other than UV, the temperature of the disinfected water shall be measured at each residual disinfectant concentration sampling point during peak hourly flow or at an alternative location approved by the department.
b. For a waterworks using chlorine, the pH of the disinfected water shall be measured at each chlorine residual disinfectant concentration sampling point during peak hourly flow or at an alternative location approved by the department.
c. The residual disinfectant concentration (C) of the water before or at the first customer and before each additional point of disinfectant application shall be measured at peak hourly flow.
d. The disinfectant contact times (T) of the water before or at the first customer and before each additional point of disinfectant application shall be determined during peak hourly flow. The disinfectant contact time to be used for calculating CT is T10, which is the detention time at which 90% of the water passing through a unit is retained within that unit. T10 shall be determined either by calculations that involve the theoretical hydraulic detention time and baffling factors that account for the degree of short-circuiting that might be expected through any given unit or by tracer studies. The baffling factors listed in Table 500.15 shall be used in determining contact time if tracer studies are not performed.
e. Inactivation credits for ozone contactors will be based on only the chambers that have a measured ozone residual. A minimum of two dedicated online monitors per ozone contactor shall be installed at locations suited to the CT calculation method used. Ozone residual levels shall be monitored continuously and recorded. Methods for computing log inactivation of Giardia lamblia and virus shall be approved by the department. Tracer studies shall be required to verify T10 values before receiving inactivation credit.
3. Instead of conducting new monitoring under subdivision D 2 of this section, an owner may elect to meet the requirements of subdivision D 3 a or D 3 b of this section.
a. The owner who has at least one year of existing data that are substantially equivalent to data collected under the provisions of subdivision D 3 of this section shall use these data to develop disinfection profiles if the owner has neither made a significant change to the treatment practice nor changed sources since the data were collected. The owner may develop a disinfection profile using up to three years of existing data.
b. The owner may use a disinfection profile developed previously in accordance with the procedures in subdivisions D 1, D 2, and D 3 of this section, if the owner has neither made a change to the treatment practice nor changed sources since the profile was developed. An owner that has not developed a virus profile shall develop a virus disinfection profile using the same monitoring data on which the Giardia lamblia profile is based.
E. The owner shall calculate the total inactivation ratio for Giardia lamblia and viruses as specified in subdivisions E 1 through E 4 of this subsection based on CT99.9 (3-log) values using the appropriate values in Tables 500.2 through 500.14. Note that the 3-log values in the tables for Giardia lamblia also indicate that a 4-log virus inactivation can be achieved. pH and temperature values between the indicated values in Tables 500.2 through 500.14 shall be determined by linear interpolation, or the CT value at the lower temperature and at the higher pH shall be used. All parameters necessary to determine the total inactivation ratio shall be monitored during peak hourly flow.
1. The owner using only one point of disinfectant application shall determine the total inactivation ratio for the disinfection segment based on either of the following methods:
a. Determine one inactivation ratio (CTcalc/CT99.9) before or at the first customer during peak hourly flow.
b. Determine successive CTcalc/CT99.9 values, representing sequential inactivation ratios, between the point of disinfectant application and a point before or at the first customer during peak hourly flow. The owner shall calculate the total inactivation ratio by determining (CTcalc/CT99.9) for each sequence and then adding the (CTcalc/CT99.9) values together to determine total inactivation (∑ (CTcalc/CT99.9)).
2. The owner using more than one point of disinfectant application before the first customer shall determine the CT value of each disinfection segment immediately before the next point of disinfectant application, or for the final segment before or at the first customer, during peak hourly flow. The (CTcalc/CT99.9) value of each segment and (∑ (CTcalc/CT99.9)) shall be calculated using the method in subdivision E 1 a or E 1 b of this subsection.
3. The owner shall determine the total logs of inactivation of Giardia lamblia by multiplying the value calculated in subdivision E 1 a or E 1 b of this subsection by 3.0.
4. The owner shall determine the total logs of inactivation of viruses by multiplying the value calculated in subdivision E 1 a or E 1 b of this subsection by 4.0.
F. A disinfection benchmark shall be calculated following the procedures in subdivisions F 1, F 2, and F 3 of this subsection.
1. For each year of profiling data collected and calculated, an owner shall determine the lowest mean monthly level of both Giardia lamblia and virus inactivation. The owner shall determine the mean Giardia lamblia and virus inactivation for each calendar month for each year of profiling data by dividing the sum of daily or weekly Giardia lamblia and virus log inactivation by the number of values calculated for that month.
2. The disinfection benchmark is the lowest monthly mean value (for waterworks with one year of profiling data) or the mean of the lowest monthly mean values (for waterworks with more than one year of profiling data) of Giardia lamblia and virus log inactivation in each year of profiling data.
3. The owner of a waterworks using chloramines, ozone, or chlorine dioxide for primary disinfection shall calculate the disinfection benchmark for viruses from the data collected in the same manner used to calculate the Giardia lamblia disinfection benchmark.
G. The owner shall retain the disinfection profile in graphic form, as a spreadsheet or in some other format acceptable to the department for evaluation as part of sanitary surveys conducted by the department.
H. Before making a significant change to the waterworks disinfection practice, the owner shall review the disinfection benchmark and consult with the department.
1. Significant changes to disinfection practice are (i) changes to the point of disinfectant application, (ii) changes to the disinfectants used in the treatment plant, (iii) changes to the disinfection process, and (iv) any other modification identified by the department.
2. The owner shall submit the following information to the department as part of the consultation process: (i) a description of the proposed change; (ii) the disinfection profile and benchmarks established for Giardia lamblia and, if necessary, viruses; (iii) an analysis of how the proposed change will affect the current levels of disinfection; and (iv) any additional information to justify the change.
5-590-505. Emergency management plan for extended power outages.
A. Each The owner of a community waterworks (including consecutive waterworks) shall develop and maintain an emergency management plan for extended power outages.
B. Each The plan shall be kept current and shall be kept retained at a location that is readily accessible to the owner in the event of an extended power outage.
C. Each The owner of a community waterworks shall certify in writing to the appropriate field office of the Office of Drinking Water in the Department of Health department that the waterworks plan has been completed such plan.
D. Each The plan shall address the following where applicable:
1. Identification of the criteria (events, duration of power outage, etc.) that will initiate activation of the plan.
2. How the community waterworks owner will respond to an extended power outage for lasting a minimum of five days.
3. Procedures for obtaining and distributing potable water in the event that the primary source(s) becomes sources become unavailable.
4. Notification procedures and example notices to the public and media (local radio stations, television stations, local newspapers, etc.) including conservation notices and boil water advisories.
5. Emergency disinfection procedures for the distribution system(s) system and storage tank(s) tank.
6. The telephone number of point of contact for the appropriate field office of the Office of Drinking Water in the Virginia Department of Health department.
7. The names and telephone numbers of points of contact for the waterworks personnel who should be notified.
8. The name and telephone number of point of contact for the Local Emergency Coordinator designated by the Virginia Department of Emergency Management.
9. The names and telephone numbers of points of contact for the electric power, natural gas, and propane distributors, or other energy supplier to the waterworks.
12VAC5-590-510. Acceptable operating practices.
A. This section is not intended to be all inclusive but reflects the concern for the public health significance of certain practices related to treatment plant waterworks operation.
B. Waterworks designed for bacteria and turbidity removal shall not be operated without adequate chemical coagulation as determined by the division.
C. Waterworks utilizing filtration in the treatment process shall not vary the rate of filtration through any single filtering unit above its design capacity unless approved by the division.
D. Filtering units equipped with rewash facilities shall not be returned to service after backwashing until being thoroughly rewashed.
B. Filter operation.
1. Gravity flow granular media filters designed for pathogen and turbidity removal shall not be operated without adequate chemical coagulation as determined by the department.
2. A waterworks utilizing gravity flow granular media filtration shall not vary the rate of filtration through any single filter above its design capacity unless approved by the department.
3. Gravity flow granular media filters equipped with filter-to-waste facilities shall not be returned to service after backwashing until a thorough rinsing period has occurred so that the filter-to-waste water has a turbidity less than or equal to 0.3 NTU.
4. All MF and UF technologies employed for pathogen removal shall demonstrate removal efficiency equal to the removal (log inactivation) credit given in Table 500.1. A direct integrity test acceptable to the department shall be conducted and include the following:
a. The direct integrity test capability shall be provided for each filter unit; and
b. The direct integrity test shall be conducted at least daily for each day the filtration unit is in operation.
E. C. All waterworks shall provide a minimum working pressure of 20 psi psi-gauge (psig) at all service connections.
D. The board recommends that all community waterworks in the Commonwealth deliver the optimum fluoride ion concentration as determined by the U.S. Department of Health and Human Services.
E. A waterworks owner shall provide the commissioner at least 90 days prior written notice of the intent to initiate or discontinue a program to provide the optimum fluoride ion concentration.
12VAC5-590-515. Use of chemicals.
A. All chemicals used in water treatment shall be compliant with [ NSF/ANSI Standard 60-2017 NSF/ANSI/CAN Standard 60-2020 ]. These chemicals shall include the following:
1. Corrosion and scale inhibitors;
2. Coagulants and flocculants;
3. Disinfectants and oxidants;
4. pH adjustment chemicals;
5. Regenerating agents; and
6. Membrane cleaning compounds.
B. Chemical containers shall bear the proper certification mark and identification consistent with the Safety Data Sheet for the chemical used.
C. The owner shall maintain documentation verifying that all chemicals meet [ NSF/ANSI Standard 60-2017 NSF/ANSI/CAN Standard 60-2020 ] certification requirements.
12VAC5-590-520. Waterworks expansion capacity.
A. At such time as the water production of a community waterworks reaches 80% of the rated capacity of the waterworks for any consecutive three-month period, the owner shall cause plans and specifications to be developed for expansion of the waterworks to include a schedule for construction; however, if it can be shown by the owner that growth within the service area is limited and will not exceed the rated capacity of the waterworks or if unusual transient conditions caused production to reach the 80% level, preparation of plans and specifications for expansion will no longer be required.
B. All waterworks shall provide metering of total water production.
A. When the water production of a community waterworks reaches 80% of the permitted capacity for any consecutive three-month period, the owner shall prepare and submit a written plan within 30 days of notification by the department to address capacity needs. This plan shall be evaluated by the department and corrective actions shall be approved by the [ commissioner department ].
B. The [ commissioner department ] may require the owner to reevaluate the source water capacity of a well by conducting a yield and drawdown test in accordance with 12VAC5-590-840 H when the well has demonstrated declining yield.
12VAC5-590-530. Reporting.
A. The results of any all required monitoring activity shall be reported by the owner [ (or their or ] the owner's authorized [ agent) agent ] to the ODW department no later than (i) the 10th day of the month following the month during which the test results were received, or (ii) the 10th day following the end of the monitoring period, whichever is shorter, unless stipulated otherwise by the commissioner department. The results of any required monitoring activity shall be reported by the owner or the owner's authorized agent in a format and method prescribed by the commissioner department. For routine compliance samples analyzed for contaminants listed in Tables 340.1 through 340.7, the owner shall request that the certified analytical laboratory performing the analyses provide the data electronically to the department as per the requirements of this section.
B. It shall be the duty and responsibility of an owner to report to the ODW department in the most expeditious manner (usually by telephone) under the following circumstances. If it is done by telephone a confirming report shall be mailed for circumstances identified in subsections C through J of this section. The owner shall contact the department for the acceptable notification method. The official laboratory data report shall be sent to the department as soon as practical.
1. C. Bacteriological examination reporting.
a. 1. When a bacteriological examination shows that samples are required (see 12VAC5-590-380 D), the owner shall collect the repeat samples within 24 hours of being notified of the positive result and shall report the repeat sample results to the appropriate ODW field office department.
b. 2. Microbial contamination, as evidenced by one or more routine distribution system water samples indicating the presence of E. coli or waterborne pathogens, shall be reported by the owner to the appropriate ODW field office department by the end of the day when the owner was notified of the test result, unless ODW's field office the department is closed, in which case ODW the department shall be notified before the end of the next business day.
c. 3. An E. coli PMCL violation shall be reported by the owner to the appropriate ODW field office department by the end of the day when the owner was notified of the test result, unless the ODW field office department is closed, in which case ODW the department shall be notified before the end of the next business day.
d. Any 4. The owner who has failed to comply with the monitoring requirements of 12VAC5-590-370 shall report the monitoring violation to the appropriate ODW field office department in writing within 10 days after the owner discovers the violation and shall notify the public in accordance with 12VAC5-590-540 A 3.
2. When the daily average of turbidity testing exceeds 5.0 NTU a report shall be made within 48 hours
D. Turbidity reporting. For a waterworks required to filter for pathogen and turbidity removal, a report shall be made within 24 hours to the department if the filtered water turbidity measurement exceeds the following concentrations based on the filtration treatment type:
1. Conventional filtration -- one NTU.
2. Diatomaceous earth filtration -- five NTU.
3. Slow sand filtration -- five NTU.
4. Membrane, bag and cartridge filtration -- one NTU.
E. PMCL exceedance.
3. 1. When a PMCL of an inorganic or organic chemical is exceeded for a single sample the owner shall report same the exceedance within seven days. If any one a sample result would cause the compliance average to be exceeded, then the owner shall report same in the sample result, in context with the compliance average, to the department within 48 hours.
4. 2. When the average value of the samples collected pursuant to 12VAC5-590-410 12VAC5-590-382 and 12VAC5-590-383 exceeds the PMCL of any organic an inorganic or inorganic organic chemical, the owner shall report same the exceedance to the department within 48 hours.
5. 3. When the maximum contaminant level PMCL for radionuclides a radionuclide has been exceeded as determined by Table 2.5 340.4, the results shall be reported to the department within 48 hours.
6. F. The owner shall report to the district engineer department within 48 hours of the failure to comply with the monitoring and sanitary survey requirements of this chapter.
7. G. The owner shall report to the district engineer department within 48 hours of the failure to comply with the requirements of any the schedule prescribed pursuant to a variance or exemption.
8. H. The owner shall report a Tier 1 violation or situation, as described in 12VAC5-590-540 A 1, to the district engineer department as soon as practical, but no later than 24 hours after the owner learns of the Tier 1 violation or situation. At the same time the report is made, the owner shall consult with the field office department to determine the need for any additional actions to address the violation or situation.
9. The owner shall report a violation of treatment technique requirement resulting from a single exceedance of the maximum allowable turbidity limit, as described in 12VAC5-590-420 B 2 a (2), B 2 a (3), B 2 b (2), B 2 c (2), and B 2 d, to the district engineer as soon as practical, but no later than 24 hours after the owner learns of the violation. At the same time the report is made, the owner shall consult with the field office to determine the need for any additional actions to address the violation or situation.
C. I. Reporting requirements for coliform treatment technique violations.
1. Any The owner who that has violated the treatment technique required in 12VAC5-590-392 B shall report the violation to the appropriate ODW field office department no later than the end of the next business day after learning of the violation and shall notify the public in accordance with 12VAC5-590-540 A 2.
2. Any The owner who that is required to conduct an assessment under 12VAC5-590-392 C shall submit the assessment report within 30 days to the appropriate ODW field office department.
3. The owner shall notify the appropriate ODW field office department in writing after each scheduled corrective action is completed for corrections that were not completed by the time of submission of the assessment form under the requirements of 12VAC5-590-392 C.
D. J. The owner of a seasonal waterworks shall submit the certification of completion of the approved start-up procedure to on a form approved by the commissioner prior to department before serving water.
Editor's Note: Text stricken in 12VAC5-590-530 E through L in the proposed regulation has not been further amended, therefore it is not published. See proposed stricken text at 36:6 VA.R. 475-845 November 11, 2019.
M. K. Reporting requirements for groundwater systems. Owners of groundwater systems The owner shall report the following information in accordance with subsection A of this section.:
1. Owners of groundwater systems The owner conducting compliance monitoring as required by 12VAC5-590-421 C shall notify the ODW department as soon as possible any time practical, but no later than the next business day, whenever the groundwater system fails to meet the ODW specified department-specified minimum residual disinfectant concentration for more than four hours, but no later than the next business day.
2. Owners of groundwater systems that are The owner required to conduct corrective action as described in 12VAC5-590-421 A shall notify the ODW department within 30 days of completion of corrective action.
3. Owners of groundwater systems The owner subject to the source water monitoring requirements of 12VAC5-590-379 that do not conduct this monitoring under the provision of 12VAC5-590-380 E, shall provide documentation to the ODW department within 30 days of the collection that the sample met the criteria defined in 12VAC5-590-380 E.
N. Information to be included on the operation monthly report shall be determined by the commissioner for each waterworks on an individual basis. Appendix G contains suggested monthly operation report requirements.
12VAC5-590-531. Reporting requirements for filtration treatment and disinfection treatment.
A. The owner of a waterworks using a surface water source, a GUDI source, or both shall report monthly to the department the following specified information.
1. Turbidity measurements as required by 12VAC5-590-376 B shall be reported within 10 days after the end of each month the waterworks serves water to the public. Information that shall be reported includes:
a. The total number of filtered water turbidity measurements collected during the month.
b. The number and percentage of filtered water turbidity measurements collected during the month that are less than or equal to the turbidity limits specified in 12VAC5-590-395 A 2 b for the filtration technology being used.
c. The owner of a waterworks that uses lime softening may apply to the department for alternative exceedance levels for the levels specified in subdivision A 1 b of this section if the owner can demonstrate that higher turbidity levels in individual filters are due to lime carryover only and not due to degraded filter performance.
2. The owner of a waterworks with combined distribution systems serving at least 10,000 persons using a surface water source, a GUDI source, or both that provides conventional filtration treatment or direct filtration shall report monthly to the department the information specified in subdivisions A 2 a and A 2 b of this section. Also, the owner of a waterworks that provides filtration approved under 12VAC5-590-395 A 2 b shall report monthly to the department the information specified in subdivisions A 2 a and A 2 b of this section.
a. Turbidity measurements collected to meet 12VAC5-590-395 A 2 b shall be reported within 10 days after the end of each month the waterworks serves water to the public. Information that shall be reported includes:
(1) The total number of filtered water turbidity measurements collected during the month.
(2) The number and percentage of filtered water turbidity measurements collected during the month that are less than or equal to the turbidity limits specified in 12VAC5-590-395 A 2 b.
(3) The date and value of any turbidity measurements collected during the month that exceed 1.0 NTU for waterworks using conventional filtration treatment or direct filtration or that exceed the maximum level set by the department under 12VAC5-590-395 A 2 b.
b. The owner shall maintain the results of individual filter monitoring collected under 12VAC5-590-376 B for at least three years. The owner shall report the completion of individual filter turbidity monitoring under 12VAC5-590-376 B within 10 days after the end of each month the waterworks serves water to the public. The owner shall report individual filter turbidity measurement results collected under 12VAC5-590-376 B within 10 days after the end of each month the waterworks serves water to the public only if measurements demonstrate one or more of the conditions in 12VAC5-590-395 A 2 b. The owner of a waterworks that uses lime softening may apply to the department for alternative exceedance levels for the levels specified in 12VAC5-590-395 A 2 b if the owner can demonstrate that higher turbidity levels in individual filters are due to lime carryover only and not due to degraded filter performance.
3. For a waterworks with combined distribution systems serving 10,000 or more persons.
a. For an individual filter that has a measured turbidity level of greater than 1.0 NTU in two consecutive measurements collected 15 minutes apart, the owner shall report the filter number, the turbidity measurement, and the dates on which the exceedances occurred. In addition, the owner shall either produce a filter profile for the filter within seven days of the exceedance if the owner is not able to identify an obvious reason for the abnormal filter performance and report that the profile has been produced or report the obvious reason for the exceedance.
b. For an individual filter that has a measured turbidity level of greater than 0.5 NTU in two consecutive measurements collected 15 minutes apart at the end of the first four hours of continuous filter operation after the filter has been backwashed or otherwise taken offline, the owner shall report the filter number, the turbidity, and the dates on which the exceedances occurred. In addition, the owner shall either produce a filter profile for the filter within seven days of the exceedance if the owner is not able to identify an obvious reason for the abnormal filter performance and report that the profile has been produced or report the obvious reason for the exceedance.
c. For an individual filter that has a measured turbidity level of greater than 1.0 NTU in two consecutive measurements collected 15 minutes apart at any time in each of three consecutive months, the owner shall report the filter number, the turbidity measurement, and the dates on which the exceedances occurred. In addition, the waterworks shall conduct a self-assessment of the filter within 14 days of the exceedances and report that the self-assessment was conducted. The self-assessment shall consist of at least the following components: assessment of filter performance, development of a filter profile, identification and prioritization of factors limiting filter performance, assessment of the applicability of corrections, and preparation of a filter self-assessment report.
d. For an individual filter that has a measured turbidity level of greater than 2.0 NTU in two consecutive measurements collected 15 minutes apart at any time in each of two consecutive months, the owner shall report the filter number, the turbidity measurement, and the dates on which the exceedances occurred. In addition, the owner shall arrange for the conduct of a comprehensive performance evaluation (CPE) by the department or a third party approved by the department no later than 30 days following the exceedance and have the evaluation completed and submitted to the department no later than 90 days following the exceedance. A CPE means a thorough evaluation and analysis of a water treatment plant's performance-based capabilities and associated administrative, operational, and maintenance practices. A CPE is conducted to identify factors that may be adversely impacting a water treatment plant's capability to achieve compliance and emphasizes approaches that can be implemented without significant capital improvements.
4. For a waterworks with combined distribution systems serving fewer than 10,000 persons.
a. For an individual filter or the turbidity of CFE for waterworks with two filters that monitor CFE instead of individual filters that has a measured turbidity level of greater than 1.0 NTU in two consecutive measurements collected 15 minutes apart, the owner shall report the filter numbers, the turbidity measurements, and the dates on which the exceedances occurred and the cause (if known) for the exceedances.
b. For an individual filter or the turbidity of CFE for a waterworks with two filters that monitor CFE instead of individual filters that has a measured turbidity level of greater than 1.0 NTU in two consecutive measurements collected 15 minutes apart at any time in each of three consecutive months, the owner shall conduct a self-assessment of the filters within 14 days of the day the filter exceeded 1.0 NTU unless a CPE as specified in subdivision A 4 c of this section was required. A waterworks with two filters that monitor the CFE instead of individual filters shall conduct a self-assessment on both filters. The self-assessment shall be reported to the department and consist of at least the following components: (i) date the self-assessment was triggered, (ii) date the self-assessment was completed, (iii) an assessment of filter performance, (iv) development of a filter profile, (v) identification and prioritization of factors limiting filter performance, (vi) assessment of the applicability of corrections, and (vii) preparation of a filter self-assessment report. The self-assessment shall be submitted within 10 days after the end of the month or 14 days after the self-assessment was triggered only if it was triggered during the last four days of the month.
c. For an individual filter or the turbidity of CFE for a waterworks with two filters that monitor CFE instead of individual filters that has a measured turbidity level of greater than 2.0 NTU in two consecutive measurements collected 15 minutes apart at any time in each of two consecutive months, the owner shall arrange for a CPE, as defined in subdivision A 3 d of this section, by the department or a third party approved by the department no later than 60 days following the day the filter exceeded 2.0 NTU in two consecutive months. The owner shall report within 10 days after the end of the month that a CPE is required and the date that it was triggered. If a CPE has been completed by the department or a third party approved by the department within the 12 prior months or the owner and the department are jointly participating in an ongoing comprehensive technical assistance project at the waterworks, then a new CPE is not required. If conducted, a CPE shall be completed and submitted to the department no later than 120 days following the day the filter exceeded 2.0 NTU in two consecutive measurements for the second straight month.
5. Reporting Cryptosporidium monitoring results.
a. The owner shall report results from the source water monitoring required in 12VAC5-590-401 B no later than 10 days after the end of the first month following the month when the sample is collected.
b. The owner shall report the following data elements for each Cryptosporidium analysis:
(1) Public water system (PWS) identification number;
(2) Facility identification number;
(3) Sample collection date;
(4) Sample type (field or matrix spike);
(5) Sample volume filtered (L), to nearest 1/4 L;
(6) Was 100% of filtered volume examined; and
(7) Number of oocysts counted.
c. Quality control for Cryptosporidium analysis:
(1) For matrix spike samples, the owner shall also report the sample volume spiked and the estimated number of oocysts spiked. These data are not required for field samples.
(2) For samples in which less than 10 L is filtered or less than 100% of the sample volume is examined, the owner shall also report the number of filters used and the packed pellet volume.
(3) For samples in which less than 100% of the sample volume is examined, the owner shall also report the volume of re-suspended concentrate and volume of this re-suspension processed through immunomagnetic separation.
d. The owner shall report the following data elements for each E. coli analysis:
(1) PWS identification number;
(2) Facility identification number;
(3) Sample collection date;
(4) Analytical method number;
(5) Method type;
(6) Source water type (flowing stream, lake or reservoir, GUDI source);
(7) E. coli/100 mL; and
(8) Turbidity.
e. The owner of a waterworks serving fewer than 10,000 persons and not required to monitor for turbidity under 12VAC5-590-401 B is not required to report turbidity with their E. coli results.
B. Reporting of requirements for enhanced treatment for Cryptosporidium.
1. The owner shall report sampling schedules under 12VAC5-590-401 B and source water monitoring results under 12VAC5-590-531 A 5, unless the owner notifies the department that the owner will not conduct source water monitoring due to meeting the criteria of 12VAC5-590-401 B 4.
2. The owner shall report the use of uncovered finished water storage facilities to the department as described in 12VAC5-590-415.
3. The owner of a waterworks that provide filtration shall report their Cryptosporidium bin classification as described in 12VAC5-590-401 D.
4. The owner shall report disinfection profiles and benchmarks to the department as described in 12VAC5-590-401 C 1 and C 2 before making a significant change in disinfection practice.
5. The owner shall report to the department in accordance with Table 531.1 for any microbial toolbox options used to comply with treatment requirements under 12VAC5-590-401 D 2. Alternatively, the department may approve a waterworks to certify operation within required parameters for treatment credit rather than reporting monthly operational data for toolbox options.
Editor's Note: Table 531.1 is not further amended from the proposed regulation, therefore it is not published. View the Table 531.14 as proposed at 36:6 VA.R. 475-845 November 11, 2019.
C. Disinfection information specified in this subsection shall be reported to the department within 10 days after the end of each month the waterworks serves water to the public. Information that shall be reported includes:
1. For each day, the lowest measurement of residual disinfectant concentration in mg/L in water entering the distribution system.
2. The date and duration of each period when the residual disinfectant concentration in water entering the distribution system fell below 0.2 mg/L and when the department was notified of the occurrence.
3. The following information on the samples collected in the distribution system in conjunction with total coliform monitoring pursuant to 12VAC5-590-395 A 2.
a. Number of instances where the residual disinfectant concentration is measured;
b. Number of instances where the residual disinfectant concentration is not measured but HPC is measured;
c. Number of instances where the residual disinfectant concentration is measured but not detected and no HPC is measured;
d. Number of instances where no residual disinfectant concentration is detected and where HPC is greater than 500/mL;
e. Number of instances where the residual disinfectant concentration is not measured and HPC is greater than 500/mL; and
f. For the current and previous month the waterworks serves water to the public, the value of "V," in percent, in the following formula:
a = the value in subdivision C 3 a of this section.
b = the value in subdivision C 3 b of this section.
c = the value in subdivision C 3 c of this section.
d = the value in subdivision C 3 d of this section.
e = the value in subdivision C 3 e of this section.
g. The department may determine that based on site-specific considerations if an owner has no means for having a sample transported and analyzed for HPC by a certified laboratory under the requisite time and temperature conditions and the waterworks is providing adequate disinfection in the distribution system, the HPC compliance requirements of subdivisions C 3 a through C 3 f of this section do not apply.
4. The owner need not report the data listed in subdivision C 1 of this section if all data listed in subdivisions C 1, C 2, and C 3 of this section remain on file at the waterworks and the department determines that the owner has submitted all of the information required by subdivisions C 1, C 2, and C 3 of this section for the last 12 months.
5. A waterworks using disinfection oxidants other than free chlorine after filtration shall continue to record disinfection profile measurements and incorporate log inactivation computations into their monthly operation reports, as described in 12VAC5-590-570.
D. Reporting requirements for DBPs. The owner shall report the following information to the department in accordance with 12VAC5-590-530. The department may choose to perform calculations and determine whether the PMCL was violated, instead of having the owner report that information.
1. Locational running annual average (LRAA) reporting:
a. The owner shall report the following information for each monitoring location to the department:
(1) Number of samples collected during the last quarter.
(2) Date and results of each sample collected during the last quarter.
(3) Arithmetic average of quarterly results for the last four quarters for each LRAA, beginning at the end of the fourth calendar quarter that follows the compliance date and at the end of each subsequent quarter. If the LRAA calculated based on fewer than four quarters of data would cause the PMCL to be exceeded regardless of the monitoring results of subsequent quarters, the owner shall report this information to the department as part of the first report due following the compliance date or anytime thereafter that this determination is made. If the owner is required to conduct monitoring at a frequency that is less than quarterly, then the owner shall make compliance calculations beginning with the first compliance sample collected after the compliance date, unless the owner is required to conduct increased monitoring under 12VAC5-590-374 F 5.
(4) Whether, based on 12VAC5-590-384 B 1, the PMCL was violated at any monitoring location.
(5) Any operational evaluation levels under 12VAC5-590-384 B 1 d that were exceeded during the quarter, and if so, the location and date and the calculated TTHM and HAA5 levels.
b. The owner of a waterworks using a surface water source, a GUDI source, or both seeking to qualify for or remain on reduced TTHM and HAA5 monitoring shall report the following source water TOC information for each water treatment plant that treats surface water or groundwater under the direct influence of surface water to the department within 10 days of the end of any quarter in which monitoring is required:
(1) The number of source water TOC samples collected each month during last quarter.
(2) The date and result of each sample collected during last quarter.
(3) The quarterly average of monthly samples collected during last quarter or the result of the quarterly sample.
(4) The RAA of quarterly averages from the past four quarters.
(5) Whether the RAA exceeded 4.0 mg/L.
2. The owner of a waterworks monitoring for chlorite under the requirements of 12VAC5-590-374 G shall report:
a. The number of entry point samples collected each month for the last three months.
b. The location, date, and result of each sample (both entry point and distribution system) collected during the last quarter.
c. For each month in the reporting period, the arithmetic average of all samples collected in each three sample set collected in the distribution system.
d. Whether, based on 12VAC5-590-384 B 3, the PMCL was violated, in which month, and how many times it was violated each month.
3. The owner of a waterworks monitoring for bromate under the requirements of 12VAC5-590-374 H shall report:
a. The number of samples collected during the last quarter.
b. The location, date, and result of each sample collected during the last quarter.
c. The arithmetic average of the monthly arithmetic averages of all samples collected in the last year.
d. Whether, based on 12VAC5-590-384 B 2, the PMCL was violated.
E. Reporting requirements for disinfectants. The owner shall report the information specified in this subsection to the department in accordance with 12VAC5-590-530 [ within 10 days after the end of each monitoring period in which samples were collected ]. The department may choose to perform calculations and determine whether the MRDL was violated, instead of having the owner report that information:
1. The owner of a waterworks monitoring for chlorine or chloramines under the requirements of 12VAC5-590-374 I 1 shall report:
a. The number of samples collected during each month of the last quarter.
b. The monthly arithmetic average of all samples collected in each month for the last 12 months.
c. The arithmetic average of all monthly averages for the last 12 months.
d. Whether, based on 12VAC5-590-384 C 1, the MRDL was violated.
2. The owner of a waterworks monitoring for chlorine dioxide under the requirements of 12VAC5-590-374 I 2 shall report:
a. The dates, results, and locations of samples collected during the last quarter.
b. Whether, based on 12VAC5-590-384 C 2, the MRDL was violated.
c. Whether the MRDL was exceeded in any two consecutive daily samples and whether the resulting violation was acute or nonacute.
F. Reporting requirements for DBPPs and enhanced coagulation or enhanced softening. The owner shall report the following information to the department [ within 10 days after the end of each monitoring period in which the samples were collected ] in accordance with [ subsection A of this section 12VAC5-590-530 ]. The department may choose to perform calculations and determine whether the treatment technique was met, instead of having the owner report that information:
1. The owner of a waterworks monitoring monthly or quarterly for TOC under the requirements of 12VAC5-590-374 J and required to meet the enhanced coagulation or enhanced softening requirements in 12VAC5-590-411 A 2 shall report:
a. The number of paired (source water and treated water) samples collected during the last quarter.
b. The location, date, and results of each paired sample and associated alkalinity collected during the last quarter.
c. For each month in the reporting period that paired samples were collected, the arithmetic average of the percent reduction of TOC for each paired sample and the required TOC percent removal.
d. Calculations for determining compliance with the TOC percentage removal requirements, as provided in 12VAC5-590-411 A 3.
e. Whether the waterworks is in compliance with the enhanced coagulation or enhanced softening percent removal requirements in 12VAC5-590-411 A 2 for the last four quarters.
2. The owner of a waterworks monitoring monthly or quarterly for TOC under the requirements of 12VAC5-590-374 J and meeting one or more of the alternative compliance criteria in 12VAC5-590-411 [ A 1 b or ] A 1 c [ or A 1 d ] shall report:
a. The alternative compliance criterion that the waterworks is using.
b. The number of paired samples collected during the last quarter.
c. The location, date, and result of each paired sample and associated alkalinity collected during the last quarter.
d. The running annual arithmetic average based on monthly averages (or quarterly samples) of source water TOC for a waterworks meeting a criterion in 12VAC5-590-411 A 1 c (1) or A 1 c (3) or of treated water TOC for waterworks meeting the criterion in 12VAC5-590-411 A 1 c (2).
e. The running annual arithmetic average based on monthly averages (or quarterly samples) of source water SUVA for a waterworks meeting the criterion in 12VAC5-590-411 A 1 c (5) or of treated water SUVA for a waterworks meeting the criterion in 12VAC5-590-411 A 1 c (6).
f. The RAA of source water alkalinity for a waterworks meeting the criterion in 12VAC5-590-411 A 1 c (3) and of treated water alkalinity for a waterworks meeting the criterion in 12VAC5-590-411 [ A 1 c (1) A 1 d (1) ].
g. The RAA for both TTHM and HAA5 for a waterworks meeting the criterion in 12VAC5-590-411 A 1 c (3) or A 1 c (4).
h. The RAA of the amount of magnesium hardness removal (as CaCO3, in mg/L) for a waterworks meeting the criterion in 12VAC5-590-411 [ A 1 c (2) A 1 d (2) ].
i. Whether the waterworks is in compliance with the particular alternative compliance criterion in 12VAC5-590-411 [ A 1 b A 1 c ] or [ A 1 d ].
G. Additional reporting requirements. The owner shall report the following incidents within 24 hours to the department:
1. A waterborne disease outbreak that is potentially attributable to that waterworks.
2. Chlorine residual of below 0.2 mg/L in the water entering the distribution system. The owner also shall notify the department by the end of the next business day whether or not the residual was restored to at least 0.2 mg/L within four hours.
12VAC5-590-532. Reporting requirements for lead and copper.
A. The owner shall report all of the information in this section to the department in accordance with this section.
B. Reporting requirements for tap water monitoring for lead and copper and for water quality parameter monitoring.
1. Except as provided in subdivision B 1 g of this section, the owner shall report the information specified in this subsection for all tap water samples specified in 12VAC5-590-375 B and for all water quality parameter samples specified in 12VAC5-590-375 C within the first 10 days following the end of each applicable monitoring period specified in 12VAC5-590-375 B and C (i.e., every six months, annually, every three years, or every nine years). For monitoring periods with a duration less than six months, the end of the monitoring period is the last date samples can be collected during the period as specified in 12VAC5-590-375 B and C.
a. The results of all tap samples for lead and copper including location or a location site code and the criteria under 12VAC5-590-375 B 1 c through B 1 f or 12VAC5-590-375 C under which the site was selected for the waterworks sampling pool.
b. Documentation for each tap water lead or copper sample for which the owner requests invalidation pursuant to 12VAC5-590-375 B 6.
c. The 90th percentile lead and copper concentrations measured from among all lead and copper tap water samples collected during each monitoring period (calculated in accordance with 12VAC5-590-385 C) unless the department calculates the 90th percentile lead and copper levels under subsection I of this section.
d. With the exception of initial tap sampling conducted pursuant to 12VAC5-590-375 B 4 a, the owner shall designate any site that was not sampled during previous monitoring periods and include an explanation of why sampling sites have changed.
e. The results of all tap samples for pH, and where applicable, alkalinity, calcium, conductivity, temperature, and orthophosphate or silica collected under 12VAC5-590-375 C 2 through C 5.
f. The results of all samples collected at the entry point to the distribution system for applicable water quality parameters under 12VAC5-590-375 C 2 through C 5.
g. The owner shall report the results of all water quality parameter samples collected under 12VAC5-590-375 C 3 through 12VAC5-590-375 C 6 during each six month monitoring period specified in 12VAC5-590-375 C 4 within the first 10 days following the end of the monitoring period unless the department has specified a more frequent reporting requirement.
2. The owner of a NTNC, or a community waterworks meeting the criteria of 12VAC5-590-405 D 2 e, that does not have enough taps that can provide first-draw samples must either:
a. Provide written documentation to the department identifying standing times and locations for enough non-first-draw samples to make up the sampling pool under 12VAC5-590-375 B 2 e by the start of the first applicable monitoring period under 12VAC5-590-375 B 4, unless the department has waived prior approval of non-first-draw sample sites selected by the owner pursuant to 12VAC5-590-375 B 2 e; or
b. If the department has waived prior approval of non-first-draw sample sites selected by the owner, then the owner shall identify in writing each site that did not meet the six-hour minimum standing time and the length of standing time for that particular substitute sample collected pursuant to 12VAC5-590-375 B 2 e and include this information with the lead and copper sample results required to be submitted pursuant to subsection B of this section.
3. At a time specified by the department, or if no specific time is designated by the department, then as early as practical before the addition of a new source or any long-term change in water treatment, an owner (i) deemed to have optimized corrosion control under 12VAC5-590-405 A 2 b (3), (ii) subject to reduced monitoring pursuant to 12VAC5-590-375 B 4 d, or (iii) subject to a monitoring waiver pursuant to 12VAC5-590-375 B 7 shall submit written documentation to the department describing the change or addition. The department must approve the addition of a new source or a long-term change in treatment before it is implemented by the owner. Examples of long-term treatment changes include the addition of a new treatment process or modification of an existing treatment process. Examples of modification include switching secondary disinfectants, switching coagulants (e.g., alum to ferric chloride), or switching corrosion inhibitor products (e.g., orthophosphate to blended phosphate). Long-term changes can include dose changes to existing chemicals if the waterworks is planning long-term changes to its finished water pH or residual inhibitor concentration. Long-term treatment changes would not include chemical dose fluctuations associated with daily source water quality changes.
4. The owner of a small waterworks applying for a monitoring waiver under 12VAC5-590-375 B 7 or subject to a waiver granted pursuant to 12VAC5-590-375 B 7 c shall provide the following information to the department in writing by the specified deadline:
a. By the start of the first applicable monitoring period in 12VAC5-590-375 B 4, the owner of a small waterworks applying for a monitoring waiver shall provide the documentation required to demonstrate that the waiver criteria of 12VAC5-590-375 B 7 a and 12VAC5-590-375 B 7 b have been met.
b. No later than nine years after the monitoring previously conducted pursuant to 12VAC5-590-375 B 7 b or 12VAC5-590-375 B 7 d (1), the owner of a small waterworks desiring to maintain its monitoring waiver shall provide the information required by 12VAC5-590-375 B 7 d (1) and 12VAC5-590-375 B 7 d (2).
c. No later than 60 days after becoming aware that it is no longer free of lead-containing or copper-containing material, the owner of a small waterworks with a monitoring waiver shall provide written notification to the department setting forth the circumstances resulting in the lead-containing or copper-containing materials being introduced into the waterworks and what corrective action, if any, the owner plans to take to remove these materials.
5. The owner of a groundwater system that limits water quality parameter monitoring to a subset of entry points under 12VAC5-590-375 C 3 c shall provide by the commencement of the monitoring written correspondence to the department that identifies the selected entry points and includes information sufficient to demonstrate that the sites are representative of water quality and treatment conditions throughout the waterworks.
C. Source water monitoring reporting requirements.
1. The owner shall report the sampling results for all source water samples collected in accordance with 12VAC5-590-375 D within the first 10 days following the end of each source water monitoring period (i.e., annually, per compliance period, per compliance cycle) specified in 12VAC5-590-375 D.
2. With the exception of the first round of source water sampling conducted pursuant to 12VAC5-590-375 D 2, the owner shall specify any site that was not sampled during previous monitoring periods and include an explanation of why the sampling point has changed.
D. Corrosion control treatment reporting requirements. By the applicable dates under 12VAC5-590-405 A 2 a, an owner shall report the following information:
1. For the owner demonstrating that corrosion control has already been optimized, information required in 12VAC5-590-405 A 2 b (2) or 12VAC5-590-405 A 2 b (3).
2. For the owner required to optimize corrosion control, the owner's recommendation regarding optimal corrosion control treatment under 12VAC5-590-405 A 1 a.
3. For the owner required to evaluate the effectiveness of corrosion control treatments, the information required under 12VAC5-590-405 A 1 c.
4. For the owner required to install optimal corrosion control designated by the department under 12VAC5-590-405 A 1 d, a letter certifying that the owner has completed installing that treatment.
E. Source water treatment reporting requirements. By the applicable dates in 12VAC5-590-405 B, an owner shall provide the following information to the department:
1. If required under 12VAC5-590-405 B 2 a, the owner's recommendation regarding source water treatment; or
2. For an owner required to install source water treatment under 12VAC5-590-405 B 2 b, a letter certifying that the owner has completed installing the treatment designated by the department within 24 months after the department designated the treatment.
F. Lead service line replacement reporting requirements. The owner shall report the following information to the department to demonstrate compliance with the requirements of 12VAC5-590-405 C:
1. No later than 12 months after the end of a monitoring period in which a waterworks exceeds the lead AL in sampling referred to in 12VAC5-590-405 C 1, the owner shall submit written documentation to the department of the materials evaluation conducted as required in 12VAC5-590-375 B 1, to identify the initial number of lead service lines in the distribution system at the time the waterworks exceeds the lead AL, and provide the owner's schedule for annually replacing at least 7.0% of the initial number of lead service lines in its distribution system.
2. No later than 12 months after the end of a monitoring period in which a waterworks exceeds the lead AL in sampling referred to in 12VAC5-590-405 C 1, and every 12 months thereafter, the owner shall demonstrate to the department in writing that the owner has either:
a. Replaced in the previous 12 months at least 7.0% of the initial lead service lines or a greater number of lines specified by the department under 12VAC5-590-405 C 6 in the distribution system; or
b. Conducted sampling that demonstrates that the lead concentration in all service line samples from an individual line collected pursuant to 12VAC5-590-375 B 2 c is less than or equal to 0.015 mg/L. In these cases, the total number of lines replaced that meet the criteria in 12VAC5-590-405 C 4 shall equal at least 7.0% of the initial number of lead service lines identified under subdivision F 1 of this section or the percentage specified by the department under 12VAC5-590-405 C 6.
3. The annual letter submitted to the department under subdivision F 2 of this section shall contain the following information:
a. The number of lead service lines scheduled to be replaced during the previous year of the waterworks replacement schedule;
b. The number and location of each lead service line replaced during the previous year of the waterworks replacement schedule; and
c. If measured, the water lead concentration and location of each lead service line sampled, the sampling method, and the date of sampling.
4. The owner of a waterworks that collects lead service line samples following partial lead service line replacement required by 12VAC5-590-405 C shall report the results to the department within the first 10 days of the month following the month in which the owner receives the laboratory results or as specified by the department. The owner shall also report any additional information as specified by the department in a time and manner prescribed by the department to verify that all partial lead service line replacement activities have taken place.
G. Public education program reporting requirements. The owner shall report the following information to the department to demonstrate compliance with the requirements of 12VAC5-590-405 D.
1. The owner of a waterworks that is subject to the public education requirements in 12VAC5-590-405 D shall within 10 days after the end of each period in which the owner is required to perform public education tasks in accordance with 12VAC5-590-405 D 2 send written notice to the department that contains:
a. A demonstration that the owner has delivered the public education materials that meet the content requirements of 12VAC5-590-405 D 1 and the delivery requirements of 12VAC5-590-405 D 2; and
b. A list of all the newspapers, radio stations, television stations, and facilities and organizations to which the owner delivered public education materials during the period in which the owner was required to perform public education tasks.
2. Unless required by the department, an owner that previously has submitted the information required by subdivision G 1 b of this section need not resubmit the information required by subdivision G 1 b of this section, as long as there has been no changes in the distribution list and the owner certifies that the public education materials were distributed to the same list submitted previously.
3. No later than three months following the end of the monitoring period, the owner shall mail a sample copy of the consumer notification of tap results to the department along with a certification that the notification has been distributed in a manner consistent with the requirements of 12VAC5-590-405 D 4.
H. Reporting of additional monitoring data. The owner of a waterworks that collects sampling data in addition to that required by 12VAC5-590-375 shall report the results to the department within the first 10 days following the end of the applicable monitoring period under 12VAC5-590-375 B, 12VAC5-590-375 C, and 12VAC5-590-375 D during which the samples are collected.
I. Reporting of the 90th percentile lead and copper concentrations where the department calculates a waterworks' 90th percentile concentrations. The owner is not required to report the 90th percentile lead and copper concentrations measured from among all lead and copper tap samples collected during each monitoring period, as required by subdivision B 1 d of this section if:
1. The department has previously notified the owner that the department will calculate the waterworks' 90th percentile lead and copper concentrations based on the lead and copper tap results submitted pursuant to subdivision I 2 a of this section and has specified a date before the end of the applicable monitoring period by which the owner shall provide the results of the lead and copper tap water samples; and
2. The owner has provided the following information to the department by the date specified in subdivision I 1 of this section:
a. The results of all tap samples for lead and copper including the location of each site and the criteria under 12VAC5-590-375 B 1 c through 12VAC5-590-375 B 1 f or 12VAC5-590-375 B 1 g under which the site was selected for the waterworks sampling pool, pursuant to subdivision B 1 a of this section;
b. An identification of sampling sites utilized during the current monitoring period that were not sampled during the previous monitoring periods and an explanation why sampling sites have changed; and
c. The department has provided the results of the 90th percentile lead and copper calculations in writing to the owner before the end of the monitoring period.
12VAC5-590-540. Public notices.
A. All owners The owner shall give public notice to (i) persons served by the waterworks and (ii) the owner of any consecutive waterworks to which it sells or otherwise provides water under the following circumstances.
1. Tier 1.
a. When E. coli are present in the distribution system, or when the waterworks fails to test for E. coli when any repeat sample tests positive for total coliform;
b. Violation of the PMCL for E. coli;
c. Violation of the PMCL for nitrate, nitrite, or total nitrate and nitrite;
d. Failure to take collect a confirmation sample within 24 hours of the waterworks receipt of the first sample showing an exceedance of the nitrate or nitrite PMCL;
e. Exceedance of the nitrate PMCL by a noncommunity waterworks, where permitted to exceed the PMCL by the commissioner department;
f. Violation of the MRDL for chlorine dioxide when one or more samples taken collected in the distribution system the day following an exceedance of the MRDL at the entry point of to the distribution system exceed the MRDL;
g. Failure to monitor chlorine dioxide residuals in the distribution system the day following an exceedance of the chlorine dioxide MRDL at the entrance to the distribution system;
h. Violation of the treatment technique requirements for filtration and disinfection resulting from a single exceedance of the maximum allowable turbidity limit, where the commissioner department determines after consultation that a Tier 1 notice is required;
i. Failure to consult with the commissioner department within 24 hours after the owner learns of the violation of the treatment technique requirements for filtration and disinfection resulting from a single exceedance of the maximum allowable turbidity limit;
j. Occurrence of a waterborne disease outbreak or other waterborne emergency (such as a failure or significant interruption in key water treatment processes, a natural disaster that disrupts the water supply or distribution system, or a chemical spill or unexpected loading of possible pathogens into the source water that significantly increases the potential for drinking water contamination);
k. Detection of E. coli in groundwater source samples; or
l. Other violations or situations with significant potential to have serious adverse effects on human health as a result of short-term exposure, as determined by the commissioner [ commissioner or ] department on a case-by-case basis.
2. Tier 2.
a. All violations of the PMCL, MRDL, and treatment technique requirements, except where a Tier 1 public notice is required or where the commissioner department determines that a Tier 1 notice is required instead per subdivision A 1 l of this subsection section;
b. Violations of the monitoring and testing procedure requirements, where the commissioner department determines that a Tier 2 rather than a Tier 3 public notice is required instead, taking into account potential health impacts and persistence of the violation;
c. Failure to comply with the terms and conditions of any variance or exemption in place; or
d. Failure to take corrective action or failure to maintain at least four-log 4-log treatment of viruses (using inactivation, removal, or an approved combination of four-log 4-log virus inactivation and removal) before or at the first customer under the treatment technique requirements for waterworks with groundwater sources.
3. Tier 3.
a. Monitoring violations, except where a Tier 1 public notice is required per subdivisions A 1 d and A 1 g of this subsection section, or where the commissioner department determines that a Tier 2 public notice is required instead per subdivision A 2 b of this subsection section;
b. Failure to comply with a testing procedure, except where a Tier 1 notice is required per subdivision A 1 b of this subsection section or where the commissioner department determines that a Tier 2 notice is required instead per subdivision A 2 b of this subsection section;
c. Operation under a variance or an exemption to a PMCL or treatment technique requirement;
d. Availability of unregulated contaminant UC monitoring results; or
e. Exceedance of the fluoride secondary maximum contaminant level (SMCL); and SMCL.
f. Reporting and recordkeeping violations specified in 12VAC5-590-530 B, C, and D, and 12VAC5-590-550 L.
4. The department may require public notice for violations or other situations not listed in this section or may require a higher tier of public notice for specific violations and situations listed in this section.
a. The content and extent of distribution of these public notices shall be determined by the department.
b. The owner shall provide the public notice certification required in subsection N of this section.
c. At least 90 days before initiating or discontinuing a program to provide the optimum fluoride ion concentration, a waterworks owner shall deliver written notice to the waterworks' consumers. Notice to consumers shall be consistent with 12VAC5-590-540 C 2 d.
B. If a waterworks has a violation, failure, exceedance, or situation in a portion of the distribution system that is physically or hydraulically isolated from other parts of the distribution system, the commissioner department may allow the owner to limit distribution of the public notice to only those persons served by that the portion of the waterworks which that is out of compliance. The decision granting limited distribution of the public notice shall be issued in writing.
C. Public notice distribution requirements.
1. For Tier 1 violations, exceedances, or situations, the owner shall:
a. Provide a public notice as soon as practical but no later than 24 hours after the owner learns of the violation, exceedance, or situation;
b. Initiate consultation with the commissioner department as soon as practical, but no later than 24 hours after the owner learns of the violation, exceedance, or situation, to determine additional public notice requirements;
c. Comply with any additional public notice requirements, including any repeat notices or direction on the duration of the posted notices, that are established as a result of the consultation with the commissioner department. Such These requirements may include the timing, form, manner, frequency, and content of repeat notices (if any) and other actions designed to reach all persons served; and
d. Provide the public notice in a form and manner reasonably calculated to reach all persons served. The form and manner shall fit the specific situation, and shall be designed to reach residential, transient, and non-transient nontransient users of the waterworks. In order to To reach all persons served, owners shall use, at a minimum, one or more of the following forms of delivery:
(1) Appropriate broadcast media (such as radio and television);
(2) Posting of the public notice in conspicuous locations throughout the area served by the waterworks;
(3) Hand delivery of the public notice to persons served by the water system waterworks; or
(4) Another delivery method approved in writing by the commissioner department.
2. For Tier 2 violations, exceedances, or situations, the owner shall:
a. Provide the public notice as soon as practical, but no later than 30 days after the owner learns of the violation, exceedance, or situation. The commissioner department may allow, on a case-by-case determination, additional time for the initial notice of up to three months from the date the owner learns of the violation, exceedance, or situation; however, the commissioner department shall not grant an extension to the 30-day deadline for any unresolved violation, exceedance, or situation.
b. Repeat the public notice every three months as long as the violation, exceedance, or situation persists, unless the commissioner department determines that appropriate circumstances warrant a different repeat notice frequency. In no circumstance shall the repeat notice be given less frequently than once per year. Repeat notice frequency less than every three months shall not be allowed for (i) a violation as specified in 12VAC5-590-380 B and 12VAC5-590-392 F; (ii) a treatment technique violation for filtration and disinfection; and (iii) other ongoing violations, exceedances, or situations.
c. Consult with the commissioner department as soon as practical but no later than 24 hours after the owner learns of a violation of the treatment technique requirements for filtration and disinfection resulting from a single exceedance of the maximum allowable turbidity limit to determine whether a Tier 1 public notice is required to protect public health. If consultation does not take place within the 24-hour period, then the owner shall distribute a Tier 1 public notice of the violation within the next 24 hours (i.e., no later than 48 hours after the owner learns of the violation).
d. Provide the initial public notice and any repeat notices in a form and manner that is reasonably calculated to reach persons served in the required time period.
(1) For a community waterworks, the owner shall:
(a) Mail or otherwise directly deliver the public notice to each customer receiving a bill and to other service connections to which water is delivered by the waterworks; and
(b) Use any other distribution method reasonably calculated to reach other persons regularly served by the waterworks, if they would not normally be reached by the notice required in subdivision C 2 d (1) (a) of this subsection section. Such These persons may include those who do not pay water bills or do not have service connection addresses (e.g., house renters, apartment dwellers, university students, nursing home patients, prison inmates, etc.). Other methods may include: Publication (i) publication in a local newspaper; (ii) delivery of multiple copies for distribution by customers that provide their drinking water to others (e.g., apartment building owners or large private employers); (iii) posting in public places served by the system waterworks or on the Internet; or (iv) delivery to community organizations.
(2) For a noncommunity waterworks, the owner shall:
(a) Post the public notice in conspicuous locations throughout the distribution system frequented by persons served by the waterworks, or by mail or direct delivery to each customer and service connection (where known); and
(b) Use any other method reasonably calculated to reach other persons served by the system if they would not normally be reached by the notice required in subdivision C 2 d (2) (a) of this subsection section. Such These persons may include those served who may not see a posted notice because the posted notice is not in a location they routinely pass by. Other methods may include (i) publication in a local newspaper or newsletter distributed to customers,; (ii) use of e-mail email to notify employees or students,; or (iii) delivery of multiple copies in central locations (e.g., community centers).
e. Maintain a posted public notice in place for as long as the violation, exceedance, or situation persists, but in no case for less than seven days, even if the violation, exceedance, or situation is resolved.
3. For Tier 3 violations, exceedances, or situations the owner shall:
a. Provide the public notice not later than one year after the owner learns of the violation, exceedance, or situation or begins operating under a variance or exemption.
b. Repeat the public notice annually for as long as the violation, exceedance, variance, exemption, or other situation persists.
c. Maintain a posted public notice in place for as long as the violation, exceedance, variance, exemption, or other situation persists, but in no case less than seven days even if the violation, exceedance, or situation is resolved.
d. Instead of individual Tier 3 public notices, the owner may use an annual report detailing all violations, exceedances, and situations that occurred during the previous twelve 12 months, as long as the timing requirements of subdivision C 3 a of this subsection section are met. For a community waterworks, the Consumer Confidence Report (CCR) CCR may be used as a vehicle for the initial Tier 3 public notice and all required repeat notices, provided that:
(1) The CCR is provided to persons served by the waterworks no later than 12 months after the owner learns of the violation, exceedance, or other situation.
(2) The Tier 3 public notice contained in the CCR meets the content requirements in subsection E D of this section.
(3) The CCR is distributed in a manner meeting the delivery requirements in subdivision D 3 e C 3 e (1) of this section.
e. For a community waterworks, the owner shall:
(1) Mail or otherwise directly deliver the public notice to each customer receiving a bill and to other service connections to which water is delivered by the waterworks; and
(2) Use any other method reasonably calculated to reach other persons regularly served by the system, waterworks if they would not normally be reached by the notice required in subdivision C 3 e (1) of this subsection section. Such These persons may include those who do not pay water bills or do not have service connection addresses (e.g., house renters, apartment dwellers, university students, nursing home patients, prison inmates, etc.). Other methods may include (i) publication in a local newspaper, (ii) delivery of multiple copies for distribution by customers that provide their drinking water to others (e.g., apartment building owners or large private employers), (iii) posting in public places or on the Internet, or (iv) delivery to community organizations.
f. For a noncommunity waterworks the owner shall:
(1) Post the public notice in conspicuous locations throughout the distribution system frequented by persons served by the waterworks, or by mail or direct delivery to each customer and service connection (where known); and
(2) Use any other method reasonably calculated to reach other persons served by the system waterworks, if they would not normally be reached by the notice required in subdivision C 3 f (1) of this subsection section. Such These persons may include those who may not see a posted notice because the notice is not in a location they routinely pass by. Other methods may include: Publication (i) publication in a local newspaper or newsletter distributed to customers;, (ii) use of E-mail email to notify employees or students;, or, (iii) delivery of multiple copies in central locations (e.g., community centers).
D. Public notice contents.
1. Each public notice for PMCL, MRDL, and TT violations and other situations requiring a public notice shall include the following elements:
a. A description of the violation, exceedance, or situation, including the contaminant(s) contaminants of concern, and (as applicable) the contaminant level(s) levels;
b. When the violation, exceedance, or situation occurred;
c. Any potential adverse health effects from the violation, exceedance, or situation, including the standard language under subdivision 5 a or 5 b of this subsection, whichever is applicable;
d. The population at risk, including subpopulations particularly vulnerable if exposed to the contaminant in their drinking water;
e. Whether alternative water supplies should be used;
f. What actions consumers should take, including when they should seek medical help, if known;
g. What the owner is doing to correct the violation, exceedance, or situation;
h. When the owner expects the waterworks to return to compliance or resolve the situation;
i. The name, business address, and phone number of the owner, operator, or designee as a source of additional information concerning the notice; and
j. A statement to encourage the notice recipient to distribute the public notice to other persons served, using the standard language under subdivision 5 c of this subsection, where applicable.
2. Each public notice for a waterworks that has been granted a variance or exemption shall include the following elements:
a. An explanation of the reasons for the variance or exemption;
b. The date on which the variance or exemption was issued;
c. A brief status report on the steps the owner is taking to install treatment, find alternative sources of source water, or otherwise comply with the terms and schedules of the variance or exemption; and
d. A notice of any opportunity for public input in the review evaluation of the variance or exemption.
3. Each public notice for a waterworks that violates the conditions of a variance or an exemption shall contain the ten 10 elements listed in subdivision D 1 of this subsection section.
4. Each public notice shall:
a. Be displayed in a conspicuous way when printed or posted;
b. Not contain overly technical language or very small print;
c. Not be formatted in a way that defeats the purpose of the notice;
d. Not contain language which that nullifies the purpose of the notice; and
e. Contain information in the appropriate language(s) languages, for waterworks serving a large proportion of non-English speaking non-English-speaking consumers, regarding the importance of the notice or contain a telephone number or address where persons served may contact the owner to obtain a translated copy of the notice or to request assistance in the appropriate language.
5. The public notice shall include the following standard language:
a. For PMCL or MRDL violations, treatment technique violations, and violations of the condition of a variance or exemption--standard an exemption, use standard health effects language as specified in Appendix O 12VAC5-590-546 corresponding to each PMCL, MRDL, and treatment technique violation and for each violation of a condition of a variance or an exemption. For violation of the treatment technique requirement, the public notice shall also include one or both of the following statements, as appropriate:
(1) "We failed to conduct the required assessment."
(2) "We failed to correct all sanitary defects that were identified during the assessment."
b. For monitoring and testing procedure violations including failure to monitor for total coliform bacteria or E. coli prior to before serving water from a seasonal waterworks--standard waterworks, use standard language as specified below, including the language necessary to fill in the blanks:
"We are required to monitor your drinking water for specific contaminants on a regular basis. Results of regular monitoring are an indicator of whether or not your drinking water meets health standards. During (compliance period), we (did not monitor or test or did not complete all monitoring or testing) for (contaminant(s)), (contaminants) and therefore cannot be sure of the quality of your drinking water during that time."
c. For all public notices--standard notices, use standard language (where applicable), as specified below in this subdivision c:
"Please share this information with all the other people who drink this water, especially those who may not have received this notice directly (for example, (e.g., people in apartments, nursing homes, schools, and businesses). You can do this by posting this notice in a public place or distributing copies by hand or mail."
d. For total coliform bacteria treatment technique violations the public notice shall include the following statement: "We found coliforms indicating the need to look for potential problems in our waterworks. When this occurs, we are required to conduct assessments to identify problems and correct any problems that are found." The public notice shall also include the following statements, as appropriate:
(1) "We failed to conduct the required assessment."
(2) "We failed to correct all sanitary defects that were identified during the assessment."
e. For E. coli treatment technique violations the public notice shall include the following statement: "We violated the standard for E. coli, indicating the need to look for potential problems in our waterworks. When this occurs, we are required to conduct a detailed assessment to identify problems and to correct any problems that are found." The public notice shall also include the following statements, as appropriate:
(1) "We failed to conduct the required assessment."
(2) "We failed to correct all sanitary defects that were identified during the assessment."
E. Public notice to new billing units or customers.
1. For a community waterworks, the owner shall give a copy of the most recent public notice for any continuing violation, exceedance, variance, or exemption, or other ongoing situations situation requiring a public notice to all new billing units or new customers prior to before or at the time service begins.
2. For a noncommunity waterworks, the owner shall continuously post the public notice in conspicuous locations in order to inform new consumers of any continuing violation, exceedance, variance, or exemption, or other situation requiring a public notice for as long as the violation, exceedance, variance, exemption, or other situation persists.
F. Special notice of the availability of unregulated contaminant UC monitoring results.
1. The owner of a community waterworks or non-transient, noncommunity waterworks a NTNC shall notify persons served by the system waterworks of the availability of the results of such the sampling no later than 12 months after the monitoring results are known.
2. The special notice shall meet the requirements for of a Tier 3 public notice and shall identify a person and telephone number to contact for information on the monitoring results.
G. Special notice for exceedance of the SMCL for fluoride.
1. Community A community waterworks that exceed exceeds the SMCL of 2 mg/L, but do does not exceed the PMCL of 4 mg/L for fluoride, shall provide public notice to persons served as soon as practical but no later than 12 months from the day the owner learns of the exceedance.
2. A copy of the notice shall be sent to all new billing units and new customers at the time service begins and to the district engineer department.
3. The owner shall repeat the notice at least annually for as long as the SMCL is exceeded.
4. If the public notice is posted, then the notice shall remain in place for as long as the SMCL is exceeded, but in no case less than seven days even if the exceedance is eliminated.
5. On a case-by-case basis, the commissioner department may require an initial notice sooner than 12 months and repeat notices more frequently than annually.
6. The form and manner of the public notice (including repeat notices) shall meet the requirements for of a Tier 3 public notice.
7. The public notice shall contain the following language, including the language necessary to fill in the blanks:
"This is an alert about your drinking water and a cosmetic dental problem that might affect children under nine years of age. At low levels, fluoride can help prevent cavities, but children drinking water containing more than 2 milligrams per liter (mg/L) of fluoride may develop cosmetic discoloration of their permanent teeth (dental fluorosis). The drinking water provided by your community waterworks (name) has a fluoride concentration of (insert value) mg/L. Dental fluorosis, in its moderate or severe forms, may result in a brown staining and/or pitting of the permanent teeth. This problem occurs only in developing teeth, before they erupt from the gums. Children under nine should be provided with alternative sources of drinking water or water that has been treated to remove the excess fluoride to avoid the possibility of staining and pitting of their permanent teeth. You may also want to contact your dentist about proper use by young children of fluoride-containing products by young children. Older children and adults may safely drink the water. Drinking water containing more than 4 mg/L of fluoride (the U.S. Environmental Protection Agency's drinking water standard) can increase your risk of developing bone disease. Your drinking water does not contain more than 4 mg/L of fluoride, but we are required to notify you when we discover that the fluoride levels in your drinking water exceed 2 mg/L because of this cosmetic dental problem. For more information, please call (name of water system contact) of (name of community waterworks) at (phone number). Some home water treatment units are also available to remove fluoride from drinking water. To learn more about available home water treatment units, you may call NSF International at 1-877-NSF-HELP 1-877-867-3435 or email info@nsf.org."
H. Special notice for nitrate exceedances above PMCL by a noncommunity waterworks.
1. The owner of a noncommunity waterworks granted permission by the commissioner department to exceed the nitrate PMCL shall provide public notice to persons served meeting the requirements for of a Tier 1 notice.
2. The public notice shall be posted continuously and shall indicate the fact that nitrate levels exceed 10 mg/L and the potential health effects of exposure, meeting the requirements for of Tier 1 public notice delivery and content.
I. Special notice for repeated failure to conduct sampling of the source water for Cryptosporidium.
1. An The owner who is required to sample source water shall provide public notice to persons served when he the owner has failed to collect any three months of required samples. The form and manner of the public notice shall satisfy the requirements of a Tier 2 notice, and the notice shall be repeated in accordance with the requirements of a Tier 2 notice.
2. The notice shall contain the following language, including the language to fill in the blanks:
"We are required to monitor the source of your drinking water for Cryptosporidium. Results of the monitoring are to be used to determine whether water treatment at the [blank – fill in treatment plant name] is sufficient to adequately remove Cryptosporidium from your drinking water. We are required to complete this monitoring and make this determination by [blank – fill in required bin determination date]. We "did not monitor" or "did not complete all monitoring or testing" on schedule and, therefore, we may not be able to determine by the required date what treatment modifications, if any, shall be made to ensure adequate Cryptosporidium removal. Missing this deadline may, in turn, jeopardize our ability to have the required treatment modifications, if any, completed by the deadline required, [blank – fill in date].
For more information, please call [blank – fill in name of waterworks contact] of [blank – fill in name of waterworks] at [blank – fill in phone number]."
3. The notice shall contain a description of what the owner is doing to correct the violation and when the owner expects the waterworks to return to compliance or resolve the situation.
J. Special notice for failure to determine bin classification or mean Cryptosporidium level.
1. An The owner who that is required to determine a bin classification or to determine mean Cryptosporidium level shall provide public notice to persons served when the determination has not been made as required. The form and manner of the public notice shall satisfy the requirements of a Tier 2 notice, and the notice shall be repeated in accordance with the requirements of a Tier 2 notice. However, a public notice is not required if the owner is complying with a schedule to address the violation approved by the ODW department.
2. The notice shall contain the following language, including the language to fill in the blanks:
"We are required to monitor the source of your drinking water for Cryptosporidium in order to determine by [blank – fill in date] whether water treatment at the [blank – fill in treatment plant name] is sufficient to adequately remove Cryptosporidium from you drinking water. We have not made this determination by the required date. Our failure to do this may jeopardize our ability to have the required treatment modifications, if any, completed by the required deadline of [blank – fill in date]. For more information, please call [blank – fill in name of waterworks contact] of [blank – fill in name of waterworks] at [blank – fill in telephone number]."
3. The notice shall contain a description of what the owner is doing to correct the violation and when the owner expects the waterworks to return to compliance or resolve the situation.
K. Special notice for significant deficiencies by a noncommunity groundwater systems system.
1. Any An owner of a noncommunity groundwater system who that has not corrected a significant deficiency within one year of being notified by the ODW department shall provide public notice to the consumers.
2. The form and manner of the public notice shall satisfy the requirements of a Tier 2 notice.
3. The owner shall continue to notify the public annually until the requirements of 12VAC5-590-421 have been satisfied. The notice shall include:
a. The nature of the significant deficiency and the date it was identified by the ODW department; and
b. The ODW department approved plan and schedule for correcting the significant deficiency including interim measures, progress to date, and which of the interim measures have been completed.
4. For a noncommunity groundwater systems system with a large proportion of non-English speaking non-English-speaking consumers, the notice shall contain information in the appropriate language or languages regarding the importance of the notice or contain a telephone number or address where the consumers may contact the owner to obtain a translated copy of the notice or assistance with the appropriate language.
5. If directed by the ODW department, the owner of a noncommunity groundwater system with significant deficiencies that have been corrected shall inform the consumers of the significant deficiencies, how the deficiencies were corrected, and the date or dates of correction.
L. The district engineer department may give notice to the public required by this section on behalf of the owner if the district engineer as long as the notice complies with the requirements of this section. However, the owner remains legally responsible for ensuring that the requirements of this section are met.
M. The department may require an owner to provide public notice for significant changes in water quality.
N. Within 10 days of completion of each initial and repeat public notice, the owner shall provide the district engineer department with the following:
1. A certification that he the owner has fully complied with the public notice requirements; and
2. A representative copy of each type of notice that was distributed, published, posted, and made available to the persons served by the waterworks and to the media.
N. O. The owner shall maintain copies of each public notice and certification for at least three years after issuance.
12VAC5-590-545. Consumer confidence reports.
A. Purpose and applicability.
1. Each The owner of a community waterworks owner shall deliver to his the owner's customers an annual report that contains information on the quality of the water delivered by the waterworks and characterizes the risks, if any, from exposure to contaminants detected in the drinking water.
2. For the purpose of this section, customers are defined as billing units or service connections to which water is delivered by a community waterworks.
3. For the purpose of this section, a contaminant is detected when the laboratory reports the contaminant level as a measured level and not as nondetected (ND) [ ND or less than (<) "non-detect," "not detected," "ND," or less than ] a certain level. [ The owner shall utilize a laboratory that complies with ] 12VAC5-590-340, and the laboratory's analytical and reporting procedures shall have been in accordance with 12VAC5-590-440; laboratory certification requirements of the Commonwealth of Virginia, Department of General Services, Division of Consolidated Laboratory Services; and consistent with current U. S. Environmental Protection Agency regulations found at 40 CFR Part 141 [ 12VAC5-590-440 These express that an analyte in a test sample cannot be reliably detected with the test equipment or laboratory instrumentation and the method used ].
B. Effective dates.
1. Each The owner of an existing community waterworks owner shall deliver his the report by July 1 annually.
2. The owner of a new community waterworks shall deliver his the first report by July 1 of the year after its first full calendar year in operation and annually thereafter.
3. The owner of a community waterworks that sells water to a consecutive waterworks shall deliver the applicable information necessary to comply with the requirements contained in this section to the consecutive waterworks by April 1 annually, or on a date mutually agreed upon by the seller and the purchaser and specifically included in a contract between the parties.
C. Content.
1. Each The owner of a community waterworks owner shall provide his the owner's customers an annual report that contains the information on the source of the water delivered as follows:
a. Each The report shall identify the source or sources of the water delivered by the community waterworks by providing information on:
(1) The type of the source water (e.g., surface water, ground water); and
(2) The commonly used name, if any, and location of the body or bodies of the source water.
b. Where a source water assessment has been completed, the report shall:
(1) Notify consumers of the availability of the assessment;
(2) Describe the means to obtain the assessment; and
(3) Include a brief summary of the waterworks' susceptibility to potential sources of contamination.
c. The owner should is encouraged to highlight in the report significant sources of contamination in the source water area if such the information is readily available.
2. For the purpose of compliance with this section, each the report shall include the following definitions:
a. "Maximum contaminant level goal" or "MCLG" means the level of a contaminant in drinking water below which there is no known or expected risk to health. MCLGs allow for a margin of safety.
b. "Maximum contaminant level" or "MCL" means the highest level of a contaminant that is allowed in drinking water. MCLs are set as close to the MCLGs as feasible using the best available treatment technology.
c. A The report for a community waterworks operating under a variance or an exemption issued by the commissioner [ department commissioner ] under 12VAC5-590-140 and 12VAC5-590-150 shall include the following definition: "Variances and exemptions" means state or EPA permission not to meet an MCL or a treatment technique under certain conditions.
d. A The report that contains data on contaminants that EPA regulates using any of the following terms shall include the applicable definitions:
(1) "Treatment technique" means a required process intended to reduce the level of a contaminant in drinking water.
(2) "Action level" means the concentration of a contaminant that, if exceeded, triggers treatment or other requirements that an owner shall follow.
(3) "Maximum residual disinfectant level goal" or "MRDLG" means the level of a drinking water disinfectant below which there is no known or expected risk to health. MRDLGs do not reflect the benefits of the use of disinfectants to control microbial contaminants.
(4) "Maximum residual disinfectant level" or "MRDL" means the highest level of a disinfectant allowed in drinking water. There is convincing evidence that addition of a disinfectant is necessary for the control of microbial contaminants.
(5) "Level 1 assessment" means a study of the waterworks to identify potential problems and determine, if possible, why total coliform bacteria have been found in our waterworks.
(6) "Level 2 assessment" means a very detailed study of the waterworks to identify potential problems and determine, if possible, why an E. coli PMCL violation has occurred and why total coliform bacteria have been found in our waterworks on multiple occasions.
3. Information on detected contaminants.
a. This section specifies the requirements for information to be included in each the report for the following contaminants:
(1) Contaminants subject to a PMCL, action level, maximum residual disinfectant level MRDL, or treatment technique as specified in 12VAC5-590-370;
(2) Unregulated contaminants subject to monitoring as specified in 12VAC5-590-370; and
(3) Disinfection byproducts or microbial contaminants,, except as provided under subdivision 5 a of this subsection, and which are detected in the finished water contaminants subject to a PMCL, AL, MRDL, or treatment technique as specified in 12VAC5-590-340.
b. The data relating to these contaminants shall be displayed in one table or in several adjacent tables. Any additional monitoring results that an owner of a community waterworks owner chooses to include in the report shall be displayed separately.
c. The data shall be derived from data collected to comply with EPA and state monitoring and analytical requirements during the calendar year preceding the year the report is due, except that where an owner is allowed to monitor for contaminants specified in subdivision C 3 a (1) and 3 a (3) of this subsection section less often than once a year, the table or tables shall include the date and results of the most recent sampling, and the report shall include a brief statement indicating that the data presented in the report are from the most recent testing done in accordance with the regulations. No data older than five years need be included.
d. For detected contaminants subject to a PMCL, action level AL, MRDL, or treatment technique as specified in 12VAC5-590-370 and listed in Tables 2.1, 2.2 (Primary Maximum Contaminant Levels only), 2.3, 2.4 (Primary Maximum Contaminant Levels only), and 2.5 listed in Tables 340.1 through 340.7, the table or tables shall contain:
(1) The PMCL for that contaminant expressed as a number equal to or greater than 1.0 as provided in Appendix O, with an exception for beta/photon emitters. When the detected level of beta/photon emitters has been reported in the units of pCi/L and does not exceed 50 pCi/L, the report may list the PMCL as 50 pCi/L. In this case, the owner shall include in the report the following footnote: The PMCL for beta particles is 4 mrem/year. EPA considers 50 pCi/L to be the level of concern for beta particles 12VAC5-590-546;
(2) The MCLG for that contaminant expressed in the same units as the PMCL as provided in Appendix O 12VAC5-590-546;
(3) If there is no PMCL for a detected contaminant, then the table tables shall indicate that there is a treatment technique, or specify the action level AL, applicable to that contaminant, and the report shall include the definitions for treatment technique and/or action level, AL, or both, as appropriate, specified in subdivision C 3 d of this subsection section;
(4) For contaminants subject to a PMCL, except turbidity and E. coli, the highest contaminant level used to determine compliance and the range of detected levels is as follows:
(a) When compliance with the PMCL is determined annually or less frequently, the highest detected level at any sampling point and the range of detected levels expressed in the same units as the PMCL.
(b) When compliance with the PMCL is determined by calculating a running annual average an RAA of all samples taken collected at a sampling point, the highest average of any of the sampling points and the range of all sampling points expressed in the same units as the PMCL. For the PMCLs for TTHM and HAA5, the owner shall include the highest locational running annual average LRAA and the range of individual sample results for all sampling points expressed in the same units as the PMCL. If more than one location exceeds the TTHM or HAA5 PMCL, then the owner shall include the locational running annual averages LRAAs for all locations that exceed the PMCL.
(c) When compliance with the PMCL is determined on a systemwide system-wide basis by calculating a running annual average an RAA of all samples at all sampling points, the average and range of detection expressed in the same units as the PMCL. The range of detection for TTHM and HAA5 shall include the individual sample results for the IDSE conducted under 12VAC5-590-370 B 3 e (2) for the calendar year that the IDSE samples were taken for the purpose of establishing the monitoring locations for EPA's "Stage 2 Disinfectants and Disinfection Byproducts Rule" initial distribution system evaluation.
(5) For turbidity, the highest single measurement and the lowest monthly percentage of combined filter samples meeting the turbidity limits specified in 12VAC5-590-420 12VAC5-590-395 A 2 b for the filtration technology being used. The report should include an explanation of the reasons for measuring turbidity;
(6) For lead and copper, the 90th percentile value of the most recent round of sampling and the number of sampling sites exceeding the action level AL;
(7) For E. coli, the total number of positive samples; and
(8) The likely source or sources of the detected contaminants. Specific information regarding contaminants may be available in sanitary surveys and source water assessments, and should be used when available to the owner. If the owner lacks specific information on the likely source, then the report shall include one or more of the typical sources for that contaminant listed in Appendix O 12VAC5-590-546 that are most applicable to the system.
e. If the owner of a community waterworks owner distributes water to his the owner's customers from multiple hydraulically independent distribution systems that are fed by different raw water sources source waters, then:
(1) The table shall contain a separate column for each service area and the report shall identify each separate distribution system; or
(2) The owner shall produce a separate report tailored to include data for each service area.
f. The table or tables shall clearly identify any data indicating violations of PMCLs, MRDLs, or treatment techniques and the report shall contain a clear and readily understandable explanation of the violation including:
(1) The length of the violation;
(2) The potential adverse health effects using the relevant language of Appendix O 12VAC5-590-546; and
(3) Actions taken by the waterworks owner to address the violation.
g. For detected unregulated contaminants subject to monitoring as specified in 12VAC5-590-370 and listed in Tables 2.6 and 2.7, for which monitoring is required, the table or tables shall contain the average and range at which the contaminant was detected. The report may include a brief explanation of the reasons for monitoring for unregulated contaminants.
4. Information on Cryptosporidium, radon, and other contaminants:
a. If the owner has performed any monitoring for Cryptosporidium, which indicates that Cryptosporidium may be present in the source water or the finished water, then the report shall include:
(1) A summary of the results of the monitoring; and
(2) An explanation of the significance of the results.
b. If the owner has performed any monitoring for radon, which indicates that radon may be present in the finished water, then the report shall include:
(1) The results of the monitoring; and
(2) An explanation of the significance of the results.
c. If the owner has performed additional monitoring that indicates the presence of other contaminants in the finished water, then the report should include any results that may indicate a health concern, as determined by the commissioner [ or department ]. Detections above a proposed MCL or health advisory level may indicate possible health concerns. For such these contaminants, the report should include:
(1) The results of the monitoring; and
(2) An explanation of the significance of the results noting the existence of a health advisory or a proposed regulation.
5. Compliance with other regulations. a. In addition to the requirements of subdivision C 3 f of this subsection section, the report shall note any violation that occurred during the year covered by the report of a requirement listed below. in this subdivision 5:
(1) a. Monitoring and reporting of compliance data;
(2) b. Filtration and disinfection prescribed by 12VAC5-590-420 12VAC5-590-395. For owners an owner who have has failed to install adequate filtration or disinfection equipment or processes, or have has had a failure of such equipment or processes which that constitutes a violation, the report shall include the following language as part of the explanation of potential adverse health effects: "Inadequately treated water may contain disease-causing organisms. These organisms include bacteria, viruses, and parasites, which can cause symptoms such as nausea, cramps, diarrhea, and associated headaches";
(3) c. Lead and copper control requirements prescribed by 12VAC5-590-370 12VAC5-590-375. For owners who fail that fails to take one or more of the prescribed actions, the report shall include the applicable language of Appendix O 12VAC5-590-546 for lead, copper, or both;
(4) d. Treatment techniques for Acrylamide acrylamide and Epichlorohydrin epichlorohydrin prescribed by 12VAC5-590-420 G 12VAC5-590-395 B. For owners an owner who violate violates the requirements of that section, the report shall include the relevant language from Appendix O; 12VAC5-590-546;
(5) e. Recordkeeping of compliance data;
(6) f. Special monitoring requirements for unregulated contaminants prescribed by 12VAC5-590-370 B 4 and for sodium; and
(7) g. Violation of the terms of a variance, an exemption, or an administrative or judicial order.
b. The report shall contain:
(1) A clear and readily understandable explanation of the violation;
(2) Any potential adverse health effects; and
(3) The steps the owner has taken to correct the violation.
c. For community groundwater systems, the following shall be included:
(1) A significant deficiency that is uncorrected at the time of the report, or;
(2) An E. coli-positive groundwater source sample that is not invalidated at the time of the report.
d. The owner of a community groundwater system shall report annually the information in subdivision 5 c of this subsection until the ODW determines that the significant deficiency or the E. coli-positive source water sample has been satisfactorily addressed. The report shall include the following information:
(1) The nature of the significant deficiency or the source of the E. coli contamination and the date the significant deficiency was identified by the ODW or the date or dates of the E. coli-positive source samples.
(2) If the E. coli contamination has been addressed in accordance with 12VAC5-590-421 and the date of such action.
(3) The ODW approved plan and schedule for correcting the significant deficiency or E. coli contamination including interim measures, progress to date, and which interim measures have been completed.
(4) In communities with a large portion of non-English speaking consumers, the notice shall contain information in the appropriate language or languages regarding the importance of the notice or contain a telephone number or address where the consumers may contact the owner to obtain a translated copy of the notice or assistance with the appropriate language.
(5) For E. coli contamination, the potential health effects language shall be included.
e. If directed by the ODW, the owner of a community groundwater system with significant deficiencies that have been corrected at the time of the report shall inform his consumers of the significant deficiencies, how the deficiencies were corrected, and the date or dates of correction under subdivisions 5 d (1) through (4) of this subsection.
6. Variances and exemptions. If a system waterworks is operating under the terms of a variance or an exemption issued by the commissioner under 12VAC5-590-140 and 12VAC5-590-150, then the report shall contain:
a. An explanation of the reasons for the variance or exemption;
b. The date on which the variance or exemption was issued;
c. A brief status report on the steps the owner is taking to install treatment, find alternative sources of source water, or otherwise comply with the terms and schedules of the variance or exemption; and
d. A notice of any opportunity for public input in the review evaluation or renewal of the variance or exemption.
7. Additional information.
a. The report shall contain a brief explanation regarding contaminants, which may reasonably be expected to be found in drinking water including bottled water. This explanation shall include the exact language of subdivisions 7 a (1), 7 a (2), and 7 a (3) of this subsection or the owner shall use his own comparable language following approval by the commissioner department. The report also shall include the exact language of subdivision 7 a (4) of this subsection.
(1) The sources of drinking water (both tap water and bottled water) include rivers, lakes or reservoirs, streams, ponds, reservoirs, springs, and wells. As water travels over the surface of the land or through the ground, it dissolves naturally occurring minerals and, in some cases, radioactive material, and can pick up substances resulting from the presence of animals or from human activity.
(2) Contaminants that may be present in source water include: (i) microbial contaminants, such as viruses and bacteria, which may come from sewage treatment plants, septic systems, agricultural livestock operations, and wildlife; (ii) inorganic contaminants, such as salts and metals, which can be naturally occurring or result from urban stormwater runoff, industrial or domestic wastewater discharges, oil and gas production, mining, or farming; (iii) pesticides and herbicides, which may come from a variety of sources such as agriculture, urban stormwater runoff, and residential uses; (iv) organic chemical contaminants, including synthetic and volatile organic chemicals SOCs and VOCs, which are byproducts of industrial processes and petroleum production, and can also come from gas stations, urban stormwater runoff, and septic systems; and (v) radioactive contaminants, which can be naturally occurring or be the result of oil and gas production and mining activities.
(3) In order to To ensure that tap water is safe to drink, EPA prescribes regulations that limit the amount of certain contaminants in the water provided by public water systems waterworks. FDA The U.S. Food and Drug Administration (FDA) regulations establish limits for contaminants in bottled water which must provide the same protection for public health.
(4) Drinking water, including bottled water, may reasonably be expected to contain at least small amounts of some contaminants. The presence of contaminants does not necessarily indicate that water poses a health risk. More information about contaminants and potential health effects can be obtained by calling the Environmental Protection Agency's EPA's Safe Drinking Water Hotline (800-426-4791).
b. The report shall include the telephone number of the owner, operator, or designee of the community waterworks as a source of additional information concerning the report.
c. In communities with a large proportion of non-English speaking non-English-speaking residents, as determined by the commissioner department, the report shall contain information in the appropriate language or languages regarding the importance of the report or contain a telephone number or address where such the residents may contact the system waterworks to obtain a translated copy of the report or assistance in the appropriate language.
d. The report shall include the following information about opportunities for public participation in decisions that may affect the quality of the drinking water. The waterworks owner should consider including the following additional relevant information:
(1) The time and place of regularly scheduled board meetings of the governing body which that has authority over the waterworks.; and
(2) If regularly scheduled board meetings are not held, then the name and telephone number of a waterworks representative who has operational or managerial authority over the waterworks.
e. The owner may include such additional information as he deems deemed necessary for public education consistent with, and not detracting from, the purpose of the report.
f. For a community groundwater system:
(1) Where there is a significant deficiency that is uncorrected at the time of the report or an E. coli-positive source water sample that is not invalidated in accordance with 12VAC5-590-380 at the time of the report, the owner shall report the following:
(a) The nature of the significant deficiency or the source water, if known, of the E. coli contamination;
(b) The date the significant deficiency was identified by the department or the date or dates of the E. coli-positive source water samples;
(c) Whether the E. coli contamination has been addressed in accordance with 12VAC5-590-421 and the date of the action;
(d) The department-approved plan and schedule, including interim measures, progress to date, and which interim measures have been completed for correcting the significant deficiency or E. coli contamination; and
(e) The potential health effects language in 12VAC5-590-546 for an E. coli-positive source water sample that is not invalidated in accordance with 12VAC5-590-380.
(2) If directed by the department, where there are significant deficiencies that have been corrected at the time of the report, then the owner shall report the significant deficiencies, how the deficiencies were corrected, and the date or dates of correction.
D. Additional health information.
1. All reports shall prominently display the following language: Some people may be more vulnerable to contaminants in drinking water than the general population. Immuno-compromised persons such as persons with cancer who are undergoing chemotherapy, persons who have undergone organ transplants, people with HIV/AIDS or other immune system disorders, some elderly, and infants can be particularly at risk from infections. These people should seek advice about drinking water from their health care providers. EPA/CDC EPA and Centers for Disease Control and Prevention guidelines on appropriate means to lessen the risk of infection by Cryptosporidium and other microbial contaminants are available from the Safe Drinking Water Hotline (800-426-4791).
2. Any waterworks The owner who that detects arsenic at levels above 0.005 mg/L, but equal to or below the PMCL of 0.010 mg/L, shall include in his the report the following informational statement about arsenic: "While your drinking water meets EPA's standard for arsenic, it does contain low levels of arsenic. EPA's standard balances the current understanding of arsenic's possible health effects against the cost of removing arsenic from drinking water. EPA continues to research the health effects of low levels of arsenic, which is a mineral known to cause cancer in humans at high concentrations and is linked to other health effects such as skin damage and circulatory problems."
In lieu Instead of the statement required in this subdivision, the waterworks owner may include his own the owner's educational statement after receiving approval from the commissioner department.
3. A waterworks owner who detects arsenic levels above 0.010 mg/L shall include the health effects language contained in Appendix O. 4. An The owner who that detects nitrate at levels above 5 mg/L, but below the PMCL, shall include in his the report the following informational statement about the impacts of nitrate on children: "Nitrate in drinking water at levels above 10 ppm is a health risk for infants of less than six months of age. High nitrate levels in drinking water can cause blue baby syndrome. Nitrate levels may rise quickly for short periods of time because of rainfall or agricultural activity. If you are caring for an infant, then you should ask advice from your health care provider."
In lieu Instead of the statement required in this subdivision, the waterworks owner may include his the owner's own educational statement after receiving approval from the commissioner department.
5. 4. All reports shall prominently display the following language: "If present, elevated levels of lead can cause serious health problems, especially for pregnant women and young children. Lead in drinking water is primarily from materials and components associated with service lines and home plumbing. (Name of Utility) is responsible for providing high quality drinking water, but cannot control the variety of materials used in plumbing components. When your water has been sitting for several hours, you can minimize the potential for lead exposure by flushing your tap for 30 seconds to two minutes before using water for drinking or cooking. If you are concerned about lead in your water, then you may wish to have your water tested. Information on lead in drinking water, testing methods, and steps you can take to minimize exposure is available from the Safe Drinking Water Hotline (800-426-4791)."
In lieu Instead of the statement required in this subdivision, the owner may include [ his ] own the owner's educational statement after receiving approval from the commissioner department.
6. Community waterworks owners who detect TTHM above 0.080 mg/L, but below the PMCL, as an annual average shall include health effects language prescribed by paragraph 82 of Appendix O.
E. Community The owner of a community waterworks owners required to complete a Level 1 or a Level 2 assessment that is not due to an E. coli PMCL violation shall include in the report the text specified in subdivisions E 1, E 2, and E 3 of this section as appropriate, filling in the blanks accordingly, and shall include in the report the text specified in subdivision E 4 of this section, if appropriate.
1. "Coliforms are bacteria that are naturally present in the environment and are used as an indicator that other, potentially harmful, waterborne pathogens may be present or that a potential pathway exists through which contamination may enter the drinking water distribution system. We found coliforms indicating the need to look for potential problems in water treatment or distribution. When this occurs, we are required to conduct assessments to identify problems and to correct any problems that are found."
2. "During the past year, we were required to conduct (insert the number of Level 1 assessments) Level 1 assessments. (insert the number of Level 1 assessments) Level 1 assessments were completed. In addition, we were required to [ take collect ] (insert the number of corrective actions) corrective actions and we completed (insert the number of corrective actions) of these actions."
3. "During the past year (insert the number of Level 2 assessments) Level 2 assessments were required to be completed for our waterworks. (insert the number of Level 2 assessments) Level 2 assessments were completed. In addition, we were required to [ take collect ] (insert the number of corrective actions) corrective actions and we completed (insert the number of corrective actions) of these actions."
4. Any An owner who that failed to complete all of the required assessments or correct all identified sanitary defects shall also include one or both of the following statements, as appropriate:
a. "During the past year, we failed to conduct all of the required assessments."
b. "During the past year, we failed to correct all identified sanitary defects that were found during the assessments."
F. Community The owner of a community waterworks owners required to conduct Level 2 assessments due to an E. coli PMCL violation shall include in the report the text specified in subdivisions F 1 and F 2 of this section, filling in the blanks accordingly, and shall include in the report the text specified in subdivision F 3 of this section, if appropriate.
1. "E. coli are bacteria whose presence indicates that the water may be contaminated with human or animal wastes. Human pathogens in these wastes can cause short-term effects, such as diarrhea, cramps, nausea, headaches, or other symptoms. They may pose a greater health risk for infants, young children, the elderly, and people with severely compromised immune systems. We found E. coli, indicating the need to look for potential problems in water treatment or distribution. When this occurs, we are required to conduct assessments to identify problems and to correct any problems that are found."
2. "We were required to complete a Level 2 assessment because we found E. coli in our waterworks. In addition, we were required to [ take collect ] (insert number of corrective actions) corrective actions and we completed (insert number of corrective actions) of these actions."
3. Any owner who that has failed to complete the required assessment or correct all identified sanitary defects shall also include one or both of the following statements, as appropriate:
a. "We failed to conduct the required assessment."
b. "We failed to correct all sanitary defects that were identified during the assessment that we conducted."
4. If a waterworks detects E. coli is detected in a waterworks and has violated the E. coli PMCL is violated, in addition to completing the table as specified in subdivision C 3 d of this section, the owner shall include one or more of the following statements to describe any noncompliance, as applicable:
a. "We had an E. coli-positive repeat sample following a total coliform-positive routine sample."
b. "We had a total coliform-positive repeat sample following an E. coli-positive routine sample."
c. "We failed to take collect all the required repeat samples following an E. coli-positive routine sample."
d. "We failed to test for E. coli when any repeat sample tested positive for total coliform."
5. If a waterworks detects E. coli is detected in a waterworks and has not violated the E. coli PMCL is not violated, in addition to completing the table as specified in subdivision C 3 d of this section, the owner may include a statement that explains that although they have detected E. coli, they are was detected, the owner is not in violation of the E. coli PMCL.
G. Report delivery and recordkeeping.
1. Each The owner of a community waterworks owner shall mail or otherwise directly deliver one copy of the report to each customer, except as follows:
a. Owners of community waterworks The owner serving fewer than 10,000 persons shall have the option to either mail (or otherwise directly deliver) a copy of the report to each customer or publish the report in a local newspaper or newspapers of general circulation serving the area in which the waterworks is located by July 1 of each year; and
b. If the owner chooses to publish the report, then the owner shall inform customers, either in the newspaper in which the report is to be published or by other means approved by the commissioner department, that a copy of the report will not be mailed to them and that a copy of the report will be made available to the public upon request.
2. Community The owner of a community waterworks owners shall make a good faith effort to deliver the report to the consumers who are served by the waterworks but are not bill paying bill-paying customers, such as renters or workers. This good faith effort shall include at least one, and preferably two or more, of the following methods appropriate to the particular waterworks:
a. Posting the reports on the Internet;
b. Mailing to postal patrons in metropolitan areas;
c. Advertising the availability of the report in the news media;
d. Publication Publishing in a local newspaper;
e. Posting in public places such as libraries, community centers, and public buildings;
f. Delivery of Delivering multiple copies for distribution by single-biller customers such as apartment buildings or large private employers;
g. Delivery Delivering to community organizations; or
h. Other methods as approved by the commissioner department.
3. No later than July 1 of each year, the owner of a community waterworks owners shall deliver a copy of the report to the district engineer department, followed within three months by a certification that the report has been distributed to customers and that the information in the report is correct and consistent with the compliance monitoring data previously submitted to the commissioner department.
4. No later than July 1 of each year, the owner of a community waterworks owners shall deliver the report to any other agency or clearinghouse specified by the commissioner department.
5. Community The owner of a community waterworks owners shall make the report available to the public upon request.
6. The owner of each a community waterworks serving 100,000 or more persons shall post the current year's report to a publicly accessible site on the Internet.
7. Community The owner of a community waterworks owners shall retain copies of the report for no less than three years.
12VAC5-590-546. Regulated contaminants for the consumer confidence reports and public notification.
A. Public notices and CCRs shall contain the appropriate mandatory language and information listed, as required by 12VAC5-590-540 and 12VAC5-590-545.
B. Information on regulated contaminants is presented in Table 546.1.
Editor's Note: Table 546.1 is not further amended from the proposed regulation, therefore it is not published. View the Table 546.1 as proposed at 36:6 VA.R. 475-845 November 11, 2019.
12VAC5-590-550. Recordkeeping.
A. The owner shall maintain all of the waterworks records in accordance with the Records Retention and Disposition Schedule of the Library of Virginia, General Schedule No. 7 for public utility records of county and municipal governments.
All owners B. The owner shall retain at their the waterworks or at a convenient location near their the waterworks the following records for the minimum not less than the time periods specified:
A. Records of microbiological 1. Microbiological analyses and turbidity analyses, including records of any repeat samples taken collected and meeting the criteria for an extension of the 24-hour period for collecting repeat samples as required under 12VAC5-590-380 -- Five years.
B. 2. Chemical Analyses -- 10 years.
3. The following information shall be provided for subdivisions B 1 and B 2 of this section:
a. Date, place, and time of sampling as well as the name of the person who collected the sample;
b. Identification of sample (e.g., routine, repeat, confirmation sample, source water, other);
c. Date of analysis;
d. Laboratory or person responsible for performing analysis;
e. Analytical method or technique used; and
f. Results of the analysis.
C. 4. Individual filter monitoring required under 12VAC5-590-530 E 1 b (2) 12VAC5-590-531 A 2 b -- Three years.
D. 5. Results of Disinfection Profile disinfection profile including raw data and analysis -- Indefinitely.
E. 6. Disinfection Benchmarking benchmarking including raw data and analysis -- Indefinitely.
F. The following information shall be provided for subsections A and B of this section:
1. Date, place, and time of sampling as well as the name of the person who collected the sample;
2. Identification of sample (e.g., routine, check sample, raw water, other);
3. Date of analysis;
4. Laboratory and/or person responsible for performing analysis;
5. Analytical method/technique used; and
6. Results of the analysis.
G. 7. Original records of all sampling data and analyses, reports, surveys, letters, evaluations, schedules, commissioner department determinations, and any other information required by 12VAC5-590-405 A 1 and 2, B, C, and D; and 12VAC5-590-375 B, C, and D 12VAC5-590-405 A 2, 12VAC5-590-405 B, 12VAC5-590-405 C, and 12VAC5-590-405 D pertaining to lead and copper. Each waterworks owner shall retain the records required by this section for no fewer than -- 12 years.
H. Owners shall keep results 8. Results from the initial round of source water monitoring under 12VAC5-590-420 B 3 a (1) 12VAC5-590-401 B 1 and the second round of source water monitoring under 12VAC5-590-420 B 3 a (2) 12VAC5-590-401 B 2 until three years after bin classification under 12VAC5-590-420 B 3 c (1) 12VAC5-590-401 D 1 for the particular round of monitoring.
I. Owners shall keep any 9. Any notification to the commissioner department that they will not conduct source water monitoring will not be conducted due to meeting the criteria of 12VAC5-590-420 B 3 a (4) for three 12VAC5-590-401 B 4 -- Three years.
J. Owners shall keep the results 10. Results of treatment monitoring associated with microbial toolbox options under 12VAC5-590-420 B 3 d (3) through (7) 12VAC5-590-401 E 3 through 12VAC5-590-401 E 7 and with uncovered finished water reservoirs under 12VAC5-590-420 L 12VAC5-590-415, as applicable, for three -- Three years.
K. 11. Action taken to correct violations of these regulations -- three this chapter-- Three years after last action with respect to violation involved.
L. Owners 12. The owner shall retain completed assessment forms for all Level 1 and Level 2 assessments conducted in accordance with 12VAC5-590-392 C, regardless of who conducts the assessment, and documentation of corrective actions completed as a result of those assessments, or other available summary documentation of the sanitary defects and correction actions taken under 12VAC5-590-392 D for a period not less than five years after completion of the assessment or corrective action, whichever is later.
M. 13. Copies of reports, summaries, or communications relating to any sanitary surveys performed -- 10 years following inspection.
N. 14. Variance or exemptions granted (and records related thereto) -- five Five years following expiration of the variance or exemption.
O. Cross connection 15. Cross-connection control program records -- 10 years.
P. Owners of 16. The owner of a waterworks that recycle recycles flow, as stipulated in 12VAC5-590-420 K 12VAC5-590-395 C, shall collect and retain on file the recycle flow information for review and evaluation by the district engineer beginning June 8, 2004 department. This information shall be retained for a minimum of 10 years. Information shall include, as a minimum:
1. a. Copy of the recycle notification submitted to the district engineer under 12VAC5-590-530 K department.
2. b. List of all recycle flows and the frequency with which they are returned.
3. c. Average and maximum backwash flow rate through the filters and the average and maximum duration of the filter backwash process, in minutes.
4. d. Typical filter run length and a written summary of how the filter run length is determined.
5. e. The type of treatment provided for the recycle flow.
6. f. Data on the physical dimensions of the equalization and/or or treatment units, typical and maximum hydraulic loading rates, type of treatment chemicals used, average dose, frequency of use, and frequency at which solids are removed, if applicable.
Q. 17. Copies of monitoring plans developed pursuant to [ these regulations this chapter ] shall be kept for the same period of time as the records of analyses taken under the plan are required to be kept under subsection A or B of this section, except as specified elsewhere in this chapter.
R. All owners 18. The owner shall retain the following additional records:
1. a. Plant operational records. -- five years after the end of the calendar year;
2. Water well completion reports. b. Current organizational or staffing chart;
3. c. Record (As-built) engineering plans and specifications of facilities. -- Retain for the life of the facility;
d. Equipment manuals for items in use -- Retain for the life of the equipment or facility;
4. e. Shop drawings of major equipment. in use -- Retain for the life of the equipment;
f. Current list or chart of required laboratory tests with test frequencies and sampling locations;
g. Current preventive maintenance schedule;
5. h. Records of equipment repair or replacement. of equipment in use --
Retain for the life of the equipment;
6. i. Updated map of water distribution system.; and
7. j. All accident reports. -- Three years.
S. Additional recordkeeping requirements for groundwater systems C. The owner of a waterworks with groundwater sources shall maintain the following records:
1. Records of corrective Corrective actions – --10 years.
2. Records of public Public notification as required by 12VAC5-590-540 – -- Three years.
3. Records of invalidation Invalidation of groundwater source samples – -- Five years.
4. For consecutive waterworks, records of notification to the wholesale waterworks of coliform-positive samples – -- Five years.
5. For a waterworks required to conduct compliance monitoring:
a. Records of the ODW Department-specified minimum disinfectant residual disinfectant – --10 years.
b. Records of the lowest Lowest daily residual disinfectant concentration – -- Five years.
c. Records of the dates Dates and duration of any failure to maintain the ODW department-specified minimum residual disinfectant concentration for a period of more than four hours – -- Five years.
d. Records of any ODW Department-specified compliance parameters for alternative treatment and records of the date and duration of any failure to meet the alternative treatment operating requirements for more than four hours – -- Five years.
12VAC5-590-560. Safety.
Since its trained personnel is the waterworks' most important asset, an important phase of waterworks operation is the protection of personnel through an active safety program; therefore, it is strongly recommended that every waterworks institute a safety program. The owner of a waterworks shall institute a safety program to inform personnel of the known hazards, preventive measures, and emergency procedures pertaining to the operation of the waterworks in accordance with VOSH laws and regulations.
12VAC5-590-565. Source water protection.
A. A waterworks owned by a county, city, or town may exercise the authority pursuant to § 15.2-2109 of the Code of Virginia to protect the waterworks from pollution or injury.
B. The owner of a waterworks with a drinking water reservoir may establish a buffer around the intake to limit such uses as body contact recreation and boats powered by engines, pursuant to a plan acceptable to the department.
C. The owner of a waterworks should develop a source water protection plan for all the sources and report ongoing or completed protection initiatives to the department.
12VAC5-590-570. Operational report forms reporting requirements.
All waterworks required to report information to the department shall use the forms approved by the division.
A. Monthly operational reports.
1. A classified waterworks is required to report monthly information to the department no later than the 10th of the month following the month during which the monitoring period occurred.
2. A classified waterworks using conventional filtration shall report using the monthly operating report (MOR) form approved by the department. All other classified waterworks shall report the required information specified in Tables 570.1 through [ 570.13 570.14 ], based on the treatment processes employed. Monitoring data shall be collected for each day the operating staff attend to the operation of the facilities.
3. To determine if a waterworks using UV reactor systems is operating within validated conditions designed in accordance with 12VAC5-590-1005, the following parameters shall be monitored and reported: (i) on/off status for each reactor; (ii) flow rate through reactor train; (iii) UV intensity as measured by a UV sensor; (iv) lamp status; (v) lamp age; and (vi) UV transmittance. The operational set points shall be reported if set point control is used. The calculated UV dose shall be reported if other than a set point control is used.
4. An unclassified waterworks is required to report quarterly the following information specified in Table 570.1, where applicable, to the department no later than the 10th of the month following the calendar quarter during which the monitoring period occurred.
5. An unclassified waterworks that is using any of the treatment processes described in Tables 570.2 through [ 570.13 570.14 ] is required to report no later than the 10th of the month following the calendar month during which the monitoring occurred. The report shall contain the required information specified in Tables 570.1 through [ 570.13 570.14 ] based on the treatment processes employed. The monitoring data shall be collected at a minimum frequency as established by the department.
6. The department may vary the reporting requirements on a case-by-case basis.
Editor's Note: Tables 570.1 through 570.14 are not further amended from the proposed regulation, therefore they are not published. View the tables as proposed at 36:6 VA.R. 475-845 November 11, 2019.
B. The owner shall report the following incidents within 24 hours to the department:
1. Water pressure below the 20 psi minimum required in the distribution system, including zero or negative pressure. Examples of these events include treatment plant or pump station shutdowns due to equipment failure, power outages, emptying of storage tanks, and draining of the distribution system during fire flow events.
2. Flooding of clearwells.
3. Flooding of groundwater wells.
4. Any other situation that occurs with the waterworks that presents or may present an imminent and substantial threat to public health.
Article 4
Cross Connection Control and Backflow Prevention in Waterworks
12VAC5-590-580. General requirements for cross-connection control and backflow prevention.
A. The purpose of this article is to require as a condition for the issuance and continued use of the operation permit for the waterworks that each owner of a waterworks Every owner shall establish and enforce a program of cross connection control and backflow prevention for each waterworks The cross connection control and backflow prevention program shall be approved by the division prior to issuance of the operation permit (see Appendix I). cross-connection control program (CCCP) in accordance with 12VAC5-590-360. The goal of the CCCP is to prevent the intrusion of contamination into the distribution system via cross-connections and backflow. [ The owner shall document the CCCP activities in a cross-connection control plan and submit the written document to the department for review and approval. ]
B. No owner shall install [ , maintain, ] or allow [ to be installed ] a service connection to any premises where cross-connections to a waterworks or a [ consumer consumer's ] water system exist, unless the [ owner and department ensure the ] cross-connections are adequately safeguarded [ to the satisfaction of the owner and the department ].
C. No owner shall install, maintain, or allow [ to be installed ] any connection whereby water from an auxiliary water system may enter a waterworks or [ consumer consumer's ] water system, unless the [ owner and department approve the ] auxiliary water system, the method of connection, and use of such system [ shall have been approved by the owner and the department ].
D. The owner, in accordance with 12VAC5-590-510 C, shall maintain acceptable working pressures in the distribution system to reduce the potential for backflow to occur.
12VAC5-590-590. Cross connections. (Repealed.)
A. The purveyor shall not install, maintain, or allow to be installed a water service connection to any premises where cross connections to a waterworks or a consumer's water system may exist unless such cross connections are abated or controlled to the satisfaction of the water purveyor or the division.
B. The purveyor shall not install, maintain, or allow to be installed any connection whereby water from an auxiliary water system may enter a waterworks or consumer's water system unless the auxiliary water system and the method of connection and use of such system shall have been approved by the water purveyor and by the division.
12VAC5-590-600. Responsibilities Cross-connection control program responsibilities.
A. General. Effective cross connection control requires the cooperation of the water purveyor, the building official, the consumer, the Virginia Department of Health, and the backflow prevention device tester.
B. Water purveyor.
1. The purveyor shall establish or cause to be established and operate a cross connection control and backflow prevention program The owner shall establish and [ operate implement ] a CCCP consistent with the extent of the distribution system and the [ type of consumer consumers ] served [ by the waterworks ]. [ The owner shall review the CCCP and written cross-connection control plan not less than every five years and update it as necessary to satisfy the requirements of this chapter. The owner shall submit updates to the department to obtain approval. The department may review the plan upon request. ] This program shall include at least one designated individual who shall be responsible for the inspection of the waterworks for cross connection and backflow prevention control. assigned by the owner. Requirements for this position shall include training and experience in cross-connection control programs. This program shall be carried out in accordance with the Uniform Statewide Building Code and shall be a continuing program.
2. Suggested elements of this program are contained in Appendix I. The purveyor has full responsibility for water quality and for the construction, maintenance, and operation of the waterworks beginning at the water source and ending at the service connection.
3. The purveyor shall have thorough inspections and operational tests made at least annually of backflow prevention devices which are required and installed at the service connection
4. In the event of backflow of pollution or contamination into the waterworks, the purveyor shall promptly take or cause corrective action, to confine and eliminate the pollution or contamination. The purveyor shall immediately notify the division when backflow occurs.
5. The purveyor shall take positive action to ensure that the waterworks is adequately protected at all times. If a cross connection exists or backflow occurs into a consumer's water system or if the pressure in the waterworks is lowered below 10 psi gauge, the purveyor may discontinue the water service to the consumer and water service shall not be restored until the deficiencies have been corrected or eliminated to the satisfaction of the purveyor.
B. The [ owner CCCP ] shall [ establish appropriate policies to complete assessments of consumer water system and shall determine both the degree of hazard and the appropriateness of existing safeguards not be in conflict with the USBC and applicable building code regulations, including 13VAC5-63 or subsequent regulations promulgated by the Board of Housing and Community Development ].
C. The [ owner CCCP ] shall [ establish procedures for completing operational tests or other evaluation procedures as appropriate at least annually and after installation, relocation, or repairs for testable backflow prevention assemblies, devices, and methods that provide containment ensure complete assessments of every consumer's water system and shall determine both the degree of hazard and the appropriateness of existing safeguards to prevent contamination from cross-connections and backflow ].
D. [ Instead of annual operational tests (12VAC5-590-600 C) and the related records and inventory of backflow prevention assemblies, backflow elimination methods, and backflow prevention devices (12VAC5-590-600 G), the owner may provide a public education program to residential and commercial consumers whose premise plumbing is not complex and where there are no known or suspected high hazards as identified in Table 630.1. For all other residential consumers, the department may approve a public education program provided by the owner as part of the CCCP The CCCP shall ensure testing, maintenance, and repairs of all backflow prevention assemblies, backflow elimination methods, and backflow prevention devices required and installed pursuant to 12VAC5-590-610 ].
1. The public education program shall be designed to prompt consumer self-assessments, increase the awareness of cross-connections, and inform the consumer of the public health hazards of backflow.
2. The public education program shall describe, at a minimum:
a. Causes of backflow;
b. Hazards and health effects of cross-connections and backflow;
c. Resources available to identify actual or potential cross-connections;
d. Safeguards to use to eliminate or reduce the hazards at the point of use; and
e. Sources for additional information. ]
E. [ The owner shall discontinue or refuse water service to the consumer to ensure that the waterworks is adequately protected from cross-connections and backflow if any of the following conditions occur:
1. A required backflow prevention assembly or backflow elimination method is not installed, tested, and maintained in accordance with the applicable sections of this chapter;
2. A required backflow prevention assembly or backflow elimination method is inoperable or has been removed or bypassed; or
3. An unprotected or inadequately protected cross-connection is known to exist on the premises and the owner has determined that there is inadequate backflow prevention at the service connection. 13VAC5-63-530, which incorporates the International Property Maintenance Code into the USBC, requires testing of RPZ assemblies, double check valve assemblies, double check detector backflow assemblies, and pressure vacuum breaker assemblies after initial installation, immediately after repairs or relocation, and annually thereafter. The CCCP shall establish procedures for completing and monitoring operational tests, or other evaluation procedures as appropriate, at least annually, and after installation, relocation, or repairs, for testable backflow prevention assemblies, devices, and methods that provide containment. The CCCP may include a public education program to:
1. Prompt consumer self-assessments, increase the awareness of cross-connections, and inform the consumer of the public health hazards of backflow.
2. The public education program, if provided as part of the CCCP, shall include, at a minimum, the following:
a. Causes of backflow;
b. Hazards and health effects of cross-connections and backflow;
c. Resources available to identify actual or potential cross-connections;
d. Safeguards to use to eliminate or control the hazards at the point of use; and
e. Sources for additional information. ]
F. [ In the event of backflow of contaminants into the waterworks, the owner shall promptly take or cause corrective action to confine and eliminate the contamination. The owner shall report the event to the department within one business day in the most expeditious manner. The owner shall submit a written report by the 10th day of the month following the month during which backflow occurred addressing the incident, its causes and effects, and safeguards required or other action taken The CCCP shall provide a method to discontinue or refuse water service to the consumer to ensure that the waterworks is adequately protected from cross-connections and backflow if any of the following conditions occur:
1. The consumer does not install, test and maintain a required backflow prevention assembly or backflow elimination method in accordance with the applicable sections of this chapter;
2. The consumer allows a required backflow prevention assembly or backflow elimination method to become inoperable or the consumer removes or bypasses it; or
3. The owner knows an unprotected or inadequately protected cross-connection exists on the premises and determines that there is inadequate backflow prevention at the service connection ].
G. [ The owner shall maintain an inventory and records of testing, repairs, and maintenance of all backflow prevention assemblies, backflow elimination methods, and backflow prevention devices required and installed under 12VAC5-590-610 In the event of backflow of contaminants into the waterworks, the owner shall promptly take or cause corrective action to confine and eliminate the contamination. The owner shall report the event to the department within one business day in the most expeditious manner. The owner shall submit a written report by the 10th day of the month following the month during which backflow occurred addressing the incident, its causes and effects, and safeguards required or other action taken ].
H. The owner shall maintain [ an inventory and ] records [ related to the CCCP implementation and other records required by the department in accordance with 12VAC5-590-550 of testing, repairs, and maintenance of all backflow prevention assemblies, backflow elimination methods, and backflow prevention devices required and installed under 12VAC5-590-610 C. In the case of single-family residences subject to 12VAC5-590-610 C 5, the owner may determine whether or not to maintain an inventory or records. The department recommends the owner follow best practices identified in the AWWA Manual of Water Supply Practices M14 and the EPA Cross-Connection Control Manual ].
[ I. The owner shall maintain an inventory and records of testing, repairs, and maintenance of all backflow prevention assemblies, backflow elimination methods, and backflow prevention devices required and installed under 12VAC5-590-610 E.
J. The owner shall maintain records related to the CCCP implementation, and any other records the department requires in accordance with 12VAC5-590-550. ]
12VAC5-590-610. Containment policy of backflow.
A. An approved backflow prevention device [ Backflow The owner shall ensure installation of backflow ] prevention assemblies or backflow elimination methods [ shall be installed ] (i) at each the service connection to a consumer's water system where, in the judgment of the water purveyor or the division, a health, pollution, or system hazard to the waterworks exists. B. When, as a matter of practicality, the backflow prevention device cannot be installed at the service connection, the device may be or (ii) [ located ] downstream of the service connection but prior to before any unprotected takeoffs.
B. Where the [ consumer consumer's ] water system is not intricate or complex and where actual or potential cross-connection hazards can be eliminated or [ reduced, controlled, instead of containment, the owner may allow consumers to use ] point-of-use isolation protection by application of appropriate backflow prevention assemblies, backflow prevention devices, or backflow elimination methods complying with the USBC. ] [ may be used instead of containment. ]
C. A backflow prevention device assembly or backflow elimination method shall be installed at each service connection to a consumer's water system serving premises where the following conditions exist:
1. Premises on which any A substance is handled in such a manner as to create an actual or potential hazard to a waterworks (this shall include premises having sources or systems containing process fluids or waters originating from a waterworks which are no longer under the control of the water purveyor) owner);
2. Premises having There exists internal cross connections cross-connections that, in the judgment of the water purveyor owner or the division department, may not be easily correctable or have intricate or complex plumbing arrangements which that make it impracticable to determine whether or not cross connections cross-connections exist;
3. Premises where, because of There are security requirements or other prohibitions or restrictions, it is impossible or impractical to make a complete cross connection survey that prevent the assessment of all potential cross-connections that may impair the quality of the water delivered;
4. Premises having There is a repeated history of cross connections cross-connections being established or reestablished;
5. Premises having fire protection systems utilizing combinations of sprinklers, fire loops, storage tanks, pumps, antifreeze protection, or auxiliary water sources including siamese connections (fire loops and sprinkler systems with openings not subject to flooding, and containing no antifreeze or other chemicals, no separate fire protection storage, or auxiliary sources, will not normally require backflow prevention); and 6. Other premises specified by the division or the purveyor when cause can be shown that a potential cross connection hazard not enumerated above exists There are fire protection systems, lawn sprinkler systems, or irrigation systems; [ or ]
6. [ Cause can be shown by the department or owner The owner or department can show ] that a potential cross-connection hazard exists.
D. Premises The owner shall ensure that [ consumers equip ] premises having booster pumps or fire pumps connected to the waterworks [ shall be equipped ] with a low pressure regulating or cutoff device to shut off the booster pump when the pressure in the waterworks drops to a minimum of 10 psi gauge control devices to prevent a reduction of pump suction line pressure to less than 20 psig.
E. An approved A backflow prevention device assembly or backflow elimination method shall be installed at each service connection to a consumer's water system serving, but not necessarily limited to, [ consumer water systems serving ] the following types of facilities, including:
1. Hospitals, mortuaries, clinics, veterinary establishments, nursing homes, and medical buildings;
2. Laboratories;
3. Piers, docks, and waterfront facilities;
4. Sewage treatment plants, sewage pumping stations, or storm water pumping stations;
5. Food and beverage processing plants;
6. Chemical plants, dyeing plants, and pharmaceutical plants;
7. Metal plating industries;
8. Petroleum or natural gas natural-gas processing or storage plants;
9. Radioactive materials processing plants or nuclear reactors;
10. Car washes and laundries;
11. Lawn sprinkler systems, and irrigation systems; 12. Fire service systems; Buildings with commercial, industrial, or institutional occupants served through a master meter;
12. Water loading facilities;
13. Slaughter houses and poultry processing plants;
14. Farms where the water is used for other than household purposes;
15. Commercial greenhouses and nurseries;
16. Health clubs with swimming pools, therapeutic baths, hot tubs, or saunas;
17. Paper and paper products paper-product plants and printing plants;
18. Pesticide or exterminating companies and their vehicles with storage or mixing tanks;
19. Facilities that blend, store, package, transport, or treat chemicals, and their related vehicles;
20. Schools or colleges with laboratory facilities;
20. Highrise buildings (four or more stories) 21. Multiuse commercial, office, or warehouse facilities; and 21. [ Multistory office and commercial buildings or both with four or more stories, including residential buildings classified by the USBC as commercial; and Highrise buildings (four or more stories); ]
22. [ Others specified by the ] purveyor [ owner or the ] division [ department when reasonable cause can be shown for a potential backflow or ] cross connection [ cross-connection hazard. Multiuse commercial, office or warehouse facilities; and
[ 23. Others specified by the owner or the department when reasonable cause can be shown for a potential backflow or cross-connection hazard. ]
F. All temporary or emergency service connections shall be protected where reasonable cause can be shown for a potential backflow or cross-connection hazard. Backflow prevention assemblies or backflow elimination methods used shall be appropriately certified or approved to match the requirements of this section.
12VAC5-590-620. Type of protection required. (Repealed.)
The type of protection required shall depend on the degree of hazard which exists or may exist and on the method of potential backflow. Backflow occurs either by back pressure or by back siphonage.
The degree of hazard, either high, moderate, or low, is based on the nature of the contaminant; the potential of the health hazard; the probability of the backflow occurrence; and the effect on waterworks structures, equipment, and appurtenances used in the storage, collection, purification, treatment, and distribution of pure water.
Table 2.10 shall be used as a guide to determine the degree of hazard for any situation.
A. Air gaps give the highest degree of protection and shall be used whenever practical to do so in high hazard situations subject to back pressure.
B. An air gap separation and a reduced pressure principle backflow prevention device will protect against back pressure when operating properly. Vacuum breakers will not protect against back pressure, but will protect against back-siphonage when operating properly.
C. Backflow prevention devices consisting of dual independent check valves with or without an intermediate atmospheric vent shall only be used in low hazard situations.
D. Barometric loops are not acceptable.
E. An interchangeable connection or change-over device has limitations which prevent its use where back pressure is present or may occur, the auxiliary supply is not an approved source, or the waterworks line pressure is less than 20 psi. Since this type connection is one of the easiest to bypass, the use of this type device will be approved only as a temporary and continuously supervised arrangement. In most instances, an approved device or method must be included and approved by the purveyor and division.
F. Reduced pressure principle type backflow preventers shall not be installed in pits or areas subject to flooding.
12VAC5-590-630. Backflow prevention assemblies, devices, and backflow elimination methods for containment.
A. Any backflow prevention assembly [ or device ] or backflow elimination method [ or backflow prevention device ] shall be of the approved type and shall comply with the Uniform Statewide Building Code USBC.
B. Any backflow prevention device shall be installed in a manner approved by the water purveyor and in accordance with the Uniform Statewide Building Code.
Editor's Note: Text stricken in 12VAC5-590-630 C in the proposed regulation has not been further amended, therefore it is not published. See proposed stricken text at 36:6 VA.R. 475-845 November 11, 2019.
B. General safeguards
1. The backflow prevention assembly [ or device or ] backflow elimination method [ or backflow elimination device ] used shall depend on the degree of hazard that exists or may exist. The safeguard shall ensure maintenance of the distribution system water quality and its usefulness.
2. The degree of hazard, either high or low, is based on (i) the nature of the contaminant; (ii) the potential of the health hazard; (iii) the potential method of backflow (either by backpressure or by backsiphonage); and (iv) the potential effect on waterworks structures, equipment, and appurtenances used in the storage, collection, purification, treatment, and distribution of potable water. Table 630.1 shall be used as a guide to determine the degree of hazard for any situation.
Table 630.1 Determination of Degree of Hazard
|
Cross-connections that meet or may meet the following conditions shall be rated at the corresponding degree of hazard.
|
High Hazard
|
Low Hazard
|
The contaminant would be toxic, poisonous, noxious, unhealthy, or of unknown quality.
|
The contaminant would only degrade the quality of the water aesthetically or impair the usefulness of the water.
|
A health hazard would exist.
|
A health hazard would not exist.
|
The contaminant would disrupt the service of piped water for human consumption.
|
The contaminant would not disrupt service of piped water for human consumption.
|
Backflow would be by either backpressure or backsiphonage.
|
Backflow would occur by backsiphonage.
|
Examples: [ lawn irrigation systems, fire sprinkler systems with chemical additives or antifreeze, ] sewage, used water, nonpotable water, auxiliary water systems, and mixtures of water and other liquids, gases, or other [ toxic or hazardous ] chemicals.
|
Examples: food residuals, [ nontoxic chemicals, and nonhazardous chemicals coffee machines, non-carbonated beverage dispensers, and residential fire sprinkler systems constructed of materials designed for potable water flow ].
|
3. The USBC and the [ manufacturer manufacturer's ] specifications shall be used to determine the appropriateness of the backflow prevention assembly or [ backflow prevention ] device application for containment.
C. [ Backflow Owners shall not allow the installation of backflow ] prevention devices or [ backflow prevention ] assemblies with openings, outlets, or vents that are designed to operate or open during backflow prevention [ shall not be installed ]:
1. In areas subject to flooding or in pits;
2. In areas with atmospheric conditions that represent a contamination threat to the potable water supply; and
3. In such a manner as to be able to be bypassed.
D. Starting January 1, [ 2022, 2023, ] persons testing and repairing backflow prevention assemblies and [ backflow prevention ] devices shall be certified by a Commonwealth of Virginia tradesman certification program (identified by DPOR as backflow prevention device workers). Until January 1, [ 2022, 2023, ] persons testing and repairing backflow prevention assemblies and [ backflow prevention ] devices shall be qualified to perform such work as demonstrated by possessing a certification or license from a local or state agency having legal authority or shall possess a certificate of completion of applicable vocational training acceptable to the owner.
Article 1
General
12VAC5-590-640. General design considerations.
A. Waterworks shall conform with to the Public Water Supply Law, Article 2 of Chapter 6 of Title 32.1 of the Code of Virginia. The engineer shall confer with the division before proceeding with the detailed designs. The engineering report and preliminary plan shall include plant site selection. Ordinarily, Community waterworks shall be designed to provide for the estimated population water demand for 10 to 30 years hence under predicted growth conditions. All waterworks shall be designed so that they can readily be increased in capacity except where circumstances preclude the probability of expansion. Expansion by modular steps should be considered. Operation and maintenance manuals are required for treatment facilities and pumping facilities.
B. Waterworks design shall be based on sound engineering practice substantiated in the engineer's design and approved by the [ commissioner department ]. Historical data or typical usage figures of waterworks with similar service area characteristics and appropriate peaking factors shall be used to support the design. USBC and design standards may be referenced for noncommunity waterworks, as appropriate.
1. Community waterworks shall be designed to meet or exceed the estimated maximum daily water demand of the service area at the design year. The design shall account for diurnal demand patterns and special demands placed on the waterworks such as firefighting, industrial use, and wholesale customers.
2. Noncommunity waterworks shall be designed to meet or exceed the peak hour demand of the proposed services. Either pump capacity or storage capacity or both may be utilized to meet the peak hour demand.
3. Effective storage.
a. Community waterworks shall provide sufficient finished water effective storage to enable the waterworks to meet the estimated maximum daily water demand at the design year. Compliance with this requirement is normally determined by the use of a hydraulic model. In the absence of a hydraulic model, effective storage shall be a minimum of one-half of estimated maximum daily water demand of the waterworks at the design year.
b. There is no minimum finished water effective storage requirement for noncommunity waterworks.
c. Effective storage of atmospheric storage tanks shall be the volume available to store finished water in atmospheric reservoirs or tanks, measured as the difference between the overflow elevation, or the normal maximum operating level, and the minimum storage elevation. For atmospheric tanks that use a portion of their volume to generate distribution system pressure, the minimum storage elevation is that elevation of water in the tank that can provide a minimum pressure of 20 psig throughout that tank's service area under distribution system-wide maximum daily water demand.
d. Effective storage of pressure storage tanks shall be one-third of the nominal pressure vessel storage capacity.
C. Waterworks shall be designed to provide a minimum residual pressure of 20 psig at all service connections. Design shall be based on the most restrictive conditions, defaulting to the greater of peak hour demand or maximum daily water demand plus applicable fire flows. Fire flow design values shall be identified by the engineer after coordination among the owner, local and state building officials, and fire officials. Distribution system hydraulic modeling may be used to demonstrate compliance with this requirement.
D. Materials used in the construction of waterworks that are in contact with the product water shall comply with [ NSF/ANSI Standard 61-2017 NSF/ANSI/CAN Standard 61-2020 ] or an approved equivalent.
12VAC5-590-650. Objectives of a waterworks. (Repealed.)
A. The objectives of a waterworks are:
1. The production of pure water; and
2. The production of water appealing to the consumer.
B. To reach the objectives of a waterworks, finished water quality shall conform with Article 1 of Part II of this chapter.
12VAC5-590-660. Site location.
A. Wells and water treatment plants shall be located above the projected 100 year flood-plain 100-year flood elevation. Lower elevations A lower elevation may be considered if it can be adequately shown that the wells or treatment plants can be protected from flooding. Site grading and adequate drainage shall be provided. Springs subject to flooding shall not be approved. See 12VAC5-590-840 E for additional well location requirements.
B. The waterworks pumping and treatment facilities shall be readily accessible in all seasons. Access roads shall be provided.
C. Consideration should be given to Functional aspects of the site shall be considered in design, including the convenience of transportation facilities to the plant site and also to the availability of electric power from more than one source of outside power.
12VAC5-590-670. Site size.
A. The area reserved around a well or spring site shall conform with 12VAC5-590-820, 12VAC5-590-830, and to 12VAC5-590-840 D and 12VAC5-590-840 E.
B. The treatment plant site shall be of ample size to accommodate expansion, and ample space shall be provided at the treatment site for adequate disposal handling of treatment plant wastes residuals.
C. The disposal of water treatment plant wastes residuals shall conform to the State Water Control Law, Chapter 3.1 of Title 62.1 of the Code of Virginia.
12VAC5-590-680. Treatment process selection and BAT.
A. The following shall be considered when selecting treatment processes to achieve treatment goals: (i) the quality and variability of the source water and (ii) possible future changes in the quality and quantity of the source water.
A. The quality and variability of the source water.
B. Possible future changes in the quality of the source.
C. Water quality goals, including the growing desire of the public for better water.
D. When removal of contaminants for which BAT has been specified is necessary, processes classified as BAT shall be employed.
E. When treatment technique requirements have been established in lieu of MCLs, processes specified by such requirements shall be employed.
F. POE or POU devices shall not be utilized for long-term compliance with PMCLs. Such devices may be considered for short term, interim use, as a condition of a variance or exemption issued by the commissioner.
B. The design shall employ best available technologies (BAT) for achieving compliance with the PMCLs for organic chemicals listed in 40 CFR 141.61 and BAT for achieving compliance with the PMCLs for inorganic chemicals listed in 40 CFR 141.62.
C. The design shall employ BAT for achieving compliance with the PMCLs for radionuclides listed in 40 CFR 141.66, including radium-226, radium-228, uranium, gross alpha particle activity, beta particle, and photon radioactivity. The design shall consider the system size and use limitations for specific technologies listed in 40 CFR 141.66.
D. Alternative technologies may be employed when approved by the [ commissioner department ].
E. When treatment technique requirements have been established instead of PMCLs or ALs, the design shall employ processes specified by these requirements.
F. POU devices shall not be used to achieve compliance with the treatment technique for microbial contaminants. POE or POU devices may be considered for short-term interim use when approved as a condition of a variance or exemption issued by the commissioner.
G. For softening, TDS removal, organics removal, and other treatment purposes, the use of RO and NF shall be in accordance with ANSI/AWWA Standard B114-16, or as allowed by the [ commissioner department ] on a case-by-case basis.
Editor's Note: Stricken 12VAC5-590-690 in the proposed regulation has not been further amended, therefore it is not published. See proposed stricken text at 36:6 VA.R. 475-845 November 11, 2019.
12VAC5-590-700. Metering total water production.
A. Waterworks providing chlorination only shall meter the water prior to treatment The design of all community waterworks shall provide metering of total water production.
B. Waterworks providing iron or manganese removal, or both, shall meter the water prior to treatment The design of all NTNCs that provide treatment or have a design capacity of greater than 300,000 gallons per month shall provide metering of total water production.
C. Waterworks providing softening by ion exchange, shall meter all water treated and total water delivered to the distribution system. D. Waterworks providing turbidity removal or softening by precipitation, or both, shall meter the water prior to and subsequent to treatment. The design of all TNCs that provide treatment or have a design capacity of greater than 300,000 gallons per month shall provide metering of total water production.
D. If the waterworks treatment process results in a waste flow, including filter backwash, ion exchange regenerate, or residual solids, then the design shall provide metering of total source water withdrawn and finished water produced.
E. All waterworks shall provide metering of total water production Metering of total water production at waterworks that do not meet the conditions found in subsections A through D of this section should be provided.
12VAC5-590-710. Site layout. (Repealed.)
A. Functional aspects of site layout shall be considered.
B. Site grading shall be provided.
C. Adequate site drainage shall be provided.
D. Walks shall be provided.
E. Access roads shall be provided.
F. Driveways shall be provided.
12VAC5-590-720. Building layout design and construction.
A. Adequate ventilation shall be provided.
B. Adequate lighting shall be provided.
C. Adequate heating shall be provided.
D. Adequate drainage shall be provided.
E. Adequate dehumidification equipment shall be provided.
F. Accessibility of equipment for operation, servicing, and removal shall be provided.
G. Flexibility of operation shall be provided.
H. Safety precautions shall be considered. Reference the applicable health and safety standards of the Virginia Department of Labor and Industry for the appropriate requirements.
I. Convenience of operation shall be considered.
J. Separate rooms for chemical storage and feed equipment to reduce dust problems shall be considered.
K. Sanitary facilities shall be provided at all waterworks installations requiring an operator in attendance at all times during operation.
A. In accordance with the USBC, Chapter 6 (§ 36.97 et seq.) of Title 36 of the Code of Virginia, and the Statewide Fire Prevention Code (§ 27.94 et seq.) of Title 27 of the Code of Virginia, all waterworks building design and construction shall include necessary features that will assure a functional and safe environment, including adequate ventilation, lighting, heating, drainage, dehumidification, and accessibility to equipment for operation and maintenance.
B. Consistent with subdivision A of this section, the waterworks building design and layout shall incorporate safety provisions to protect waterworks operators and other personnel, in accordance with Article 1 (§ 40.1-22) of Chapter 3 of Title 40.1 of the Code of Virginia. These provisions must comply with federal occupational safety and health standards and regulations promulgated under 29 USC § 651 et seq. and shall include separation of incompatible chemicals, confined space entry, handrails and guards, ladders, lighting, warning signs, smoke detectors, chlorine leak detectors, protective equipment, safety showers, eye washes, and fire extinguishers.
L. C. Positive identification of the contents of a piping system shall be by lettered legend giving the name of the contents. Arrows should shall be used to indicate the direction of flow. Legends shall be applied close to valves, adjacent to changes in direction and branches, where pipes pass through walls and floors, and at frequent intervals on straight pipe runs. The lettering shall be of such color, size, and location so as to be clearly visible and readable.
M. No conduit or basin containing filtered water shall have a common division wall with another conduit or basin D. Common division walls between basins or conduits containing nonpotable water and potable water are prohibited. Vertical double division walls, where separated sufficiently to permit ready access for inspection, are permissible where the division walls are monolithic in construction and are properly keyed into their footings or are cast monolithically with their footings.
E. Shop space and storage [ requirements facilities ] shall be provided.
F. Wherever pipes pass through walls of concrete structures, extra wall castings to facilitate expansion and future uses shall be provided.
12VAC5-590-725. Automated monitoring and control systems.
The design of computers, including supervisory control and data acquisition (SCADA) systems if used to monitor and control water treatment and distribution system facilities, shall meet the following general requirements:
1. Data security.
a. Automated systems used to display and record data or control functions that are connected to the internet shall be secure.
b. Backup power supply shall be provided to allow orderly shutdown of the computer system and prevent corruption of data. The protection shall also power associated communications equipment.
c. Adequate hardware shall be in place to allow a high degree of SCADA and computer system reliability and data security.
d. Adequate hardware and associated facilities shall be provided for data archiving.
2. Equipment protection. SCADA and computer systems shall have adequate protection from voltage surges and spikes on the power supply, external data links, and environmental conditions.
3. Data displaying and recording.
a. SCADA and computer systems used to meet the continuous recording requirements of this chapter shall record an observation on a minimum frequency of once per 15 minutes, unless a greater recording frequency is required.
b. SCADA and computer systems used to meet the indicating and recording requirements of this chapter shall provide displays that show a minimum 24-hour trend of results for each parameter. The display panel shall be located in an area where it can be routinely viewed by the waterworks operators.
c. SCADA and computer systems used to meet the indicating and recording requirements of this chapter shall monitor the values and provide alerts for the operator by visual display and audible alarms. Alarm conditions shall be recorded into an alarm log.
4. Waterworks pumps, chemical feeders, and other essential electrical equipment controlled through a SCADA or an automated control system shall have the capability for independent manual operation. Where a high degree of reliability is required, a backup control system shall be provided.
12VAC5-590-730. Standby power capability Alternate power sources.
Standby power capability may be required by the division so that water may be treated or pumped, or both, to the distribution system in order to maintain a minimum level of service during an emergency.
A. An emergency management plan for extended power outages shall be developed for each community waterworks as specified in 12VAC5-590-505.
B. Alternative power sources at all waterworks shall be considered in the design to maintain a minimum level of service during an electrical power outage.
12VAC5-590-740. Maintenance and servicing of equipment. (Repealed.)
Adequate facilities must be provided for the maintenance and servicing of automatic equipment.
12VAC5-590-750. Shop space and storage. (Repealed.)
Adequate facilities should be included for shop space and storage consistent with the designed facilities.
12VAC5-590-760. Laboratory facilities.
Laboratory equipment and facilities shall be compatible with the raw water source, intended design of the water treatment plant, and the complexity of the water treatment involved.
A. Testing equipment provided shall be adequate for the purpose intended and recognized procedures must be utilized The design of laboratory facilities shall be compatible with the equipment provided, the water supply, and the design and complexity of the water treatment.
B. Sufficient The design of community waterworks and NTNCs shall provide for adequate floor and bench space, adequate ventilation, adequate light, storage room, laboratory sink, and auxiliary facilities shall be provided. Office space is not included in the following specified laboratory sizes: adequate separation of incompatible activities, adequate environmental controls, and auxiliary facilities sufficient to carry out reliable testing.
1. Waterworks providing iron or manganese removal, or softening by ion exchange should provide a laboratory with a minimum of 64 square feet of floor area and 20 square feet of bench area.
2. Waterworks providing turbidity removal or softening by precipitation, or both, should provide a laboratory with a minimum of 200 square feet of floor area and 65 square feet of bench area.
3. Waterworks providing turbidity removal or softening by precipitation, or both, and in-plant bacteriological analysis should provide a laboratory with a minimum of 300 square feet of floor area and 100 square feet of bench area.
C. When a bacteriological laboratory is required a separate room of adequate space shall be provided. Certified analytical laboratory facilities analyzing drinking water shall comply with 1VAC30-41.
12VAC5-590-770. Sample taps Sampling and monitoring equipment.
A. Sample taps shall be provided so that water samples can be obtained from each water source water and each entry point to the distribution system. At waterworks providing treatment, sample taps shall be provided from each unit operation of treatment, with the taps being located at the master control sink in the laboratory. Taps shall be consistent with sampling needs and shall not be of the petcock type at the entrance and exit of each unit treatment process and at the entry point to the distribution system.
1. For surface water treatment plants, a master control sink shall monitor source water, chemically treated water, settled water, combined filter water, and at the entry point to the distribution system.
2. All sample taps shall discharge in the downward direction and be provided with a suitable air gap to prevent cross-connection.
B. Continuous monitoring instrumentation shall have electronic sensors that continuously read the parameter and shall display results in real time. Continuous recording equipment shall be provided with the monitoring instrument to store in memory or print one data point at least every 15 minutes. Each result shall be a single result at that time; if signal averaging is applied, the averaging period shall not exceed 30 seconds. The recording equipment shall be capable of producing a paper copy or equivalent electronic file showing daily trends, including maximum, minimum, and average values.
12VAC5-590-780. Wall castings. (Repealed.)
Consideration shall be given to providing extra wall castings built into the structure to facilitate expansion and future uses wherever pipes pass through walls of concrete structures.
12VAC5-590-790. Water supply service Process water.
The water supply service for treatment facilities shall be taken from a point after there has been thorough mixing of all chemicals added to the water Process water shall be taken from the finished water. An approved backflow prevention assembly or device shall be installed on the process water supply pipe before connection to the treatment process or equipment.
Editor's Note: Text stricken in 12VAC5-590-800 in the proposed regulation has not been further amended, therefore it is not published. See proposed stricken text at 36:6 VA.R. 475-845 November 11, 2019.
12VAC5-590-810. Paints, coatings, sealers, or liners Components, materials, and products.
Paints, coatings, sealers or liners which contact raw, partially treated, or potable water and are used in pipes, tanks, or equipment which can convey or store these waters shall be approved by the division before application All components, materials, and products that will be in contact with source water, partially treated water, finished water, or water treatment chemicals shall comply with [ NSF/ANSI Standard 61-2017 NSF/ANSI/CAN Standard 61-2020 ].
Article 2
Source Development
12VAC5-590-820. General New source water selection and sampling.
A. Preference shall be given to the best available sources of supply which that present minimal risks of contamination from wastewaters point and which nonpoint pollution sources that contain a minimum of impurities that may be hazardous to health and that give the greatest potential of ensuring a sufficient quantity of potable water.
B. In all cases, sources shall be selected and maintained on a basis which that will assure that the water is continuously amenable to available treatment processes. In selecting the source of water to be developed, the designing engineer must owner shall prove to the satisfaction of the [ commissioner department ] that the water which is to be delivered to the consumers shall comply with all applicable PMCLs of the board with respect to bacteriological, physical, chemical and radiological qualities to be delivered to the consumers will comply with 12VAC5-590-340.
C. All water samples for bacteriological, chemical, physical, and radiological analyses must shall be submitted to the Commonwealth of Virginia, Department of General Services, Division of Consolidated Laboratory Services DCLS or to a testing laboratory certified by the Division of Consolidated Laboratory Services DCLS. All bacteriological analyses must be performed at laboratories in accordance with analysis 12VAC5-590-370 A and 12VAC5-590-480 B 2 Analytical methods shall be in accordance with 12VAC5-590-440.
12VAC5-590-840. Groundwater sources.
A. A groundwater source includes all water obtained from drilled wells and springs. Wells and springs should shall be protected from contamination during construction. All public water supply wells intended to serve a waterworks shall be constructed by registered Virginia contractors a certified water well system provider. All wells shall be constructed in a manner to protect groundwater resources by preventing contaminated water or water having undesirable physical, chemical, or radiological characteristics from entering potable water aquifers.
B. All wells located within the Eastern Virginia or the Eastern Shore Groundwater Management Areas shall be constructed in a manner to protect groundwater resources by preventing blending or cross contamination of the aquifers.
1. Wells shall not be constructed with screens in multiple aquifers.
2. Geophysical logging and formation sampling shall be required for all wells during construction, in addition to submitting a Uniform Water Well Completion Report, Form GW-2.
3. Observation and production wells shall be constructed with gravel packs and grout in a manner that prevents movement between aquifers. Gravel pack shall be terminated close to the top of the well screens and shall not extend above the top of the screened aquifer. The remainder of the annular space shall be filled with grout material.
4. Pump intake setting shall be documented and the pump intake shall not be set below the top of a confined aquifer or the bottom of an unconfined aquifer that supplies water to the well.
C. All groundwater sources must be analyzed for chemical, physical, radiological, and bacteriological quality in order to determine treatment requirements as described in 12VAC5-590-840 K. Groundwater containing total coliform concentrations of less than 100 and more than three organisms per 100 milliliters based on the geometric mean of 20 or more samples shall be disinfected. Groundwater containing total coliform concentrations of 100 or more organisms per 100 milliliters based on the geometric mean of 20 or more samples constitutes unacceptable contamination for disinfection only. Groundwater with widely fluctuating or increasing bacteriological results may be determined by the division to be unsuitable for disinfection treatment alone.
The class of well to be constructed shall be determined by the division. All well lot, well location, and well construction requirements contained in this section may be varied by the division as specific geologic and site conditions dictate.
1. Minimum well lot D. Wells intended for use as a community waterworks shall be located on a well lot meeting the following minimum requirements:
a. 1. The well lot shall provide a distance of at least 50 feet from the well to all property lines of the well lot. Larger well lots may be required under certain conditions. Fencing of the well lot may be required under certain conditions;
2. The owner shall consider the need for a larger well lot for future expansion, the need to provide security measures such as lot fencing, and the need to establish additional well lots for future use;
b. 3. If the well lot does not adjoin a public road, then an all-weather access road shall be provided and an access easement recorded as part of the well lot;
c. 4. The well lot shall be graded to divert surface runoff away from the well and to prevent ponding on the well lot; and
d. 5. The well lot or lots must and access to the lot shall be located by a survey, and a final plat plan and dedication document prepared and recorded as described in 12VAC5-590-200. The final plat plan must agree with the preliminary plat plan with respect to size and boundaries of the lot or lots selected for well or wells. One of the following must be submitted:
(1) A copy of the plat plan showing that it has been duly recorded and signed by the clerk of the circuit court for the jurisdiction where the well is located and giving the deed book and page number and date of recording will be required before a construction permit can be issued or
(2) If the well lot is identified on a recorded plan of the subdivision as a well lot, then this is acceptable, if recorded as indicated in subdivision A 1 d (1) above; and
e. In addition, a dedication document duly recorded with the clerk of the circuit court must be furnished stating that the well lot shall be used only for waterworks appurtenances as long as this lot is utilized as part of a waterworks.
2. E. Minimum well location requirements:
a. 1. The horizontal distance from the well to any septic tank, purification field sanitary drainfield, pit privy, cesspool, barnyard, hog animal feed lot, cemetery, geothermal well or source of similar contamination, as well as and all surface runoff from such actual or potential sources of contamination, shall be at least 50 feet;.
b. 2. The horizontal distances from the well to any pipe carrying sewage or pipe in which sewage can back up shall be at least 50 feet; and.
c. The horizontal distance from the well to any petroleum or chemical storage tank or pipe line or similar source of contamination shall be at least 50 feet, except that where plastic type well casing is used, the separation distance shall be at least 100 feet. This 100-foot separation may be obtained by an enlarged well lot, easements, deed restrictions, or other equivalent legal means.
3. A minimum separation distance of 50 feet shall be maintained between a fuel storage tank and a well; however, a lesser distance may be allowed if the fuel is propane or natural gas, or if it is liquid fuel meeting the following requirements:
a. Liquid fuel tanks shall be located above grade.
b. Liquid fuel tanks shall be double-walled with an inner wall leak-detection alarm or single-walled with a full-capacity containment system constructed of compatible material.
c. Liquid fuel lines shall be located above grade or enclosed in a protective casing if below grade, and liquid fuel tanks shall be provided with a paved and curbed parking pad at the tank filling location.
4. The [ commissioner department ] shall require a spill response plan if the fuel is stored within 50 ft of the well.
F. The class of well to be constructed shall be determined by the [ commissioner department ]. A Uniform Water Well Completion Report, Form GW-2, shall be completed and submitted to the department with the project documents, in accordance with procedures in 12VAC5-590-200.
3. 1. Minimum construction requirements for Class I wells:
a. The well shall be drilled and cased to a depth sufficient to exclude undesirable groundwater, but in no case shall the casing this depth be less than 100 feet in depth; below finished grade.
b. The diameter of the drill hole to the depth required above shall be at least three inches greater than the outside diameter of the couplings of the casing to be used; and.
c. For wells constructed in consolidated formations, the lower end of the casing shall terminate in solid rock or other impervious formation when practical to do so.
c. d. The annular space around the casing shall be grouted to a depth of at least 100 feet in a manner satisfactory to the division [ commissioner department ]. When the outer casing cannot be removed, the annular spacing between the drill hole and the outer casing shall also be sealed in a manner approved by the division [ commissioner department ].
4. 2. Minimum construction requirements for Class II wells. This classification includes two types of construction, either of which is acceptable:
a. Type A wells in which the annular space around the casing is grouted a minimum of 20 feet from the surface:
(1) The well shall be drilled and cased to a depth of at least 100 feet; and
(2) The cased drill hole shall pass through at least the first 50 feet of unconsolidated formation such as caving sand, gravel or other material that will collapse against the casing;
b. Type B wells in which the annular space around the casing is grouted:
(1) a. The well shall be drilled and cased to a depth sufficient to exclude undesirable groundwater, but in no case shall the casing be less than 50 feet in length; this depth be less than 50 feet below finished grade.
(2) b. The diameter of the drill hole to the depth required above shall be at least three inches greater than the outside diameter of the couplings of the casing to be used;.
(3) The c. For wells constructed in consolidated formations, the lower end of the enlarged portion of the drill hole should terminate in solid rock or other impervious formation when practical to do so; and.
(4) d. The annular space around the casing shall be grouted to a depth of at least 50 feet in a manner satisfactory to the division [ commissioner department ]. When the outer casing cannot be removed, the annular spacing between the drill hole and the outer casing shall be sealed in a manner approved by the division [ commissioner department ].
B. General well development requirements: G. Well construction materials and development.
1. Water used in well construction shall be from a satisfactory potable water source or from the well under construction.
2. Casing and liner pipe:.
a. Shall be metallic pipe meeting ASTM, ANSI, AWWA or API Steel casing and liner pipe shall meet ASTM, [ NSF/ANSI NSF/ANSI/CAN ], or AWWA specifications and standards applicable to wells. Dimensions shall conform to the following table: Steel pipe dimensions shall conform to Table 840.1.
Editor's Note: Tables of 12VAC5-590-840 are not further amended from the proposed regulation, therefore they are not published. View the tables as proposed at 36:6 VA.R. 475-845 November 11, 2019.
b. Plastic pipes may be approved following investigation by the division. The casing shall be PVC type 1120 (cell identification 12454), NSF approved for well casings meeting appropriate ASTM, ANSI, AWWA or API specifications and used to depths in conformance with the information contained in the following tables: Plastic well casing shall be PVC meeting ASTM F480-14, [ NSF/ANSI Standard 61-2017, NSF/ANSI/CAN Standard 61-2020, ] or AWWA Standard [ A100-15 A100-20 ]. Depths shall not exceed the published resistance to hydraulic collapse pressure of the PVC casing, taking into account the installation techniques and grouting methods. Well casing wall thickness shall be sufficient to withstand anticipated formation and hydrostatic pressures and mechanical forces imposed during installation, well development, and use. PVC well casing shall meet the requirements of ASTM, [ NSF/ANSI NSF/ANSI/CAN ], and AWWA, as applicable.
c. Heavy weight Heavyweight casing pipe may be required under certain geologic and hydrostatic conditions: and.
d. Where corrosive conditions exist, materials such as coated casings, stainless steel, bronze, or plastic may be used as casings or linings subject to approval by the division [ commissioner department ], and meeting the requirements of [ NSF/ANSI Standard 61-2017 NSF/ANSI/CAN Standard 61-2020 ].
3. Packers or other well construction materials shall be of a material that will not impart taste, odors, toxic substances, or bacterial contamination to the water in the well. No lead is to be used in packers, flux, piping, etc.
4. Screens, where required, shall:
a. Be constructed of material which that will not be damaged by chemical action of groundwater or future cleaning operations;
b. Have size of openings to be based on sieve analysis of the formation to be screened, and should shall be adequate to pass flows at a velocity of 0.1 foot per second ft/sec or less; and
c. Be installed so that exposure above the pumping level will not occur.
5. A water well completion report shall:
a. Be submitted to the division, the State Water Control Board and the owner; and
b. Provide all data requested on the most recent well completion form.
6. The yield and drawdown test data over a 48-hour minimum period shall be provided; however, in those areas where geologic conditions warrant, the required test period may be varied by the division.
7. Chemical conditioning shall be included in specifications as to method, equipment, chemicals, testing for residual chemicals, disposal of waste, and inhibitors used.
8. 5. Grouting requirements.
a. Neat cement grout is normally required and shall consist of cement (API Spec. 10, Class G cement or Class B similar to ASTM C150 TYPE II) shall consist of Portland cement and water with not more than six gallons of water per 94-pound sack of cement, and shall be in place within 48 hours of well construction. A maximum of 6.0%, by weight, bentonite and 2.0%, by weight, calcium chloride, may be added. NOTE: When exceptional conditions require the use of a less fluid grout to bridge voids, a mixture of cement (ASTM C150 TYPE II), sand and water in the proportion of not more than two parts by weight of sand to one part of cement with not more than six gallons of clean water per 94 pound sack of cement may be used if approved by the division; Other grout mixes may be approved by the [ commissioner department ] where special conditions warrant.
b. Application.
(1) Grout shall be installed by means of continuous pressure grouting from the bottom of the annular opening upward in one continuous operation until the annular opening is filled.
(2) Sufficient annular opening shall be provided to permit a minimum of 1-1/2 inches of grout around the protective casing, including couplings, if used.
(3) Prior to Before grouting, bentonite, Aquagel, or similar approved materials may be added to the annular opening, in the manner indicated for grouting; and wells, suitable fill material such as bentonite, low-strength cement and sand mix, or similar materials that have been approved by the [ commissioner department ] shall be added to the annular opening below the grout zone to seal and stabilize these areas. Instead of this requirement, the casing may be grouted for its entire depth.
c. Protective casing Casing shall be provided with sufficient centralizers attached to the casing to permit allow unobstructed flow and uniform thickness of the grout.
9. Plumbness and alignment:
a. Every well shall be tested for plumbness and alignment;
b. The test method shall be clearly stated in specifications; and
c. Excessive kinks and bends shall not be acceptable.
d. Where plastic well casing is used, the heat of hydration of cement mixtures and the hydraulic collapse pressure of the casing shall be taken into consideration when choosing grout composition and placement in accordance with DEQ guidelines.
10. 6. To prevent tampering and contamination of the source water, unused wells shall be capped and locked. Watertight welded metal plates, set screw caps, or screw-on caps are acceptable for temporarily capping a well until the pumping equipment is installed.
H. A well yield and drawdown test shall be performed in accordance with requirements of this subsection. The [ commissioner department ] may require additional pumping wells, observation wells, or longer duration tests where site conditions warrant.
1. The yield and drawdown test duration shall be a minimum of 48 hours. Data to be collected during the yield and drawdown test shall be recorded on the Well Yield and Recovery Report form provided by the department. When the source water requirements for a noncommunity waterworks are determined to be three gpm or less over normal hours of operation, the 48-hour minimum drawdown test may be reduced to no less than 12 hours. Any reduction shall be approved by the [ commissioner department ] before conducting the test.
2. Discharge from the pumping well shall be conveyed away from the test site to avoid recharge.
3. Where multiple wells are intended to be used, the location and geology of each well in the vicinity shall be evaluated. The [ commissioner department ] shall require that:
a. The yield and drawdown test be performed simultaneously on the multiple wells, or
b. During the yield and drawdown test of the pumping well, the water levels of the neighboring wells shall be monitored. If the water level of the neighboring wells declines in response to the pumping well, then additional evaluation shall be required by a professional engineer or a professional geologist with experience in groundwater source evaluations.
4. The [ commissioner department ] may consider alternative testing methods and analyses as proposed by professional engineers or professional geologists with experience in groundwater source evaluations. Where geological conditions exist that prohibit an accurate determination of well yield using methods prescribed in this subsection, additional testing procedures shall be required on an individual basis and approved by the [ commissioner department ].
5. When an aquifer test is required by DEQ for a well located in a GWMA, the yield and drawdown test may be incorporated into the aquifer test plan protocol if approved by the [ commissioner department ] before conducting the test.
I. Well appurtenances.
1. A sanitary seal shall be provided on the top of the well casing, or a watertight well cap shall be provided when a pitless adapter is installed.
2. The well casing shall extend at least 12 inches above the concrete floor or apron.
3. Where aprons are used, they shall be centered on the well and measure at least six feet by six feet by six inches thick.
4. Provisions shall be made for venting the well casing to the atmosphere. Where vertical turbine pumps are used, vents into the side of the casing may be necessary to provide adequate venting.
5. Each well casing shall be provided with equipment and appurtenances for measuring the water level elevation in the well. Corrosion-resistant materials shall be used. Where necessary, the appurtenances shall be attached firmly to the drop pipe or pump column and in a manner as to prevent entrance of foreign materials.
6. All pitless well units, adapters, and watertight caps shall be listed by the Water Systems Council as certified products, or as approved by the [ commissioner department ].
J. Every new, modified, or reconditioned groundwater well or spring shall be disinfected after placement of the final pumping equipment. Wells shall be disinfected in accordance with AWWA Standard C654-13.
K. Water quality tests. Water quality sampling and analysis shall be conducted for every new, modified, or reconditioned well or spring to determine what treatment, if any, is required. All samples shall be analyzed by DCLS or a testing laboratory certified by DCLS. Water quality analytical methods shall conform to requirements contained in 12VAC5-590-440.
11. 1. Bacteriological quality:.
a. Every new, modified, or reconditioned groundwater source shall be disinfected after placement of the final pumping equipment; and
b. A series of nine consecutive negative samples for bacteriological examination or a series of 20 or more samples for most probable number (MPN) examination is required.
12. Samples for chemical, physical and radiological analyses shall be submitted on every new, modified, or reconditioned well. The sample must be collected near the end of the pumping test and after the well water has cleared.
a. Bacteriological samples for new or deepened wells shall consist of a series of 20 samples collected at a minimum of 30-minute intervals during the last 10 hours of the yield and drawdown test. These samples shall be analyzed for both total coliform density and E. coli density. See 12VAC5-590-380 G for groundwater disinfection treatment requirements, and see 12VAC5-590-430 for surface water influence determinations.
b. Bacteriological samples for modified or reconditioned wells shall consist of two samples collected at least 30 minutes apart, at a minimum, while the pump is in continuous operation. These samples shall be analyzed for both total coliform density and E. coli density. More samples may be required by the [ commissioner department ] , depending on the work performed.
2. Samples for new wells shall be collected for chemical, physical, and radiological contaminants listed in Tables 340.1 through 340.4. SOC tests may be waived by the [ commissioner department ] if supported by the source water assessment of vulnerability to contamination. Chemical sampling analysis for a TNC may be limited to nitrate and nitrite only. Samples shall be collected at the end of the yield and drawdown test and after the well water has shown no further change in the clarity of the water. Chemical, physical, and radiological constituent testing for modified or reconditioned wells shall be determined on an individual basis by the [ commissioner department ].
13. L. Observation wells:
a. 1. Shall be constructed in accordance with the requirements for permanent wells if they are to remain in service after completion of the groundwater study; and of DEQ if they are constructed in a GWMA. Otherwise, they shall be constructed in accordance with [ 12VAC5-590-630. 12VAC5-630-420 ] if they are to remain in service as observation wells after completion of the groundwater study.
b. 2. Shall be protected at the upper terminal to preclude the entrance of contamination.
14. Well abandonment:
a. Observation wells and groundwater sources which are not in use shall be sealed by methods which will restore the controlling geological conditions which existed before they were constructed;
b. Temporary abandonment.
(1) Any water well temporarily removed from service, or completed but not put into service, shall be sealed with a watertight cap or well-head seal.
(2) Such well shall be so maintained that it will not be a source or channel of contamination during temporary abandonment; and
c. Permanent abandonment.
(1) All casing and screen materials may be salvaged.
(2) The well shall be checked from land surface to the entire depth of the well before it is plugged to ascertain freedom from obstructions that may interfere with plugging (sealing) operations.
(3) The well shall be thoroughly chlorinated prior to plugging (sealing).
(4) Bored wells shall be completely filled with cement grout or dry clay compacted in place.
(5) Wells constructed in unconsolidated formations shall be completely filled with cement grout or clay slurry by introduction through a pipe initially extending to the bottom of the well. Such pipe shall be raised, but remain submerged in grout, as the well is filled.
(6) Wells constructed in consolidated rock formations or which penetrate zones of consolidated rock may be filled with sand or gravel opposite the zones of consolidated rock. The top of the sand or gravel fill shall be at least five feet below the top of the consolidated rock. The remainder of the well shall be filled with sand-cement grout only.
15. M. Sealing of select zones. All zones containing water of undesirable quality or zones to be protected but excluded from final well completion shall be grouted from a point at least five feet above the zone to a point at least five feet below the zone.
C. Special requirements for various groundwater sources:
1. N. Gravel packed wells:
a. 1. The gravel utilized shall be free of foreign material, properly sized, washed, and then disinfected prior to before or during placement;.
b. 2. The gravel refill pipes, when used, shall be incorporated within the pump foundation or concrete apron and terminated with screwed or welded caps at least 12 inches above the pumphouse pump house floor or concrete apron;.
c. Gravel 3. The gravel refill pipes in the grouted annular opening shall be surrounded by a minimum of 1-1/2 inches of grout.
d. Means 4. A means for the prevention of leakage of grout into the gravel pack of the screen shall be provided; and.
e. 5. The minimum protective casing and grouted depth shall be acceptable to the division [ commissioner department ].
6. Wells located in a GWMA shall have gravel packing installed in accordance with 12VAC5-590-840 B 3.
2. O. Radial water collectors will collector systems shall be considered on an individual basis by the division [ commissioner department ].
3. Multiple aquifer wells. The annular space between producing aquifers should be grouted to prevent the mixing of waters of different qualities (see subdivision B 15). An approved bentonite material specifically manufactured as a grout may be considered.
4. P. Flowing artesian wells located outside a GWMA will be considered on an individual basis by the division an individual basis by the [ commissioner department ].
5. Springs:
a. Springs may be considered only when it is not possible to develop an acceptable well or other source;
b. Springs may be approved only after an extensive sanitary survey and bacteriological, turbidity, chemical, and flow data over a time period sufficient to establish year-round quality and quantity. The amount of land required for protection of the spring shall be determined by the division on a case-by-case basis;
c. Springs shall be considered as surface water sources if they are influenced by surface conditions. Indicators of such influence include turbidity, bacteriological, and chemical quality that varies with surface conditions;
d. Springs shall be protected from entry of surface water;
e. Springs shall be housed in a permanent structure; and
f. Springs shall be continuously chlorinated.
1. The well shall be equipped with a pitless adapter specifically designed for pressurized artesian wells.
2. Special well construction, casing, and sealing may need to be considered for flowing artesian wells.
Q. Capacity determination of wells used for community waterworks shall meet the daily water demand.
1. Capacity of wells located in consolidated rock formations shall be determined by the well sustainable yield, and the actual installed (production) well pump capacity, whichever value is less. The sustainable yield shall be calculated as follows:
(A x 1440 min/day) / 1.8 = gpd well sustainable yield, where A = well yield (gpm) determined by the yield and drawdown test conducted in accordance with 12VAC5-590-840 H.
2. Capacity of wells located in unconsolidated formations shall be determined by the well yield and the actual installed (production) well pump capacity, whichever value is less.
R. Waterworks serving 50 or more residential connections employing only wells providing the source water shall include at least two wells. If only two wells are provided, then the second well shall be rated for at least 30% of the waterworks permit capacity.
S. The owner of a waterworks serving fewer than 50 residential connections with a single well providing the source water shall provide or have ready access to a replacement pump and other components and materials needed for pump replacement. Instead of this requirement, the owner may provide 48 hours of total finished water storage volume based on the maximum daily water demand.
T. Springs.
1. The water quality of spring sources shall be established by obtaining samples over a period of time agreeable to the [ commissioner department ] to assess the bacteriological, physical, chemical, and radiological characteristics.
2. Springs shall be housed in a permanent structure and protected from entry of surface water.
3. The amount of land required for protection of the spring source shall be determined by the owner and approved by the [ commissioner department ].
4. The design of spring sources shall provide for continuous disinfection.
5. The capacity of spring sources shall be determined using actual flow data.
a. Sufficient daily flow data shall be collected to conduct a frequency distribution analysis. The capacity of a spring source is defined as the low flow rate for one day with a projected recurrence period of 30 years (i.e., 30-year, one-day low flow).
b. The Log-Pearson Type III method of frequency distribution analysis shall be used to make the determination, with a minimum of 1,000 daily flow measurements.
c. If sufficient data is not available to conduct the analysis specified in this subsection, then the lowest recorded daily flow rate may be considered to be the spring capacity. Sufficient flow records shall be available to capture the spring flow during drought conditions, and shall be acceptable to the [ commissioner department ].
Article 3
Processes and Devices
12VAC5-590-850. General Appropriate treatment.
A. The design of water treatment processes and devices facilities shall depend upon the evaluation of the nature and quality of the particular source water to be treated and the desired required quality of the finished water as set forth in Article 1 of Part II, Drinking Water Standards, and Article 2 of Part III, Source Development. All surface water shall receive treatment by chemical addition, for coagulation, flocculation, clarification, filtration, and disinfection unless otherwise approved by the division. Some types of treatment processes may require presedimentation. Operation and maintenance manuals are required. Treatment process selection shall follow the requirements of 12VAC5-590-680.
B. The design of water treatment facilities shall address safety considerations as required in 12VAC5-590-560.
12VAC5-590-860. Chemical application.
Only chemicals authorized in the construction permit or subsequently authorized by the division and in compliance with National Sanitation Foundation Standards 60 and 61 shall be used to treat drinking water or as an additive to drinking water.
A. Plans and specifications shall be submitted for review evaluation and approval, as provided for required in Part I [ (12VAC5-590-10 et seq.) (12VAC5-590-200 through 12VAC5-590-220) ], and shall include:
1. Descriptions of feed equipment, including maximum and minimum feed ranges;
2. Location of feeders, piping layout, and points of application;
3. Storage Chemical storage and handling facilities;
4. Specifications for chemicals to be used;
5. Operating and control procedures features; and
6. Descriptions of testing equipment and procedures.
B. Chemicals shall be applied to the water at such points and by such means as to:
1. Assure maximum efficiency of treatment;
2. Provide maximum protection to the consumer;
3. Provide maximum safety to operators;
4. Assure satisfactory mixing of the chemicals with the water;
5. Provide maximum flexibility of operation through various points of application, when appropriate;
6. Prevent backflow or back-siphonage backsiphonage between multiple points of feed through common manifolds; and
7. Provide for the application of pH-affecting chemicals to the raw source water prior to before the addition of the coagulant in turbidity removal processes.
C. Feed equipment.
1. Where chemical feed is necessary for the treatment of the supply source water, such as chlorination, coagulation, or other essential processes: a. A minimum of two feeders shall be provided; and b. A standby unit or combination of units of sufficient capacity, a standby feeder or combination of feeders shall be available to replace provide the required chemical dose with the largest unit during shutdowns feeder out of service.
2. Feeders shall be of such design and capacity to meet the following requirements:
a. Feeders shall be able to supply at all times the necessary amounts of chemical at an accurate rate throughout the range of feed; at all times.
b. Proportioning of chemical feed to the rate of flow shall be provided where the water flow is not constant; or where specifically required by the [ commissioner department ].
c. Positive displacement type solution feed pumps, or gravity feed through rotometers rotameters, shall be used to feed liquid chemicals, but should not normally be used to feed chemical slurries; and.
d. Chemical solutions shall be prevented from being siphoned into the water supply by:
(1) Providing vacuum relief,
(2) Providing a suitable air gap, or
(3) Other approved devices or piping arrangements;
e. The service water supply shall be protected from contamination by chemical solutions by:
(1) Equipping the supply line with backflow or back-siphonage prevention devices or
(2) Providing an air gap between supply line and solution tank;
f. d. Chemical contact materials and surfaces shall be resistant to the aggressiveness of the chemical solution;.
g. e. Dry chemical feeders shall:
(1) Measure chemicals volumetrically or gravimetrically;
(2) Provide effective solution of the chemical in the solution pot;
(3) Preferably provide Provide gravity feed from solution pots; and
(4) Completely enclose chemicals to prevent emission of dust to the operation room;.
h. f. No direct connection may shall exist between any sewer and a drain or overflow from the feeder or solution chamber or tank; and.
i. g. A separate chemical waste tank should be considered.
3. Chemical feed equipment:
a. Shall be located near points of application to minimize length of feed lines;
b. Shall be readily accessible for servicing and repair, and observation of operation; and
c. Shall be located and within a protective curbings provided curbing so that chemicals resulting from equipment failure, spillage, or accidental drainage shall not enter the water in conduits or treatment or storage basins.
4. Control:.
a. Feeders may shall be manually or automatically controlled capable of both manual and automatic control with the automatic control reverting to manual control as necessary;
b. The feeders Feeders shall be manually started following shutdown, unless otherwise approved by the division [ commissioner department ]; and
c. Automatic chemical dose or controls with residual analyzers may be approved for use and shall provide alarms for critical values, and shall include indicating and recording charts equipment.
5. Solution tanks. All solution tanks shall be manufactured of materials suitable as a for food contact surface: or that meet the requirements of 12VAC5-590-810.
a. Means shall be provided to maintain uniform strength of solution, consistent with the nature of the chemical solution. Continuous agitation is necessary shall be provided to maintain slurries in suspension;.
b. Two solution tanks of specific capacity may be required for a chemical to assure continuity of chemical application during servicing; Solution tanks shall be of sufficient number and capacity to assure continuous chemical application during tank servicing, and the access openings shall be curbed and fitted with tight covers.
c. Each tank exceeding 30 gallons in capacity or fixed in place shall be provided with a drain unless other means of dewatering the tank are provided.
(1) No direct Direct connection between any tank or drain and a sewer shall be permitted is prohibited.
(2) All drains shall terminate at least two pipe diameters, but not less than two inches, above the rim of the receiving sump, conduit, or waste receptacle;.
d. Means shall be provided to indicate the solution level in the tank;.
e. Make-up Process water shall enter the tank above the rim at a distance of two pipe diameters but not less than two inches;.
f. Chemical solutions shall be kept covered.
(1) Polyphosphate solutions shall be disinfected by carrying a chlorine residual when added to unchlorinated water.
(2) Large tanks with access openings shall have such openings curbed and fitted with tight covers;
g. Subsurface locations for Buried or subsurface chemical storage or solution tanks shall: are prohibited.
(1) Be free from sources of possible contamination;
(2) Assure positive drainage for groundwaters, accumulated water, chemical spills, and overflows; and
h. Overflow pipes, when provided, shall:
(1) Be turned downward, with end screened and when located outside, be provided with an appropriately sized screened end to prevent entry of insects and small animals;
(2) Have free discharge;
(3) Be located where noticeable; and
(4) Be directed so as not to contaminate the water or be a hazard to operating personnel.
6. Weighing scales.
a. Shall be provided for weighing cylinders at all water treatment plants utilizing chlorine gas; for large water treatment plants, indicating and recording type are desirable;
b. Shall be required for fluoride solution provided for fluorosilicic acid feed systems in conjunction with a loss of weight loss-of-weight recorder;
c. Should be required Shall be considered for volumetric dry chemical feeders; and
d. Shall be accurate to measure increments of 0.5% of load.
7. Feed lines.
a. Shall be as short as possible in length of run and be:
(1) Of durable, corrosion resistant corrosion-resistant material;
(2) Easily accessible throughout the entire length;
(3) Protected against freezing; and
(4) Readily cleanable.;
b. Shall slope upward from chemical source to feeder, when conveying gases;.
c. Shall introduce corrosive chemicals in such a manner as to minimize potential for corrosion;.
d. Shall be designed consistent with scale forming solids depositing properties of the water, chemical solution, or mixture conveyed;.
e. Shall not carry chlorine gas beyond the chlorine feeder room unless the chlorine is under vacuum; and.
f. Shall be designed so that liquid alum does not mix with water prior to before the point of application.
8. Service water supply: Process water.
a. Water used for dissolving dry chemicals, diluting liquid chemicals, or operating chemical feeders shall be:
(1) Only from From a safe, approved source;
(2) Protected from contamination by appropriate means;
(3) Ample in supply and adequate in pressure;
(4) Provided with means for measurement when preparing specific solution concentrations by dilution; and
(5) Properly treated for hardness when necessary.
b. Where a booster pump is required, duplicate equipment a spare pump shall be provided and, when necessary, standby power.
c. Backflow prevention shall be achieved by appropriate means such as:
(1) An air gap between the fill pipe and overflow rim of the solution or dissolving tank, and equivalent to two pipe diameters but not less than two inches;
(2) An approved reduced pressure zone backflow preventer, consistent with the degree of hazard, aggressiveness of chemical solution, back pressure sustained, location, and available means for maintaining and testing the device; or
(3) A satisfactory vacuum relief device.
D. Chemicals.
1. Quality.a. Chemical containers shall be fully labeled to include:
(1) Chemical name, purity and concentration;
(2) Supplier name and address;
(3) Precautions in handling; and
(4) Requirements of Virginia Department of Labor and Industry, Virginia Occupational Safety and Health Standards for General Industry, section 1910.1200(f).
b. Chemicals shall meet American Water Works Association standards, where applicable, and be stamped or certified accordingly.
c. Provisions may be required for assay of the chemicals delivered where the quality is in doubt.
d. Chemicals having a distinguishing color may be used, providing the coloring material is not toxic in concentrations used and will not impart taste, odor, or color to the water supply.
2. 1. Storage.
a. Space shall be provided where at least 30 days of chemical supply can be stored in dry storage conditions, based on the average dose and average annual water treatment plant flow rate. Storage shall be at a location that is convenient for efficient handling unless local suppliers and safety. Lesser storage capacity may be approved if the owner can demonstrate that the local suppliers or other conditions indicate lesser storage is adequate will provide an uninterrupted source of chemicals.
b. Cylinders of chlorine gas shall be:
(1) Isolated from operating areas;
(2) Restrained in position to prevent upset; and
(3) Stored in rooms separate from ammonia storage.
c. Liquid chemical storage tanks shall:
(1) Have a liquid level indicator; and
(2) Have an overflow and a receiving basin or drain capable of receiving accidental spills or overflows.
d. Special precautions shall be taken with: (1) Sodium sodium chlorite, to eliminate any danger of explosion; and.
(2) e. Activated carbon, which is a potentially combustible material, requiring isolated, fireproof storage and explosion proof electrical outlets, lights, and motors in areas of dry handling. The following special precautions shall be taken in areas where activated carbon is stored, handled, and fed.
(1) Isolated, cool, and dry areas free from sources of ignition shall be provided for activated carbon storage;
(2) Electrical equipment, devices, and materials shall comply with applicable codes;
(3) Ventilation in areas associated with the storage, handling, and feeding of activated carbon shall be localized so as not to cause dust or material to be drawn into other areas; and
(4) Activated carbon shall not be stored with strong oxidants such as ozone, liquid chlorine (i.e., compressed chlorine gas), and permanganate.
e. f. Chemicals shall be stored in covered or unopened shipping containers, unless the chemical is transferred into an approved covered storage unit.
f. g. Solution storage or day tanks supplying feeders directly should have sufficient capacity for one day of operation.
g. h. Acid storage tanks shall be vented to the outside atmosphere, but not through vents in common with day tanks.
3. 2. Handling.
a. Provisions shall be made for measuring quantities of chemicals used to prepare feed solutions.
b. Storage tanks and pipelines for liquid chemicals shall be specific to the chemicals and not for alternates.
c. Chemicals that are incompatible shall not be fed, stored, or handled together.
d. Provisions shall be made for the proper transfer of dry chemicals from shipping containers to storage bins or hoppers in such a way as to minimize to mitigate the quantity of dust which that may enter the room in which the equipment is installed. Control shall be provided by use of:
(1) Vacuum pneumatic equipment or closed conveyor systems;
(2) Facilities for emptying shipping containers in special enclosures; or
(3) Exhaust fans and dust filters which that put the hoppers or bins under negative pressure.
e. Precautions shall be taken with electrical equipment to prevent explosions, particularly in the use of sodium chlorite and activated carbon and other hazards.
f. Acids shall:
(1) Be kept in closed, acid resistant acid-resistant shipping containers or storage units; and
(2) Not be handled in open vessels, but should be pumped in undiluted form from original containers, through a suitable hose, to the point of treatment or to a covered day tank.
g. Carts, elevators, and other appropriate means shall be provided for lifting chemical containers to minimize mitigate excessive lifting by operators.
h. Provisions shall be made for disposing of empty containers by an approved procedure which that will minimize mitigate exposure to the chemical.
E. Housing.
1. Structures, rooms, and areas accommodating chemical feed equipment shall provide convenient access for servicing, repair, and observation of operation.
2. Floor surfaces shall be smooth and impervious, slip-proof, and well drained with a slope of %u215B inch per foot, minimum.
3. Open basins, tanks, and conduits shall be protected from chemical spills or accidental drainage.
F. Operator safety. Safety provisions shall protect people at the waterworks from chemical exposures in accordance with VOSH laws and regulations.
1. Gases from feeders, storage, and equipment exhausts shall be conveyed to the outside atmosphere, above grade, and remote from air intakes.
2. See 12VAC5-590-1000 and 12VAC5-590-1001 for special provisions for handling and storing chlorine.
3. A plastic bottle of hydrochloric acid (muriatic acid in commercial form) shall be available for ammonia leak detection where ammonia gas is used or stored.
4. At least one pair of rubber gloves with long gauntlets, a dust respirator of a type approved by the Virginia Occupational Safety and Health Standards for General Industry, Section 1910.134 that complies with VOSH laws and regulations for toxic dusts, and an apron or other protective clothing shall be provided for each operator in any shift who will handle dry chemicals.
5. Rubber gloves, clothing protection, and goggles shall be provided for each operator preparing chemical solutions.
6. 5. Facilities such as emergency eye wash and showers shall be provided for washing of the face, gloves, and protective equipment.
7. See 12VAC5-590-1000 E.
12VAC5-590-865. Conventional filtration treatment.
A. Conventional filtration treatment is generally used for surface water sources. It is defined as a series of four processes: coagulation, flocculation, sedimentation, and filtration. The specific design parameters shall consider the water supply characteristics and variability in quality due to seasonal and climatic events.
B. Conventional filtration treatment plants shall provide staged, multiple treatment process units to allow individual units to be taken out of service without disrupting operation.
C. The [ commissioner department ] may require presedimentation of waters containing high turbidity or organics (as measured by TOC).
1. Presedimentation basins utilizing a coagulant feed shall have hoppered bottoms or shall be provided with continuous sludge removal equipment. The minimum hydraulic detention time shall be three hours. The [ commissioner department ] may require greater detention times depending on the source water quality and the level of pretreatment required.
2. Presedimentation basins without coagulant feed shall provide a minimum hydraulic detention time of 24 hours. The design shall address future needs for solids removal and handling.
3. Incoming water shall be dispersed across the full width of the line of travel as quickly as possible. Short circuiting shall be minimized. The [ commissioner department ] may require baffling on large basins.
4. Provisions for bypassing presedimentation basins shall be provided.
5. Surface runoff shall be prevented from entering presedimentation basins or reservoirs.
6. Dikes shall be structurally sound and protected against wind action and erosion.
12VAC5-590-870. Mixing and sedimentation. (Repealed.)
A. Plants designed for processing surface waters shall:
1. Provide multiple units for coagulation, flocculation, and sedimentation at plants having a rated capacity greater than 100 gallons per minute;
2. Permit operation of flocculation basins in series or parallel;
3. Be constructed to permit units to be taken out of service without disrupting operation; and
4. Provide multiple stage treatment facilities when required by the division.
B. Water containing high turbidity or coliform organisms may require pretreatment, usually sedimentation, either with or without the addition of chemicals. When pretreatment is used, the following requirements must be met:
1. Presedimentation basins utilizing a coagulant shall have hoppered bottoms or shall be equipped with continuous sludge removal apparatus;
2. Incoming water shall be dispersed across the full width of the line of travel as quickly as possible; short circuiting must be prevented;
3. Provisions for bypassing sedimentation basins shall be included; and
4. Three hours detention is the minimum period required. Greater detention may be required depending on raw water quality.
C. Flash mixing is the rapid dispersion of chemicals throughout the water to be treated, usually by violent agitation, to enhance coagulation.
1. Turbidity removal plants other than those of the solids contact type shall provide flash mixing facilities.
2. Basins shall be equipped with mechanical mixing devices; other arrangements, such as baffling, may be acceptable only under special conditions. Where mechanical mixing devices are utilized, duplicate units or spare mixing equipment shall be provided.
3. Design parameters:
a. The detention period shall not be less than 10 seconds;
b. The design of the flash mixing unit should be based upon the mean temporal velocity gradient G (expressed as units of seconds1). Typical values for G and T are:
|
T (seconds)
|
G (seconds1)
|
|
20
|
1,000
|
|
30
|
900
|
|
40
|
700
|
|
Longer time
|
790
|
For optimization, the engineer should determine the appropriate G value and detention time through experimentation;
c. The point of application of the coagulant shall be at the point of maximum mixing intensity;
d. The physical configuration of the mixing basin shall be designed to eliminate vortexing; and
e. Flash mix units should be designed to allow speed variation throughout at a range of one to three.
4. Properly designed static mixers may be utilized.
D. Flocculation mixing is the agitation of treated water at low velocity gradients for sufficient time to agglomerate coagulated particles.
1. Basin inlet and outlet design shall prevent short circuiting and destruction of floc. A drain and overflow shall be provided. Multiple units shall be provided for continuous operability and each basin shall be designed so that individual basins may be isolated without disrupting plant operation.
2. Design parameters:
a. The minimum detention time shall be 30 minutes;
b. The design of the flocculation units shall be based upon the value of GT (mean temporal velocity gradient in seconds¹) X (detention time in seconds) which is ordinarily in the range of 20,000 to 200,000. The engineer should establish the value of GT through experimentation;
c. Variable speed drive units shall be designed to provide speed variations throughout a range of four to one;
d. To control short circuiting in mechanical flocculators, at least three successive compartments should be provided. In addition, special attention should be given to the ports between compartments to further suppress short circuiting;
e. To accomplish maximum power input and reduce particle shearing, tapered flocculation should be provided;
f. In basins utilizing vertical shaft flocculators, wing walls, or stators shall be provided to prevent vortexing; and
g. The flocculation basins must be so designed that individual basins may be isolated without disrupting plant operation.
3. Flocculation and sedimentation basins shall be as close together as possible. The velocity gradient of the flocculated water through pipes or conduits to settling basins shall not be greater than the velocity gradient utilized in flocculating the water. Where velocity gradient is not used as a design parameter, the linear velocity in pipes and conduits from the flocculators to the settling basin shall not exceed 0.5 feet per second. Allowances must be made to minimize turbulence at bends and changes in direction.
4. Baffling may be used to provide for flocculation in small plants only after consultation with the division. The design should be such that the velocity gradients noted above may be maintained. Turbidity removal plants other than solids contact shall provide flocculation basins.
5. Safety. Guard rails and adequate lighting shall be provided.
E. Sedimentation shall follow flocculation/mixing. The detention time for effective clarification is dependent upon a number of factors relating to basin design and the nature of the raw water. The number of basins required is dependent upon the plant size, turbidity, color, colloidal matter, and taste and odor causing compounds to be removed.
1. Plants utilizing rapid rate gravity filters in conjunction with conventional sedimentation shall provide a minimum of four hours effective settling (detention) time. Effective settling time shall be calculated using the volume of the basins from the stilling wall to the submerged effluent orifice or weir.
2. Inlets shall be designed to distribute the water equally and at uniform velocities. Open ports, submerged ports, stilling walls, and similar entrance arrangements are required. Where stilling walls are not provided, a baffle shall be constructed across the basin close to the inlet and shall project several feet below the water surface to dissipate inlet velocities and provide uniform flows across the basin.
3. Outlet devices shall be designed to maintain velocities suitable for settling in the basin and to minimize short circuiting. The use of submerged orifices or submerged weirs is required. The maximum velocity gradient in pipes and conduits from the settling basins to the filters shall not exceed that used in flocculation. Where velocity gradient is not used as a parameter the linear velocity in pipes and conduits from settling basins shall not exceed 1.0 foot per second.
4. Rectangular sedimentation basins should be designed with a length to width ratio of at least four to one. Surface overflow rates should be within the range of 0.25 to 0.38 gallons per minute per square foot in processes utilizing flocculation, the lower limit being utilized for cold waters and the higher limit being applied to warm waters.
5. The circular clarifiers of the center feed, peripheral feed, and spiral flow type will be considered on an individual basis.
6. Basins shall be provided with a means for dewatering. Basin bottoms shall slope toward the drain not less than one foot in twelve feet unless mechanical sludge collection equipment is provided.
7. Superstructures are acceptable at specific plant locations where necessary. In areas where settling basins are subject to high and frequent cross winds, consideration should be given to the provision of windbreaks.
8. The velocity through settling basins shall not exceed 1.0 foot per minute. The basins shall be designed to minimize short circuiting. Baffles shall be provided as necessary to minimize short circuiting.
9. An overflow weir (or pipe) shall be installed which will establish the maximum water level desired on top of the filters. It shall discharge with a free fall at a location where the discharge will be noted.
10. Permanent ladders or handholds shall be provided for safety on the inside walls of basins above the water level. Guard rails shall be included. Flushing lines or hydrants shall not include interconnection of the potable water with nonpotable water.
11. For plants having a capacity of 100 gallons per minute or more, multiple basins are required and shall be so designed that individual basins may be isolated without disrupting plant operation.
12. Mechanical sludge collecting equipment shall be considered for all plants with a capacity of 100 gallons per minute or more.
13. Facilities are required by the State Water Control Board for disposal of sludge (see 12VAC5-590-990). Provision shall be made for the operator to observe or sample sludge being withdrawn from unit.
F. Units that combine softening and clarification are acceptable where water characteristics are not variable and flow rates are uniform. Before solids contact units are considered as clarifiers without softening, specific approval of the division shall be obtained. Clarifiers shall be designed for the maximum uniform rate and shall be adjustable to changes in flow which are less than the design rate and for changes in water characteristics. A minimum of two units is required.
1. A representative of the manufacturer shall supervise the installation and initial operation of each unit.
2. The following equipment shall be provided for plant operation.
a. Complete outfit of tools and accessories; and
b. Adequate piping with suitable sampling taps so located as to permit the collection of samples of water from critical portions of the units.
3. Chemical feed requirements are those listed in 12VAC5-590-860.
4. Mixing devices shall be constructed to:
a. Provide good mixing of the raw water with previously formed sludge particles; and
b. Prevent deposition of solids in the mixing zone.
5. Flocculation equipment:
a. Shall be adjustable;
b. Shall insure that coagulation occurs in a separate chamber or baffled zone within the unit; and
c. Shall provide a flocculation and mixing period of at least 30 minutes.
6. The sludge equipment shall provide either internal or external sludge concentrators in order to obtain a concentrated sludge with a minimum of waste water.
7. Sludge removal design shall provide that:
a. Sludge pipes shall be not less than three inches in diameter and so arranged as to facilitate cleaning;
b. Entrance to sludge withdrawal piping will prevent clogging;
c. Valves are located outside the tank for accessibility;
d. The operator may observe or sample sludge being withdrawn from the unit; and
e. A timeclock with proportional timer shall be provided for automatic blowoff.
8. Cross connections:
a. Blowoff outlets and drains shall terminate and discharge at a place satisfactory to the division; and
b. Cross connection control shall be included for the potable water mains used to backflush sludge lines.
9. The detention time shall be established on basis of the raw water characteristics and other local conditions that affect the operation of the unit. Based on design flow rates, the minimum detention time shall be:
a. Two hours for suspended solids contact clarifiers; and
b. One hour for the suspended solids contact softeners.
10. Softening units should be designed so that continuous slurry concentrates of 1.0% or more, by weight, can be satisfactorily maintained.
11. Water losses:
a. Solids contact units shall be provided with suitable controls for sludge withdrawal;
b. Total water losses should not exceed:
(1) Five percent for clarifiers; and
(2) Three percent for softening units; and
c. The solids concentration of sludges bled to waste should be:
(1) Three percent by weight for clarifiers,
(2) Five percent by weight for softeners.
12. Units used as clarifiers should be equipped with orifices. Units used for softening should be equipped with either overflow weirs or orifices. Weirs shall be:
a. Adjustable;
b. At least equivalent in length to the perimeter of the tank; and
c. Constructed so that surface water does not travel over 10 feet horizontally to the collection trough.
13. Weir loading:
a. Weir loading shall not exceed 20 gallons per minute per foot of weir length for units used as softeners; and
b. Orifices shall produce uniform rising rates over the entire area of the tank and shall provide for an exit velocity not to exceed 1.0 foot per second.
14. Upflow rates shall not:
a. Exceed 1.75 gpm/ft2 of area at the slurry separation line for units used as softeners; or
b. Exceed 1.0 gpm/ft2 of area at the sludge separation line for units used as clarifiers.
15. Consideration shall be given to providing a superstructure to enclose the solids contact unit, to enhance the treatment process, and for the protection of piping and associated sampling valves.
12VAC5-590-871. Coagulation and flocculation.
A. Rapid mixing is the rapid dispersion of chemicals throughout the water to be treated, usually by violent agitation, to promote coagulation.
1. Rapid mix basins or inline static mixers shall be provided.
2. Basins shall be equipped with mechanical mixing devices. Other arrangements, such as baffling, may be acceptable under special conditions and only when approved by the [ commissioner department ]. Where mechanical mixing devices are utilized, duplicate units or spare mixing equipment shall be provided.
3. Rapid mix basins with mechanical mixers should be based upon the mean temporal velocity gradient "G" (expressed as units of seconds-1). The owner's engineer shall submit the basis for the selected velocity gradient considering the chemicals to be added and water temperature. Typical values for G and T are:
TABLE 871.1
Rapid Mix Basin GT Values
|
T (seconds)
|
G (seconds-1)
|
20
|
1,000
|
30
|
900
|
40
|
700
|
60
|
600
|
a. The point of application of the coagulant shall be at the point of maximum mixing intensity;
b. The physical configuration of the mixing basin shall be designed to eliminate vortexing; and
c. Mechanical mixers should be designed to allow speed variation with a highest speed of at least three times the lowest speed.
B. Flocculation mixing is the agitation of treated water at low velocity gradients for sufficient time to agglomerate coagulated particles.
1. Basin inlet and outlet design shall prevent short circuiting and destruction of floc. A drain and overflow shall be provided. Multiple units shall be provided for continuous operability, and each basin shall be designed so that individual basins may be isolated without disrupting plant operation. Basins shall be arranged to allow for either series or parallel operation.
2. Design parameters:
a. The minimum detention time shall be 30 minutes for water treatment plants employing rapid rate gravity filters, and 20 minutes for water treatment plants using high rate gravity filters. Basin flow-through velocity should not be less than 0.5 ft/min or greater than 1.5 ft/min.
b. The design of the flocculation units shall be based upon the value of GT, which is ordinarily in the range of 20,000 to 200,000. The owner's engineer should establish the value of GT through experimentation.
c. Agitators shall be driven by variable speed drive units with peripheral tip speed of the paddles ranging from 0.5 to 3.0 ft/sec.
d. To control short circuiting in mechanical flocculators, at least three successive compartments should be provided. In addition, special attention should be given to the ports between compartments to further suppress short circuiting.
e. To accomplish maximum power input and reduce particle shearing, tapered flocculation should be provided.
f. In basins utilizing vertical shaft flocculators, wing walls, or stators shall be provided to prevent vortexing.
3. Flocculation and sedimentation basins shall be as close together as possible. The velocity gradient of the flocculated water through pipes or conduits to settling basins shall not be greater than the velocity gradient utilized in flocculating the water. Where velocity gradient is not used as a design parameter, the linear velocity in pipes and conduits from the flocculators to the settling basin shall not exceed 0.5 ft/sec unless otherwise approved by the [ commissioner department ]. Allowances shall be made to minimize turbulence at bends and changes in direction.
4. Baffling may be used for flocculation in small water treatment plants only when approved by the [ commissioner department ]. The design should allow the velocity gradients noted in subdivision B 3 of this subsection to be maintained.
12VAC5-590-872. Sedimentation.
A. The water treatment plant capacity, source water quality, and filtration process used shall be considered in determining the number and design of sedimentation basins.
B. The minimum settling time shall be four hours for water treatment plants employing rapid rate gravity filters, and a minimum of three hours for water treatment plants using high rate gravity filters. Reduced settling times may be approved by the [ commissioner department ] where effective settling is demonstrated. Effective settling time shall be calculated using the volume of the basins from the stilling wall to the submerged effluent orifice or weir, including the volume under launders or finger weirs.
C. Inlets shall be designed to distribute the water equally and at uniform velocities. Open ports, submerged ports, stilling walls, and similar entrance arrangements are required. Port velocities should be in the range of 0.5 to 1.5 ft/sec. Where stilling walls are not provided, a baffle shall be constructed across the basin close to the inlet and shall project several feet below the water surface to dissipate inlet velocities and provide uniform flows across the basin.
D. Outlet weirs or submerged orifices shall be designed to maintain settling velocities in the basin and minimize short circuiting. Outlet weirs and submerged orifices shall be designed as follows:
1. The rate of flow over the outlet weir shall not exceed 20,000 gpd/ft of the outlet launder.
2. Submerged orifices shall not be located lower than three feet below the normal water surface.
3. The entrance velocity through the submerged orifices shall not exceed 0.5 ft/sec.
E. The linear velocity in pipes and conduits from settling basins shall not exceed 1.0 ft/sec.
F. Rectangular sedimentation basins shall be designed with a length-to-width ratio of at least 4:1.
G. Surface overflow rates shall be within the range of 0.25 to 0.38 gpm/ft2 in water treatment plants using rapid rate filters, and a maximum of 0.5 gpm/ft2 for water treatment plants using high rate filters. Increased surface overflow rates and reduced settling times may be approved by the [ commissioner department ] where effective settling is demonstrated. The length and area between launders and finger weirs may be included in determining length-to-width ratio and overflow rates.
H. Basins shall be provided with a means for dewatering. Basin bottoms shall slope toward the drain not less than one foot in 12 feet unless mechanical sludge collection equipment is provided.
I. In areas where settling basins are subject to high and frequent cross winds, windbreaks shall be considered. Covers or enclosures shall be considered in locations subject to freezing.
J. The velocity through settling basins shall not exceed 1.0 ft/min. The basins shall be designed to minimize short circuiting. Baffles shall be provided as necessary to minimize short circuiting.
K. Multiple basins shall be provided for continuous operability, and each basin shall be designed so that individual basins may be isolated without disrupting plant operation.
L. Mechanical sludge collecting equipment shall be considered for all plants.
M. Sedimentation basins with tube or plate settlers shall meet the following design requirements:
1. Inlet and outlets shall be designed to maintain velocities suitable for settling in the basin and minimize short circuiting. Plate units shall be designed to ensure even flow distribution across the units.
2. Drain piping from the settler units shall be sized to facilitate a quick flush of the basin and to prevent flooding other portions of the plant.
3. Where units are located outdoors, adequate freeboard shall be provided above the top of the settlers to prevent freezing.
4. The maximum loading for tube settlers shall be two gpm/ft2 of cross-sectional area unless higher rates are demonstrated through pilot plant or in-plant demonstration studies.
5. The maximum loading for plate settlers shall be 0.5 gpm/ft2 based upon 80% of the projected horizontal plate area.
6. Flushing lines shall be provided to facilitate maintenance and shall be properly protected against backflow or backsiphonage.
12VAC5-590-873. Solids contact treatment units.
A. Solids contact units shall be acceptable for combined flocculation and clarification where source water characteristics are not variable and flow rates are uniform. When approved, these units shall be designed for the maximum uniform rate and shall be adjustable to changes in flow that are less than the design rate and for changes in water characteristics.
B. A minimum of two units shall be provided.
C. A rapid mix device designed in accordance with 12VAC5-590-871 A shall be provided. Mixing devices shall be constructed to:
1. Provide good mixing of the source water with previously formed sludge particles; and
2. Prevent deposition of solids in the mixing zone.
D. Flocculation equipment designed in accordance with 12VAC5-590-871 B shall:
1. Be equipped with an adjustable drive mechanism;
2. Ensure that coagulation occurs in a separate chamber or baffled zone within the unit; and
3. Provide a flocculation period of at least 20 minutes.
E. The sludge equipment shall provide either internal or external sludge concentrators in order to obtain a concentrated sludge with a minimum of waste water. Sludge removal systems shall provide:
1. Sludge pipe sizes of not less than three inches in diameter;
2. Piping arrangements to prevent clogging and to facilitate cleaning;
3. Valves that are located outside the tank for accessibility;
4. A means to observe or sample sludge being withdrawn from the unit;
5. A time clock with proportional timer with automatic blowoff; and
6. Suitable controls for sludge withdrawal.
F. Cross-connections.
1. Blowoff outlets and drains shall terminate and discharge at a place satisfactory to the [ commissioner department ]; and
2. Cross-connection control shall be included for the potable water mains used to flush sludge lines.
G. The detention time shall be established on the basis of the source water characteristics and other local conditions that affect the operation of the unit. The minimum detention time shall be two hours for suspended solids contact clarifiers.
H. Orifices shall produce uniform rising rates over the entire area of the tank and shall provide for an exit velocity not to exceed 1.0 ft/sec.
I. Upflow rates shall not exceed 1.0 gpm/ft² of area at the sludge separation line.
12VAC5-590-874. Gravity filtration.
A. At least two gravity filter units shall be provided in conventional filtration treatment plants and direct filtration treatment plants.
B. Filter loading rates shall not exceed 2.0 gpm/ft2 of filter area for rapid rate filters and shall not exceed 4.0 gpm/ft2 for high rate filters, during normal operation. Alternative loading rates may be approved by the [ commissioner department ] when effective filtration is demonstrated.
C. The filter structure shall be so designed as to comply with the following:
1. The walls within the filter shall be vertical;
2. The filter walls shall not protrude into the filter media;
3. There shall be no common wall between filtered or finished water and any lesser quality water;
4. The filter shall be covered by a superstructure if determined necessary under local climatic conditions;
5. There shall be head room to allow normal inspection and operation;
6. A curb at least four inches high shall surround each filter to prevent floor drainage into the filter;
7. The maximum velocity gradient of treated water in pipes and conduits to the filters shall not exceed that used in flocculation. Where velocity gradient is not used as a design parameter, the linear velocity in pipes and conduits from settling basins to filters shall not exceed 1.0 ft/sec;
8. Influent pipes or conduits, where solids loading is heavy, shall be straight and equipped with cleanouts;
9. Backwash water drain capacity shall be sufficient to carry the maximum flow;
10. Access in the form of walkways not less than 24 inches in width shall be provided to each filter; and
11. The normal operating water surface on a filter shall be at the same hydraulic grade level as the sedimentation basin, if no intermediate treatment process is provided.
D. Backwash water troughs shall be so designed as to provide:
1. Bottom elevation of the trough above the maximum level of expanded media during backwashing;
2. At least a two-inch freeboard inside the trough at the maximum rate of wash;
3. A level top or edge;
4. Spacing so that each trough serves an equal area of each filter; and
5. Maximum horizontal travel of suspended particles to reach the trough not to exceed 3.0 ft.
E. Filter media shall be free from detrimental chemical or bacterial contaminants. Acceptable filter media shall include anthracite coal, silica sand, garnet sand, and GAC. Other natural or synthetic media may be approved by the [ commissioner department ] when pilot-scale or full-scale demonstration studies demonstrate that the media is capable of meeting the filter effluent turbidity treatment technique requirements in Part II [ (12VAC5-590-340 et seq.) (12VAC5-590-395) ] of this chapter.
1. Filters may be of single media, dual media, or multimedia design depending upon the water to be treated and the specific filtration process employed. A total media depth of not less than 27 inches shall be provided after cleaning and scraping.
2. Types of filter media:
a. Anthracite coal. A sieve analysis shall be provided. Anthracite media shall have:
(1) An effective size from 0.45 to 0.55 mm with a uniformity coefficient not greater than 1.65 when used alone.
(2) An effective size from 0.8 to 1.2 mm with a uniformity coefficient not greater than 1.85 when used in dual or multimedia filters.
b. Silica sand. A sieve analysis shall be provided. The media shall be clean silica sand having an effective size from 0.35 to 0.55 mm and a uniformity coefficient not greater than 1.65.
c. Garnet sand. A sieve analysis shall be provided. The media shall have an effective size from 0.15 to 0.35 mm.
d. Granular activated carbon (GAC) may be used as a media for filtration. The [ commissioner department ] may require pilot studies where precursor or organics removal is a treatment objective. The design shall include the following:
(1) GAC media shall meet the basic specifications for filter media contained in this section, except the uniformity coefficient shall not be greater than 2.0. The [ commissioner department ] may allow larger size media based upon pilot-scale or full-scale demonstration testing. The [ commissioner department ] may require that a layer of sand media be placed below the GAC.
(2) Provisions shall be made for periodic treatment of GAC filter material for the control of bacteria and other growths.
(3) Provisions shall be made for GAC media replacement or regeneration.
(4) Only materials suitable for use with GAC media filters shall be utilized.
F. Support media.
1. Sand. A sieve analysis shall be provided. A three-inch layer of sand shall be used as a supporting media for the filter media where supporting gravel is used and shall have an effective size from 0.8 to 2.0 mm and a uniformity coefficient not greater than 1.7.
2. Gravel. When used as the supporting media, gravel shall consist of hard, rounded particles and shall not include flat or elongated particles. The coarsest gravel shall be 2-1/2 inches in size when the gravel rests directly on the strainer system and shall extend above the top of the perforated laterals or strainer nozzles. Not less than four layers of gravel shall be provided in accordance with the size and depth distribution specified in Table 874.1.
3. Changes of gravel depths and sizes may be considered by the [ commissioner department ] where proprietary filter bottoms are proposed.
TABLE 874.1 Gravity Filter Gravel Support Bed
|
SIZE
|
DEPTH
|
2-1/2 - 1-1/2 inches
|
5 - 8 inches
|
1-1/2 - 3/4 inches
|
3 - 5 inches
|
3/4 - 1/2 inches
|
3 - 5 inches
|
1/2 - 3/16 inches
|
2 - 3 inches
|
3/16 - 3/32 inches
|
2 - 3 inches
|
G. Filter bottoms and strainer systems. The [ commissioner department ] may allow deviations from requirements of this subdivision for high rate filters and for proprietary filter bottoms. Porous plate bottoms shall not be used where iron, manganese, or hard water may result in clogging. The design of manifold-type collection systems shall:
1. Minimize loss of head in the manifold and laterals;
2. Assure even distribution of backwash water and an even rate of filtration over the entire area of the filter;
3. Provide a ratio of the area of the final openings of the strainer systems to the area of the filter of about 0.003;
4. Provide a total cross-sectional area of the laterals at about twice the total area at the final openings; and
5. Provide a manifold that has a cross-sectional area which is 1-1/2 to two times the total area of the laterals.
H. Surface wash or air scouring of filters shall be provided.
1. All rotary surface wash devices shall be designed with:
a. Provisions for water pressures of at least 45 psig;
b. A vacuum breaker or other device or assembly to prevent backsiphonage; and
c. Adequate surface wash water to provide 0.5 - 1.0 gpm/ft2 of filter area.
2. Air scouring shall provide for:
a. An air flow rate of three to five scfm/ft2 of filter area when air is introduced in the underdrain. A lower air flow rate shall be used when the air scour distribution system is placed above the underdrain.
b. A method for avoiding loss of filter media during backwashing.
c. A fluidization backwash following air scour sufficient to restratify the filter media. The backwash water delivery system shall be in accordance with this section except the rate of flow should not exceed 8.0 gpm/ft2 unless operating experience demonstrates that a higher rate is necessary to remove scoured particles from the filter media.
I. Turbidity monitoring.
1. Indicating and recording turbidimeters meeting the requirements of 12VAC5-590-770 B shall be provided for:
a. The source water;
b. The settled water from each sedimentation basin;
c. The filter effluent from each filter; and
d. The CFE.
2. Finished water indicating and recording turbidimeters shall be considered if chemical pH adjustment occurs following filtration.
3. The location of the turbidity sample tap shall allow turbidity to be monitored for both the filtered water and the filter-to-waste water.
4. The design may incorporate an operator selected filter effluent high turbidity alarm.
J. Appurtenances.
1. A sampling tap shall be placed between each filter and the effluent rate-of-flow controller to sample filtered water and filter-to-waste water. The location of sample taps shall allow turbidity to be monitored of both the filtered water and the filter-to-waste water.
2. Indicating and recording loss-of-head gauges shall be provided on all filters having a capacity of greater than 100 gpm. An indicating loss-of-head gauge shall be provided on all filters having a capacity of 100 gpm or less.
3. Indicating and recording rate-of-flow gauges shall be provided on all filters having a capacity of greater than 100 gpm. An indicating and totalizing water meter may be used instead of an indicating and recording gauge on filters having a capacity of 100 gpm or less.
4. Effluent rate-of-flow controllers of the direct acting, indirect acting, or constant rate types shall be provided on each filter.
a. All control devices used shall incorporate an auxiliary shutoff valve in the filter effluent line. Indirect and direct acting effluent rate-of-flow control devices shall start operation from the closed position. Failure of indirect acting controllers shall not result in any increase in the rate of flow.
b. Filter effluent rate-of-flow control that simply maintains a constant water level on the filter is prohibited.
c. Control devices shall be configured to prevent exceeding the design filter hydraulic loading rate when any filter is taken out of service.
5. Provisions for draining the filter-to-waste (rewash) with appropriate backflow prevention and rate control shall be provided on each filter. The filter-to-waste design flow rate shall be equal to the filtration rate.
6. A high pressure hose and hose rack shall be provided to allow washing down filter walls.
K. Backwash provisions.
1. Filtered or finished water shall be applied uniformly across the filter in an upflow direction to provide at least 50% media expansion during all operating conditions. This will normally require backwash flow rates of up to 20 gpm/ft2 depending on media size, media specific gravity, uniformity coefficient, and water temperature.
2. The backwash water shall be provided at the required rate by backwash pumps, backwash water tanks, the high service main, or a combination of these methods. Consideration should be given to including provisions to obtain backwash water from the distribution system or other sources and to supply backwash water during plant start-up or during catastrophic events.
3. At least two backwash water pumps shall be installed unless an alternate means of obtaining backwash water is available.
4. The volume of backwash water provided shall be sufficient to backwash one filter at the design backwash flow rate and duration during the warmest water temperature. This backwash water volume shall be in addition to any other water storage requirements.
5. A backwash water controller or valve shall be provided on the main backwash water supply line to obtain the desired rate of filter wash with the backwash water valves on the individual filters open wide.
6. Consideration shall be given to provide for seasonal adjustments of the backwash flow rate to ensure proper backwashing while preventing media loss and to conserve water.
7. The rate-of-flow indicator on the main backwash water supply line shall be located so that it may easily be read by the operator during the backwashing process.
8. Where backwash water pumps are provided, a means for air release shall be installed between the backwash water pump and the backwash water valve.
L. Other design considerations.
1. Roof drains shall not discharge into the filter or basins and conduits preceding the filters.
2. Provision shall be made for continuous operation of all other filtering units while one filtering unit is out of operation.
3. High rate filtration shall be provided with precise coagulation control. A multiple six-gang stirring machine for performing jar tests shall be provided in addition to one or more of the following means of controlling the coagulation process:
a. Zeta potential, as measured by microelectrophoresis.
b. Pilot filters. Where dual pilot filters are used, two units shall be provided. Each pilot filter shall consist of a small filter (about six inches in diameter) containing the same type and depth of media as the plant filters. The pilot filter shall be equipped with recording turbidimeters on the effluent to measure the filterability of the water as reflected by turbidity monitoring.
c. Streaming current monitor, defined as a continuous sampling instrument that measures the electric current generated when water flows past suspended particles contained in the water.
4. High rate filtration shall be provided with indicating and recording pH monitoring equipment for:
a. The source water;
b. The rapid mix effluent; and
c. The finished water leaving the treatment plant.
12VAC5-590-875. Direct filtration.
A. Direct filtration is defined as a series of treatment processes, including coagulation and filtration but excluding sedimentation. Direct filtration shall be considered only for treatment of high quality and seasonally consistent surface water sources or GUDI sources.
B. An in-plant demonstration study or pilot study shall be required to demonstrate acceptable performance of direct filtration. The study shall be conducted over a sufficient time to treat all expected source water conditions throughout the year. The pilot plant filter shall be of a similar type and operated in the same manner as proposed for full-scale operation.
C. The department may require presedimentation meeting the requirements of 12VAC5-590-865 C to be provided [ prior (in the treatment sequence) ] to direct filtration treatment plants.
D. Rapid mix coagulation and flocculation shall be provided, meeting the requirements of 12VAC5-590-871.
E. Filters shall be dual media or multimedia gravity filters. Design of filtration units shall meet requirements for rapid rate or high rate gravity filters in 12VAC5-590-874, including filter structure, filter media, support gravel, backwash provisions, rate-of-flow control, surface wash, or air scour. Alternative designs may be considered by the department.
F. Turbidity monitoring.
1. Indicating and recording turbidimeters meeting the requirements of 12VAC5-590-770 B shall be provided for:
a. The source water;
b. The filter effluent from each filter; and
c. The CFE.
2. Finished water indicating and recording turbidimeters shall be considered if chemical softening occurs following filtration.
G. Where automatic unit process control is provided, manual override of all automatic features shall be provided.
1. Automatic start-up of treatment plant unit processes is prohibited.
2. Valve actuators shall be provided with manual override capability.
H. The plant design should allow for the future installation of sedimentation basins.
12VAC5-590-880. Filtration Diatomaceous earth filtration.
A. Rapid rate gravity filters acceptable for the treatment of water from surface water sources or groundwater sources under the direct influence of surface water.
1. Pretreatment is required where rapid rate gravity filters are utilized. Pretreatment shall include but not be limited to disinfection, coagulation, flocculation, and sedimentation.
2. At least two filtering units shall be provided at plants having a rated capacity of more than 100 gpm and less than 2 MGD. The total number of filters necessary at plants having a rated capacity equal to or greater than 2 MGD may be estimated utilizing the following formula:
N = 2.7 (Q)0.5
(Formula as per Morrell and Wallace from Hardenbergh and Rodie's "WATER SUPPLY AND WASTE DISPOSAL 1960").
Where N equals number of filter units and Q equals plant capacity in million gallons per day.
3. The design rate of filtration shall be two gallons per minute per square foot of filter area.
4. The filter structure shall be so designed as to comply with the following requirements:
a. The walls within the filter shall be vertical;
b. The filter walls shall not protrude into the filter media;
c. The filter shall be covered by a superstructure if determined necessary under local climatic conditions;
d. There shall be head room to permit normal inspection and operation;
e. The filter shall have a minimum depth of 8-1/2 feet as measured from the normal operating water surface to the bottom of the underdrainage system;
f. A minimum water depth of three feet as measured from the normal operating water surface to the surface of the filter sand;
g. There shall be a water seal on the effluent line to prevent backflow of air to the filters;
h. A curb at least four inches high shall surround each filter to prevent floor drainage into the filter;
i. A hand rail shall enclose each filter or filter bank;
j. The maximum velocity gradient of treated water in pipes and conduits to the filters shall not exceed that used in flocculation. Where velocity gradient is not used as a parameter, the linear velocity in pipes and conduits from settling basins to filters shall not exceed 1.0 foot per second;
k. Influent pipes or conduits where solids loading is heavy, or following lime soda softening, shall be straight and equipped with cleanouts.
l. Washwater drain capacity shall be sufficient to carry the maximum flow;
m. Access in the form of walkways not less than 24 inches in width shall be provided to each filter; and
n. The normal operating water surface on a filter shall be at the same hydraulic grade level as the sedimentation basin.
5. Washwater troughs shall be so designed as to provide:
a. Bottom elevation of the trough above the maximum level of expanded media during washing;
b. A top elevation of the trough above the filter surface, not to exceed 30 inches;
c. A two inch freeboard at the maximum rate of wash;
d. A level top or edge;
e. Spacing so that each trough serves the same number of square feet of filter area; and
f. Maximum horizontal travel of suspended particles to reach trough not to exceed three feet.
6. Filter material.
a. Sand--A sieve analysis shall be provided by the design engineer. The media shall be clean silica sand having:
(1) A depth of not less than 27 inches and generally not more than 30 inches after cleaning and scraping; and
(2) An effective size of from 0.35mm to 0.5mm, depending upon the quality of the raw water and a uniformity coefficient not greater than 1.6.
b. Supporting media for the filter sand-A sieve analysis shall be provided by the design engineer. A three-inch layer of torpedo sand shall be used as a supporting media for the filter sand; such torpedo sand shall have:
(1) An effective size of 0.8mm to 2.0mm; and
(2) A uniformity coefficient not greater than 1.7.
c. Anthracite-A sieve analysis shall be provided by the design engineer. Clean crushed anthracite or a combination of sand and anthracite may be considered on the basis of data specific to the project; this media shall have:
(1) An effective size from 0.45mm to 0.8mm; and
(2) A uniformity coefficient not greater than 1.7.
d. Gravel, when used as the supporting media, shall consist of hard, rounded particles and shall not include flat or elongated particles. The coarsest gravel shall be 2-1/2 inches in size when the gravel rests directly on the strainer system, and must extend above the top of the perforated laterals or strainer nozzles. Not less than four layers of gravel shall be provided in accordance with the following size and depth distribution:
|
SIZE
|
DEPTH
|
|
2-1/2 to 1-1/2 inches
|
5 to 8 inches
|
|
1-1/2 to 3/4 inches
|
3 to 5 inches
|
|
3/4 to 1/2 inches
|
3 to 5 inches
|
|
1/2 to 3/16 inches
|
2 to 3 inches
|
|
3/16 to 3/32 inches
|
2 to 3 inches
|
Reduction of gravel depths may be considered upon application to the division where proprietary filter bottoms are proposed.
e. Granular activated carbon - See 12VAC5-590-960 B 6.
7. Porous plate bottoms shall not be used where iron or manganese may clog them or with waters softened by lime. The design of manifold type collection systems shall be such as to:
a. Minimize loss of head in the manifold and laterals;
b. Assure even distribution of washwater and an even rate of filtration over the entire area of the filter;
c. Provide a ratio of the area of the final openings of the strainer systems to the area of the filter of about 0.003;
d. Provide a total cross sectional area of the laterals at about twice the total area at the final openings; and
e. Provide a manifold which has a cross sectional area which is 1-1/2 to two times the total area of the laterals.
8. Surface wash facilities are required. Revolving type surface washers shall be provided; however, other types may be considered. All rotary surface wash devices shall be designed with:
a. Provisions for water pressures of 45 to 100 psi;
b. A vacuum breaker or other device to prevent backsiphonage;
c. Provisions for adequate surface wash water to provide 0.5 to one gallon per minute per square foot of filter area; and
d. Air washing may be considered.
9. The following shall be provided for every filter:
a. A sampling tap shall be placed between the filter and the effluent rate of flow controller and shall be equipped with an auxiliary spigot at the point of connection to the effluent line;
b. Indicating and recording loss of head gauges shall be required on all filters having a capacity of greater than 100 gallons per minute. An indicating loss of head gauge shall be required on all filters having a capacity of 100 gallons per minute or less;
c. Indicating and recording rate of flow gauges shall be required on all filters having a capacity of greater than 100 gallons per minute. An indicating and totalizing water meter may be used in lieu of an indicating and recording gauge on filters having a capacity of 100 gallons per minute or less;
d. Effluent rate of flow controllers of the direct acting, indirect acting, constant rate, or declining rate types shall be required on each filter. All control devices used must incorporate an auxiliary shutoff valve in the filter effluent line. Indirect and direct acting effluent rate of flow control devices shall start operation from the closed position; Failure of indirect acting controllers shall not result in any increase in the rate of flow, at the time of failure;
e. Provisions for draining the filter to waste (rewash) with appropriate measure for backflow prevention are required;
f. Hose bibb, hose, and suitable rack for storage of hoses are required; and
g. Indicating and recording turbidimeters on filter effluent with automatic high turbidity alarm are required at all plants having a capacity of 10 MGD or more.
10. Provisions shall be made for washing filters (backwashing) as follows:
a. A minimum rate of 15 gallons per square foot per minute, consistent with water temperatures and specific gravity of the filter media; a rate of 20 gallons per square foot per minute or more is recommended to provide for adequate expansion of the filter media;
b. Filtered water shall be provided at the required rate by washwater tanks, a washwater pump, from the high service main, or a combination of these;
c. Washwater pumps shall be in duplicate unless an alternate means of obtaining washwater is available;
d. The volume of washwater shall provide for not less than 15 minutes wash of one filter at the design rate of wash;
e. A washwater controller or valve shall be provided on the main washwater line to obtain the desired rate of filter wash with the washwater valves on the individual filters open wide;
f. The rate of flow indicator on the main washwater line shall be located so that it can be easily read by the operator during the washing process; and
g. Where backwash pumps are provided, a means for air release must be provided between the backwash pump and the washwater valve.
11. Miscellaneous:
a. Roof drains shall not discharge into the filter or basins and conduits preceding the filters;
b. Provisions must be made for continuous operation of all other filtering units while one filtering unit is out of operation; and
c. Automatic startup of filtering units is prohibited.
B. High rate gravity filters are acceptable for the treatment of water from surface water sources or groundwater sources under the direct influence of surface water. See 12VAC5-590-890 for design requirements.
C. Slow sand gravity filters are acceptable for the treatment of water from certain surface water sources or certain groundwater sources under the direct influence of surface water.
1. Source restrictions. Raw water quality for application to a slow sand filter without pretreatment shall meet the following requirements:
a. Not exceed a turbidity level of 5 NTU monthly average or 30 NTU peak day over a one year period;
b. Not exceed 800 total coliforms in 80% of a minimum of 50 samples taken over a minimum of a 52 week period;
c. Not exceed an apparent color level of 15 CU monthly average over a one year period; and
d. Groundwater sources under the direct influence of surface water shall pilot test to determine if the water contains sufficient nutrients for slow sand filtration to be a viable option.
2. Pretreatment. Raw waters that cannot meet the criteria listed in 12VAC5-590-880 C 1 a through c shall be treated to that quality prior to application to a slow sand gravity filter.
a. Presedimentation may be an appropriate pretreatment depending on the size and specific gravity of the turbidity particles.
b. Coarse media filtration of either a horizontal or vertical flow configuration may be appropriate for reducing levels of smaller size particles. Normally such roughing filters would be designed to accommodate periodic media removal, cleaning, and replacement.
c. Chemical flocculation and coagulation is normally not appropriate pretreatment for slow sand gravity filters.
d. Preoxidation is normally not appropriate pretreatment for slow sand gravity filters.
3. Number of filters. At least two filters shall be provided. In all cases the filters shall be capable of meeting the design maximum daily water demand with one filter out of service.
4. Filter media. Sand shall be clean silica sand that meets the following criteria:
a. The effective size shall be between 0.15 mm and 0.35 mm.
b. The uniformity coefficient shall not exceed 2.5.
c. The sand depth shall not exceed 55 inches. A minimum depth of 30 inches is required for normal operation.
5. Supporting media. Gravel shall meet the requirements of 12VAC5-590-880 A 6 d.
6. Structural details.
a. Sufficient head room shall be provided for normal movement on the filter by operating personnel for periodic sand removal operations.
b. Adequate manholes and access ports shall be provided for moving sand off and onto the filter.
c. There shall be no common wall between finished water and any lesser quality water.
d. Consideration should be given to providing facilities for dirty sand storage and washing, as well as for clean sand storage.
e. All slow sand filters should be covered.
7. Hydraulic design.
a. Filter to waste shall be provided for all slow sand filters.
b. Water entering the filter shall be distributed in a manner such that the surface of the filter shall not be disturbed in any way.
c. The nominal rate of filtration may range from 45 to 150 gpd/ft2 (0.031 to 0.10gpm/ft2) of sand area.
d. The minimum depth of water over the filters shall be three feet. The maximum depth of water over the filters shall not exceed five feet. An overflow capable of handling the maximum flow to the filter shall be provided at the maximum filter water level.
e. Underdrains shall be provided to assure an even rate of filtration across the filter surface. The maximum velocity of water in the lateral underdrains shall be 1.0 ft/sec. The underdrain spacing shall not exceed 12 feet.
f. Each filter shall be capable of being filled with water from the bottom up.
g. Each filter shall be equipped with a loss-of-head guage; a rate-of-flow control device such as an orifice, weir, or butterfly valve; a weir or effluent pipe designed to assure that the water level over the filter never drops below the sand surface; and filtered water sample taps.
8. Performance report. At the conclusion of at least 12 months but no more than 18 months operation of the full scale plant an engineering report shall be submitted to the division that summarizes operating conditions and establishes optimum filter curing time, optimum filter run times, raw and finished water bacteriological and turbidity data, and any other pertinent factors.
D. A. Diatomaceous earth filtration is essentially a straining process. The use of these filters is acceptable for application to surface waters or groundwaters under the direct influence of surface water shall be limited to treatment of a surface water source, a GUDI source, or both with low turbidity and low bacterial contamination, and may be used for iron removal for groundwaters from groundwater.
1. Source restrictions. Raw water quality for application to a diatomaceous earth filter without pretreatment shall meet the following requirements:
a. Bacteria shall not exceed 50 total coliforms in any sample.
b. Color shall not exceed 15 apparent CU units in any sample.
c. Turbidity shall not exceed 5 NTU in any sample.
2. Pretreatment. If the raw water can be treated to meet the above source restrictions diatomaceous earth filtration may be utilized.
3. B. Pilot plant study. Installation of a diatomaceous earth filtration system shall be preceded by a pilot plant study on the water to be treated.
a. Conditions of the the study, such as duration, filter rates, head loss accumulation, slurry feed rates, turbidity removal, bacteria removal, and other relative information shall be approved by the division prior to the study.
b. Satisfactory pilot plant results shall be obtained prior to submission of final construction plans and specifications.
c. The pilot plant study shall demonstrate the ability of the system to meet applicable drinking water standards at all times.
4. C. Types of filters. Pressure or vacuum diatomaceous earth filtration units will be considered for approval.
5. D. Treated water storage. Treated water storage capacity in excess of normal requirements shall be provided to:
a. 1. Allow operation of the filters at a uniform rate during all conditions of system demand at or below the approved filtration rate, and
b. 2. Guarantee continuity of service during adverse raw source water conditions without bypassing the system.
6. E. Number of units. At least two filtering units shall be provided at plants having a rated capacity of more than 100 gpm.
7. F. Precoat.
a. 1. Application. A uniform precoat shall be applied hydraulically to each septum by introducing a slurry to the tank influent line and employing a filter-to-waste or recirculation system.
b. 2. Quantity. Diatomaceous earth in the amount of 0.2 lb/ft2 of filter area or an amount sufficient to apply a minimum of 1/2-inch coating shall be used with recirculation.
8. G. Body feed. A body feed system to apply additional amounts of diatomaceous earth slurry during the filter run is required.
a. 1. Quantity. Rate of body feed is dependent on raw source water quality and characteristics and must be determined in the pilot plant study.
b. 2. Adequate accessibility to the feed system and slurry lines is required.
c. 3. Continuous mixing of the body feed slurry is required.
d. 4. Consideration should be given to providing a coagulant coating (alum or suitable polymer) of the body feed.
9. Filtration.
a. H. Rate of filtration. The recommended nominal rate is 1.0 gpm/ft2 of filter area and hydraulic loading rate shall not exceed 1.5 gpm/ft2 of filter area. The filtration rate shall be controlled.
b. I. Head loss. The head loss shall not exceed 30 psi for pressure diatomaceous earth filters, or a vacuum of 15 inches of mercury for a vacuum system.
c. J. Recirculation. A recirculation or holding pump shall be employed to maintain a differential pressure across the filter when the unit is not in operation in order to prevent the filter cake from dropping off the filter elements. A minimum recirculation rate of 0.1 gpm/ft2 filter area shall be provided.
d. K. Septum or filter element. The filter elements shall be structurally capable of withstanding maximum pressure and velocity variations during filtration and backwash cycles, and shall be spaced such so that no less than one inch is provided between elements or between any element and a wall. Means shall be provided to check the septum(s) septum for cleanliness or damage. Consideration should be given to providing septum assemblies where an individual septums septum can be removed, cleaned, repaired, and replaced.
e. L. Inlet design. The filter influent shall be designed to prevent scour of the diatomaceous each earth from the filter element.
10. M. Backwash. Provision shall be made for periodic backwashing of the filter. A satisfactory method to thoroughly remove and dispose of spent filter cake shall be provided.
11. N. Appurtenances. The following shall be provided for every filter:
a. 1. Sampling taps for raw source and filtered water,;
b. Loss of head 2. A loss-of-head or a differential pressure gauge,;
c. Rate-of-flow 3. A rate-of-flow indicator, preferable with totalizer,; and
d. 4. A throttling valve used to reduce rates below normal during adverse raw source water conditions.
12. Monitoring. Turbidity monitoring is required for filter effluent. The monitoring may be done by recorder or daily periodic measurements.
E. Direct filtration.
1. General. Direct filtration refers to the filtration of high quality and seasonally consistent raw water without prior sedimentation. Design shall be preceded by a pilot study acceptable to the division. An in-plant demonstration study may be appropriate where a conventional treatment plant is to be converted to direct filtration.
2. Preliminary engineering report. A report shall be prepared and submitted to the division which included the following specific items, in addition to those listed in 12VAC5-590-200 C:
a. Historical summary of meteorological conditions.
b. Historical summary of raw water quality covering a period of at least one year with special reference to fluctuation in quality and possible sources of contamination. The following raw water parameters should be evaluated:
(1) Apparent color
(2) Turbidity
(3) Bacterial concentration
(4) Microscopic biological organisms
(5) Temperature
(6) Total solids
(7) General inorganic and organic chemical characteristics
(8) Additional parameters as required by the division.
c. Description of the pilot plant study methods and work to be done.
3. The pilot plant or in-plant demonstration study shall be conducted over a sufficient time to treat all expected raw water conditions throughout the year. The pilot plant filter shall be of a similar type and operated in the same manner as proposed for full-scale operation. The following items, as a minimum, shall be addressed:
a. Chemical mixing conditions including shear gradients and detention periods.
b. Chemical feed rates.
c. Use of various coagulant and filtration aids including polymers.
d. Flocculation conditions and contact time necessary for optimum filtration for each coagulant proposed.
e. Filtration rates.
f. Filter gradation, types of media, and depth of media.
g. Filter breakthrough conditions and backwash requirements.
4. Final engineering report. A final report including the engineer's design recommendation shall be prepared and submitted prior to the submission of plans and specifications.
5. Treatment facilities.
a. Flash mixing and flocculation. The design shall be based on the results of the pilot plant or in-plant demonstration study and the requirements in 12VAC5-590-870 C and D.
b. Filtration. Filters shall be dualmedia or multimedia gravity filters. The final design shall be based on the results of the pilot plant or in-plant demonstration study and the requirements in 12VAC5-590-890. Turbidity at the sand-coal interface of each filter shall be monitored by indicating and recording equipment.
6. Plant siting. The plant design should allow for the future installation of sedimentation basing.
F. Rapid rate pressure filters.
The use of these filters may be considered for iron and manganese and other clarification processes. Pressure filters shall not be used in the filtration of polluted water, water from surface water sources, groundwater under the direct influence of surface water, or following lime soda softening.
1. Minimum criteria relative to number, rate of filtration, structural details and hydraulics, filter media, etc. provided for rapid rate gravity filters also apply to pressure filters where appropriate.
2. The normal rate of filtration shall be 3 gpm/ft2 of filter area.
3. The filters shall be designed to provide:
a. Loss of head gauges on the inlet and outlet pipes of each filter;
b. An easily readable meter or flow indicator on each battery of filters. A flow indicator is recommended for each filtering unit;
c. Filtration and backwashing of each filter individually with an arrangement of piping as simple as possible to accomplish these purposes;
d. Minimum sidewall shell height of five feet. A corresponding reduction in sidewall height is acceptable where proprietary bottoms permit reduction of the gravel depth;
e. The top of the washwater collection trough to be at least 18 inches above the surface of sand;
f. The underdrain system to collect efficiently the filtered water and to distribute the backwash water at a rate not less than 15 gpm/ft2 of filter area;
g. Location of flow indicators and controls that is easily readable while operating the control valves;
h. Air release valve on the highest point of each filter;
i. Accessible manhole to facilitate inspections and repairs;
j. Means to observe the wastewater during backwashing; and
k. Construction to prevent cross connection.
O. Turbidity monitoring. Indicating and recording turbidimeters meeting requirements of 12VAC5-590-770 B shall be provided for:
1. The source water;
2. The effluent from each filter unit; and
3. The CFE.
P. An operation and maintenance manual shall be provided for all diatomaceous earth filtration units. The manual shall include the following:
1. A detailed description of the treatment units and the control of each unit for optimal performance;
2. A preventative maintenance schedule;
3. The manual adjustment and override procedures for all automatic control features; and
4. A troubleshooting guide for typical problems.
Q. The owner shall require the equipment manufacturer to provide onsite start-up and follow-up training.
12VAC5-590-881. Slow sand filtration.
A. Slow sand filters shall be approved only after a pilot study demonstrates that the water supply contains sufficient nutrients for use of this treatment technology.
B. At least two filters shall be provided. In all cases, the filters shall be capable of meeting the design maximum daily water demand with one filter out of service.
C. Sand shall be clean silica sand that meets the following criteria:
1. The effective size shall be between 0.15 mm and 0.35 mm;
2. The uniformity coefficient shall not exceed 2.5; and
3. The sand depth shall not exceed 55 inches. A minimum depth of 30 inches is required for normal operation.
D. Supporting media gravel shall meet the requirements of 12VAC5-590-874 F.
E. Structural details.
1. All slow sand filters shall be covered.
2. Sufficient head room shall be provided for normal movement on the filter by operating personnel for periodic sand removal operations.
3. Adequate manholes and access ports shall be provided for moving sand off and onto the filter.
4. There shall be no common wall between the finished water and any water of lesser quality.
5. All filters shall be protected from freezing.
F. General design requirements.
1. Filter to waste shall be provided for all slow sand filters.
2. Water entering the filter shall be distributed in a manner so that the surface of the filter shall not be disturbed in any way.
3. The nominal rate of filtration range shall be from 45 to 150 gpd/ft2 (0.031 to 0.10 gpm/ft2) of sand area.
4. The minimum depth of water over the filters shall be three feet. The maximum depth of water over the filters shall not exceed five feet. An overflow capable of handling the maximum flow to the filter shall be provided at the maximum filter water level.
5. Underdrains shall be provided to assure an even rate of filtration across the filter surface. The maximum velocity of water in the lateral underdrains shall be 0.75 ft/sec. The underdrain spacing shall not exceed three feet.
6. Each filter shall be capable of being filled with water from the bottom up.
7. Each filter shall be equipped with a loss-of-head gauge; a rate-of-flow control device such as an orifice, weir, or butterfly valve; a weir or effluent pipe designed to assure that the water level over the filter never drops below the sand surface; and filtered water sample taps.
8. Monitoring, indicating, and recording turbidimeters meeting the requirements of 12VAC5-590-770 B shall be provided for:
a. The source water;
b. The filter effluent from each filter unit; and
c. The CFE.
9. The filters shall be designed to operate to waste after scraping or replacement of the sand, until the ripening process is complete and the turbidity meets the requirements of 12VAC5-590-395 A 2 b (3).
12VAC5-590-882. Membrane filtration.
A. Applicability. This section pertains to the use of membrane filtration as follows:
1. For pathogen and turbidity log removal credits in accordance with Table 500.1 in 12VAC5-590-500, the use of MF and UF are allowed.
2. For softening, total dissolved solids (TDS) removal, organics removal, and other treatment purposes, reverse osmosis (RO) and nanofiltration (NF) are allowed in accordance with 12VAC5-590-680 G.
B. Membrane filtration systems shall meet all requirements contained in 12VAC5-590-401 E 6 b to be granted removal credit for Giardia lamblia and Cryptosporidium.
C. A demonstration study shall be conducted on the water to be treated before the installation of a membrane filtration system unless the owner can demonstrate to the satisfaction of the [ commissioner department ] that the source water quality range over all four seasons of a year will be adequately treated by the proposed design.
D. All membrane treatment units for pathogen and turbidity removal shall employ MF or UF using hollow fiber, positive pressure-driven membrane filtration technology. They may employ either an inside-to-outside or outside-to-inside flow direction.
E. The number of membrane units shall be a function of the overall treatment facility capacity, waterworks capacity, and water demand. Multiple membrane units shall be provided where the treatment facility design capacity exceeds 0.5 MGD.
F. Approved materials and chemicals.
1. All membrane materials, associated piping, and other components in contact with the water shall be in accordance with 12VAC5-590-810.
2. Chemicals used in any membrane cleaning process shall be in accordance with 12VAC5-590-515.
G. Turbidity monitoring. Continuous indicating and recording equipment meeting the requirements of 12VAC5-590-770 B shall be provided for the following locations:
1. Source water;
2. Pretreated water, such as by coagulation, flocculation, and sedimentation (if applicable);
3. Filtrate from each membrane unit; and
4. Combined filter effluent, where more than one membrane unit is installed.
H. Indicating and recording equipment for entry point chlorine residual monitoring shall be provided. Indicating and recording equipment for filtered water temperature monitoring shall be provided.
I. Pressure monitoring:
1. Indicating equipment shall be provided for monitoring the pressure drop across any prefilter.
2. Indicating and recording equipment shall be provided for monitoring the pressure drop across membrane modules, (i.e., transmembrane pressure).
3. Integrity monitoring. Indicating and recording equipment for direct integrity test monitoring shall be provided and shall document the date, time, and results of every test performed on each unit.
J. Flow measurement. Equipment shall be provided for measuring or calculating the following flows:
1. Source water, gpm and totalized;
2. Filtrate from each unit, gpm and totalized;
3. Flux from each unit, gpd/sf;
4. Recirculation to each unit, gpd or percent of feed flow, if applicable;
5. Entry point, gpm and totalized; and
6. Waste.
K. An alarm system shall be provided that will report alarm conditions and shut down the treatment plant and entry point flow as necessary.
1. All alarms shall be reported to a location manned 24 hours per day or to a person on call and shall report alarm conditions audio-visually at the water treatment plant.
2. At a minimum, the following points shall be monitored by the alarm system. Alarm and shut down set point conditions will be determined by the [ commissioner department ] on an individual basis.
a. Feed water flow;
b. Feed water turbidity, if required by the [ commissioner department ];
c. Filtrate turbidity from each unit exceeding operational control criteria;
d. Membrane direct integrity test initiation, failure, and exceeding operational control criteria; and
e. Entry point disinfectant residual.
L. Sample taps shall be provided to monitor the following:
1. Source water;
2. Source water storage tank effluent;
3. Feed water after prefiltration;
4. Filtrate from each membrane unit;
5. Combined filtrate from all units;
6. Entry point; and
7. Additional sample taps to monitor the presence of cleaning solutions used in either the backwash or cleaning operations.
M. Equipment shall be provided, using variable frequency drive or other suitable means to adjust the feed pump output in order not to exceed the design flux in the event modules are taken off line.
N. Pressure gauges.
1. A portable, pocket-type pressure gauge of the correct range and accuracy for the application and with the capability of being calibrated shall be provided to check the pressure readings of the pressure transducers installed on the membrane units.
2. At each location of a pressure transducer, a 1/4-inch diameter pressure gauge with American National Standard Taper Threads (NPT) connection shall be provided to facilitate the connection of a portable, pocket-type test gauge.
O. Clean-in-place systems, including tanks, piping, all joints, and valves, shall be compatible with the cleaning solution and shall be corrosion resistant.
P. An operation and maintenance manual shall be provided for all membrane filtration treatment units. The operation and maintenance manual shall include the following:
1. A maintenance schedule for each piece of equipment.
2. Operation procedures, including software user instructions.
3. A troubleshooting guide.
4. Identification of specific proprietary equipment or software not available to the owner or operator.
5. A service call number.
6. DIT requirements.
7. Chemical cleaning instructions.
8. A detailed description of the treatment units and the control of each unit for optimal performance.
Q. A means shall be provided to isolate a compromised module or fiber or both. A means to visually inspect modules while simultaneously conducting the DIT shall be provided. Alternatively, sonic testing equipment that provides a relative accelerometer reading shall be provided where visual inspection cannot be performed.
12VAC5-590-883. Bag and cartridge filtration.
A. Bag or cartridge filtration shall be limited to treating a surface water source, a GUDI source, or both with low turbidity.
B. A pilot plant study shall be conducted on the water to be treated before the installation of a bag or cartridge filter system.
C. Bag and cartridge filtration systems shall be granted removal credit for Giardia lamblia and Cryptosporidium in accordance with 12VAC5-590-401 E 6 a, provided that they meet the requirements of this section.
D. General design requirements.
1. All system components such as housing, bags, cartridges, gaskets, O-rings, and other components in contact with water shall be in accordance with 12VAC5-590-810. All cartridge filter housing shall be certified by the ASME certification program, or equivalent, for pressure vessels and stamped with the appropriate certification mark.
2. Indicating and recording turbidimeters meeting requirements of 12VAC5-590-770 B shall be provided for the source water and the CFE. The [ commissioner department ] may require indicating and recording effluent turbidimeters for each filter unit.
3. The maximum flux rate across the final filter shall not exceed 0.2 gpm/ft2.
4. Maximum differential pressure across the cartridge filter shall not exceed 20 psi.
5. Pressure gauges and sampling taps shall be provided before and after each bag or cartridge filter.
6. Provisions to accomplish filter-to-waste shall be provided.
7. Automatic start-up of bag or cartridge filters is prohibited.
8. An alarm system shall be provided that will report alarm conditions and shut down the treatment plant and entry point flow.
a. All alarms shall be reported to a location manned 24 hours per day or to a person on call and shall report alarm conditions audio-visually at the water treatment plant.
b. The following shall be monitored by the alarm system:
(1) Source water turbidity;
(2) Feed water flow;
(3) If applicable, filtrate turbidity from each unit exceeding operational control criteria;
(4) Combined filter effluent turbidity exceeding operational control criteria;
(5) Differential pressure at each unit; and
(6) Entry point disinfectant residual.
9. At least two filtering units shall be provided at plants having a rated capacity of greater than 100 gpm.
E. Operation and maintenance documents shall be provided for all bag or cartridge filter units and shall include:
1. Detailed description of the bag or cartridge treatment units and the control of each unit for optimal performance.
2. Procedural criteria, such as pressure differential, turbidity, and other parameters, and expected frequency of bag or cartridge filter replacement.
3. A preventative maintenance schedule.
4. Manual adjustment and override procedures for any automatic control features.
5. Troubleshooting guide for typical problems.
F. The owner shall require the equipment manufacturer to provide onsite start-up and follow-up training.
12VAC5-590-890. High rate treatment processes. (Repealed.)
A. General.
High rate treatment processes are characterized by:
1. Precise coagulation control;
2. Turbidity monitoring throughout the process;
3. pH monitoring throughout the process;
4. Reduced flocculation time;
5. Reduced sedimentation time;
6. Use of multimedia filters incorporating anthracite and silica or other types of filter materials; and
7. Filter rates greater than two gallons per minute per square foot of filter area and not exceeding four gallons per minute per square foot of filter area.
B. Instrumentation.
1. The coagulation process shall be controlled by:
a. Zeta potential shall be measured by microelectrophoresis;
b. Dual pilot filters shall be required. The pilot filter shall consist of a small filter (about six inches in diameter) containing the same type and depth of media as the plant filters, and which is operated in the same manner as the larger plant units except that the plant raw water after the treatment chemicals have been added rather than the coagulated and settled water is applied to the pilot filter. The pilot filter shall be equipped with recording turbidimeters on the effluent to measure the filterability of the water as reflected by turbidity monitoring. Departures from these standards using proprietary pilot filters may be considered;
c. Streaming current monitor--a continuous sampling instrument which measures the electric current generated when water flows past suspended particles contained in the water; and
d. In addition to one of the above devices, a multiple six-gang stirring machine for performing jar tests shall be provided.
2. Indicating and recording turbidity monitoring shall be provided for monitoring the turbidity of:
a. The raw water;
b. Settled water from each sedimentation basin;
c. Filter effluent from each filter; and
d. Finished water leaving the treatment plant.
3. Indicating and recording pH monitoring equipment shall be provided for monitoring:
a. The raw water;
b. The flash mix effluent; and
c. The finished water leaving the treatment plant.
C. Unit processes.
1. Flash mix facilities shall conform with 12VAC5-590-870 C.
2. Flocculation design shall comply with 12VAC5-590-870 D, except the minimum detention time shall be 20 minutes.
3. Sedimentation design shall comply with 12VAC5-590-870 E, except the minimum effective detention time shall be three hours.
4. Filtration.
a. The maximum rate of filtration shall not exceed four gallons per minute per square foot of filter area.
b. Number of filter units. At least two units shall be provided at plants having a rated capacity less than two million gallons per day. The total number of filters necessary at plants having a rated capacity equal to or greater than two million gallons per day may be estimated using the following formula:
N = 1.35 (Q)0.5
(Based upon the formula as per Morrell and Wallace from Hardenbergh and Rodie's "WATER SUPPLY AND WASTE DISPOSAL 1960" and modified for the high rate process).
Where N equals the number of filter units, Q equals the plant capacity in million gallons per day.
c. Filters incorporated in the high rate treatment process shall be of the dual media or multimedia type. The media shall consist of anthracite, silica sand, or other suitable filter materials. Both dual media and mixed media filters will be considered. Since filters media designs utilized in the high rate treatment process are generally proprietary in nature, no attempt will be made to set standards for the minimum filter media depth, the effective size and uniformity coefficient of the filter media, or the specific gravity. However, beds having a minimum total depth of 27 inches of filter media with a minimum of 10 inches of fine sand will be considered. Other proposals for high rate processes shall be considered individually by the division.
d. Structural details and hydraulics - see 12VAC5-590-880 A 4.
e. Washwater trough - see 12VAC5- 590-880 A 5.
f. Filter bottoms and strainers - see 12VAC5-590-880 A 7.
g. Surface wash - see 12VAC5-590-880 A 8.
h. Appurtenances - see 12VAC5-590-880 A 9.
i. Backwash - see 12VAC5-590-880 A 10.
j. Miscellaneous - see 12VAC5-590-880 A 11.
5. Chemical application.
a. Suitable equipment for application of filter aids (polymers) to the influent of the filters shall be provided.
b. See 12VAC5-590-860.
12VAC5-590-895. Pre-engineered package treatment units.
A. Pre-engineered package treatment units are defined as predesigned, factory built, and transported virtually assembled to the operation site. The provisions of 12VAC5-590-290 shall apply.
B. General design considerations.
1. A rapid mix unit process shall be provided. The design shall meet requirements of 12VAC5-590-871 A.
2. Flocculation units shall meet requirements of 12VAC5-590-871 B or as identified and justified in the approved PER.
3. Sedimentation units shall meet requirements of 12VAC5-590-872 or as identified and justified in the approved PER.
4. Filters shall be dual media or multimedia gravity filters. Design of filtration units shall meet the requirements of 12VAC5-590-874 or as identified and justified in the approved PER.
5. Indicating and recording turbidimeters meeting requirements of 12VAC5-590-770 B shall be provided for the:
a. Source water;
b. Applied water to each filter;
c. Filter effluent from each filter; and
d. CFE.
6. Sufficient overflows and drains shall be provided to maintain a maximum water level within the plant, including the depth of water over the filters, and to facilitate complete draining of the package unit.
7. Where automatic unit process control is provided, operator adjustment of chemical feed rates, times, and sequences shall be provided as well as a manual override of all automatic features.
a. Automatic start-up of water treatment unit processes is prohibited.
b. Valve actuators shall be provided with manual override capability.
8. Treatment units installed at ground level shall be provided with stairways, walkways, or other suitable means to allow access for operation and maintenance and observation of all treatment process units. Filters shall be adequately accessible to facilitate evaluation of the entire filter bed for media condition and placement, fluidization during backwashing, and evaluation of compaction during filtration.
C. An operation and maintenance manual shall be provided for all pre-engineered package treatment units. The operation and maintenance manual shall include the following:
1. A detailed description of the treatment units and the control of each unit for optimal performance.
2. A preventative maintenance schedule.
3. Manual adjustment and override procedures for any automatic control features.
4. A troubleshooting guide for typical problems.
D. The owner shall require the equipment manufacturer to provide onsite start-up and follow-up training.
12VAC5-590-900. Softening Cation exchange softening.
Softening shall not be used as the sole treatment method for surface waters or bacteriologically contaminated groundwater.
A. The softening process design selected shall be based upon the mineral qualities of the raw source water and the desired finished water quality in conjunction with requirements for disposal of sludge or brine water, cost of the plant, cost of the chemicals, and the plant location.
A. Lime, excess lime, and excess lime soda processes. The applicable design standards for mixing, flocculation, and sedimentation are the same for the lime, excess lime, and excess lime soda processes as for conventional clarification except that the minimum flash mix time is five minutes, flocculation time is 40 minutes, and settling time is two hours. Where softening is included as a treatment process in conjunction with clarification, the greater detention time criteria shall govern. For criteria pertaining to softening with solids contact units, see 12VAC5-590-870 F.
1. Mechanical sludge removal equipment shall be provided in the sedimentation basin.
2. Determinations shall be made of the CO2 content of the raw water. When concentrations exceed 10 milligrams per liter, the economics of removal by aeration as opposed to removal with lime should be considered.
3. Equipment for stabilization of water softened by the excess lime and excess lime soda processes is required.
4. Staging shall be considered when the excess lime soda process is employed.
5. Provision shall be included for proper disposal of softening sludges.
6. The use of excess lime shall not be considered an acceptable substitution for chlorination.
B. Cation exchange process.
B. Iron, manganese, or a combination of the two, in the oxidized state or unoxidized state, should shall not exceed 0.3 milligrams per liter mg/L in the water as applied to the ion cation exchange material. Pretreatment shall be required when the content of iron, manganese, or a combination of the two, is one milligram per liter or more.
1. C. The units may shall be of pressure or gravity type, or of either an upflow or downflow design, using automatic or manual regeneration. Automatic regeneration is suggested for small plants.
2. D. The design capacity for hardness removal should shall not exceed 20,000 grains per cubic foot grains/ft3 when the resin is regenerated with 0.3 pounds of salt per kilograin of hardness removed.
3. E. The depth of the cation exchange material should shall not be less than three feet.
4. F. The hydraulic loading rate of softening should not exceed seven gallons per square foot per minute seven gpm/ft2 and the backwash rate should be six to eight gallons per square foot per minute gpm/ft. 2
5. G. The freeboard shall depend upon the specific gravity of the media and the direction of the water flow.
6. H. The bottoms, strainer systems, and support for the cation exchange material shall conform to criteria provided for rapid rate gravity filters. See also 12VAC5-590-874.
7. I. Facilities shall be included for even distribution of brine over the entire surface of both upflow and downflow units. Backwash, rinse, and air relief discharge pipes shall be installed in such a manner as to prevent any possibility of backsiphonage.
8. J. A bypass shall be provided around softening the cation exchange units to produce a blended water of desirable hardness. Meters shall be installed to measure total water delivered to the distribution system and on each softener unit. An automatic proportioning or regulating device and shutoff valve should be provided on the bypass line. In some installations, it may be necessary to treat the bypassed water to obtain acceptable levels of iron and manganese in the finished water.
9. K. Waters having turbidity of five units NTUs or more turbidity shall not be applied directly to the cation exchange softener. Silica gel materials should be used for water having a pH above 8.4 and should not be used when iron is present. When the applied water contains a chlorine residual, the cation exchange material shall be a type that is not damaged by the chlorine residual chlorine. Phenolic resin shall not be used.
10. Smooth nose sampling L. Sampling taps shall be provided for the collection of representative samples for both bacteriological and chemical analyses. The taps shall be located to provide for sampling of the softener influent, softener effluent, and the blended water. The sampling taps for the blended water shall be at least 20 feet ft downstream from the point of blending.
11. M. Brine measuring or salt dissolving salt-dissolving tanks and wet salt storage facilities shall be covered. The makeup water inlet shall have a free fall discharge of two pipe diameters but not less than two inches above the maximum liquid level of the unit or be protected from backsiphonage. Water for filling the tank should be distributed over the entire surface by pipes above the maximum brine level in the tank. The salt shall be supported on graduated layers of gravel under which is a suitable means of collecting the brine. Wet salt storage basins must be equipped with manhole or hatchway openings having raised curbs and watertight covers having with overhanging edges similar to those required for finished water reservoirs. Overflows, where provided, shall be turned down, have a proper free fall discharge and be protected with noncorrodible screens or self-closing flap valves.
12. N. Wet salt storage basins shall have sufficient capacity to store at least 30 days a 30-day operating supply.
13. O. Stabilization of the finished water for corrosion control shall be provided shall be considered.
14. P. Suitable disposal must be provided for the brine waste.
15. Q. Pipes and contact materials shall be resistant to the aggressiveness of the salt.
16. Salt storage tanks and feed equipment should be enclosed and separated from other operating areas in order to prevent damage to equipment.
12VAC5-590-910. Aeration. (Also see 12VAC5-590-970.)
A. Aeration treatment devices as described herein may be used is acceptable for oxidation, separation of gases, or for taste and odor control. General design requirements include the following:
A. Natural draft aeration.
The design of natural draft aeration shall provide the following:
1. The water shall be distributed uniformly onto the top tray;
2. The water shall be discharged through a series of three or more trays with the separation of trays not less than six inches;
3. The trays shall be loaded at a rate ranging from one gallon per minute to five gallons per minute for each square foot of total tray area;
4. The trays shall have slotted, woven wire cloth, or perforated bottoms;
5. The perforations shall be 3/16 to 1/2 inches in diameter and spaced one to three inches on centers when perforations are used;
6. Eight to 12 inches of inert media shall be used, such as coke or limestone which shall be two to six inches in size, and will not readily disintegrate due to freezing cycles;
7. The aerated water shall receive disinfection treatment; and
8. The trays shall be designed using materials resisting deterioration with consideration being given to corrosion, slime, and algae control.
B. Forced or induced draft aeration devices shall be designed to:
1. Provide an adequate liquid distribution and countercurrent of air through the enclosed aeration column;
2. Be insectproof and lightproof;
3. Be such that air introduced into column shall be screened through insect proof screen and be as free of dust as possible;
4. Ensure that water outlet is adequately sealed to prevent unwanted loss of air; and
5. Ensure that the sections of the aerator can be easily reached and removed for maintenance.
C. Pressure aeration may be used for oxidation purposes if a pilot plant study indicates the method is applicable; it is not acceptable for removal of dissolved gases. Filters following pressure aeration shall have adequate exhaust devices for release of air. Pressure aeration devices shall be designed to:
1. Give thorough mixing of compressed air with the water being treated; and
2. Provide screened and filtered air, free of obnoxious fumes, dust, dirt, and other contaminants.
1. The aerated water shall be chlorinated following aeration.
2. The equipment shall incorporate materials resistant to deterioration and corrosion and shall be designed to eliminate the potential for fouling problems from calcium carbonate and iron precipitation and from algae, slime, and bacteriological growth. Disinfection capability shall be provided before the aeration treatment units.
3. The equipment shall be easily accessed and serviced.
4. The air introduced into the treatment units shall be filtered and shall be free of insects, obnoxious fumes, dust, dirt, and other contaminants. If blowers are located inside a building, then the air intakes shall extend to the outside and be furnished with appropriate air filters.
5. Air exhaust outlets shall be located to avoid induced contaminants, particularly at or near occupied areas or blower intakes.
6. Duplicate blowers, motors, or multiple treatment units shall be required for treatment processes designed to meet the drinking water quality standards in 12VAC5-590-340.
B. Natural, forced, or induced draft aeration units shall be designed to provide an adequate liquid distribution and countercurrent of air through the enclosed aeration column, and adequately seal the water outlet to prevent unwanted loss of air.
C. Pressure aeration means the injection of compressed air into the water to be treated, typically for oxidation. Pressure aeration shall not be approved for removal of dissolved gases. Filters following pressure aeration shall have adequate exhaust devices for the release of air. Pressure aeration devices shall be designed to provide thorough mixing of compressed air with the water being treated.
D. Packed tower aeration (air stripping) is suitable for removing VOCs, THMs, carbon dioxide, and radon.
1. Justification shall be provided for the selected design parameters (e.g., height and diameter of the unit, air-to-water ratio, packing depth, surface loading rate, and other features). The design shall consider the effects of temperature change and the resulting impact in contaminant removal efficiency. Pilot plant studies may be required to substantiate the design.
2. The packing material used shall be resistant to the aggressiveness of the water, dissolved gases, and cleaning materials, and shall meet requirements of 12VAC5-590-810.
3. Water shall be evenly distributed at the top of the tower using spray nozzles or orifice-type distributor trays that will prevent short circuiting. A mist eliminator above the water distribution system may be required.
4. A means to allow for discharge and wasting of water or chemicals used to clean the tower shall be provided.
5. Sample taps shall be provided in the influent and effluent piping.
6. The design shall prevent freezing of the influent riser and effluent piping.
7. An overflow pipe discharging 12 to 24 inches above the ground and over a drainage inlet structure or splash pad shall be provided.
8. A sufficient number of access ports with a minimum diameter of 24 inches shall be provided to facilitate inspection, media replacement, media cleaning, and maintenance of the unit interior.
9. A positive air flow sensing device and a pressure gauge shall be installed on the air influent line. If the aeration unit is designed to remove a contaminant with a PMCL, then the positive air flow sensing device shall be an integral part of an automatic control system that will turn off the influent water if positive air flow is not detected.
D. E. Other methods of aeration may be used if applicable to the treatment needs. Such methods include, but are not restricted to, spraying, diffused air, and mechanical aeration. The treatment processes shall be designed to meet the particular needs of the water to be treated and are subject to the approval of the division [ commissioner department ].
E. Aerators that discharge through the atmosphere should be protected from wind by being placed in a louvered enclosure designed to provide easy access to the interior.
F. Aerators that are used for oxidation or removal of dissolved gases from waters that will be given no further treatment other than chlorination shall be protected from contamination from insects and birds.
G. Ventilation shall be provided to prevent the accumulation of released gases in the building housing the treatment facilities.
H. A bypass should be provided for all aeration units.
12VAC5-590-920. Iron and manganese control.
A. Iron and manganese control, as used herein in this section, refers solely to treatment processes designed specifically for this purpose. The treatment process used will depend upon the character of the raw source water. The selection of one or more treatment processes shall meet specific local conditions as determined by engineering investigations, including chemical analyses of representative samples of water to be treated, and receive the approval of the division [ commissioner department ]. The [ commissioner department ] may require that pilot studies be conducted.
It may be necessary to operate a pilot plant in order to gather all information pertinent to the design.
A. Removal B. Iron and manganese removal by oxidation, detention, and filtration.
1. Oxidation may be by aeration or by chemical oxidation with shall be accomplished by aeration or by chemicals, such as chlorine or, potassium permanganate, sodium permanganate, or a combination thereof.
2. A minimum detention of 30 minutes shall be provided following oxidation by aeration in order to insure that the oxidation reactions are as complete as possible. This minimum detention time shall be reduced only when a pilot plant using the water under study demonstrates a lesser detention time. The detention basin shall be designed as a holding tank with no provision for sludge collection but with sufficient baffling to prevent short circuiting. Sedimentation basins shall be provided when treating water with high iron or manganese content or where chemical coagulation is used to reduce the load on the filters. The detention time shall be in a range of one to four hours where sedimentation is necessary prior to filtration. Pilot studies should be made of the water to determine the necessary detention time.
3. Filtration - see 12VAC5-590-880.
B. Removal by lime-soda process - see 12VAC5-590-900 A.
C. Removal by units using continuous potassium permanganate regeneration.
This process consists of a continuous feed of potassium permanganate to the influent of a manganese greensand filter. Positive displacement type feeders shall be provided, and the feed rate shall be adequately controlled by using feeders which are paced by water meters or ratio type feeders (which are a combination type feeder and flow meter) to prevent an overdosage of potassium permanganate.
1. The permanganate shall be applied following pH affecting chemicals.
2. Other oxidizing agents or processes such as chlorination or aeration may be used prior to the permanganate feed to reduce the cost of the chemical.
3. The normal filtration rate is three gallons per minute per square foot. Lower filtration rates may be required or higher filtration rates may be permitted if justified by field studies and approved by the division
4. The normal wash rate is eight to 12 gallons per minute per square foot.
5. Air washing may be provided.
6. Sample taps shall be provided.
a. Prior to application of permanganate;
b. Immediately ahead of filtration;
c. At a point between the anthracite coal media and the manganese treated greensand;
d. Halfway down the manganese treated greensand; and
e. For filter effluent.
D. Removal by ion exchange. This process of iron and manganese removal may not be acceptable for waters containing high concentrations (more than 1.0 milligrams per liter) of iron, manganese, or combination thereof. Applications may be limited based on the media used. This process may not be acceptable where either the raw water or wash water contains dissolved oxygen. (See 12VAC5-590-900 B for general cation exchange information.)
2. The design shall consider:
a. pH adjustment to promote rapid oxidation;
b. A pre-settling tank located ahead of the filters to remove oxidized iron and increase filter run times;
c. A manganese-oxide coating on the filter media, such as manganese greensand. The total depth of media shall not be less than 30 inches. Media shall have an effective size from 0.3 to 0.35 mm and a uniformity coefficient of no more than 1.6. Following initial placement of the media, care shall be taken to remove fines by backwashing and skimming the surface; and
d. An anthracite cap layer over the manganese-oxide coated media having a depth of six to 18 inches.
3. Aeration shall be designed in accordance with 12VAC5-590-910.
4. Flow proportional chemical feeders shall be provided, and the feed rate shall be adequately controlled by using feeders that are paced by water meters to prevent an over-dosage of chemical. A flow switch in place of a flow proportional feeder may be permissible.
5. Sample taps shall be provided before the application of the oxidant, immediately ahead of filtration, and at the filter effluent.
6. Pressure filters shall include provisions for:
a. Pressure gauges on the inlet and outlet pipes of each filter or a differential pressure gauge on each filter;
b. An easily readable meter or flow indicator on each battery of filters. A flow indicator is recommended for each filtering unit;
c. Filtration, backwashing, and filter-to-waste of each filter individually:
(1) Backwash water shall be evenly distributed in an adequate quantity to achieve at least a 30% media bed expansion during backwashing. The backwash rate shall be based on the media;
(2) The top of the backwash water collection trough shall be at least 18 inches above the media surface;
(3) An underdrain system to efficiently collect the filtered water and to distribute an adequate quantity of backwash water to achieve at least a 30% media bed expansion during backwashing;
d. Flow indicators and controls are located so that they are easily readable while operating the control valves;
e. An air release valve on the highest point of each filter;
f. An accessible manhole to facilitate inspections and repairs for filters greater than 36 inches in diameter;
g. A means to observe the wastewater during backwashing; and
h. Construction to prevent cross-connection.
C. Iron and manganese removal by ion exchange shall only be approved for removing low concentrations (less than 0.5 mg/L) of combined iron and manganese. The [ commissioner department ] may require pilot studies be conducted to determine post-exchange pH/alkalinity adjustment. See 12VAC5-590-900 for general ion exchange design requirements.
E. D. Sequestering - see 12VAC5-590-950 E iron and manganese.
1. Sequestration with polyphosphates shall be considered for polishing filtered water; however, it shall not be used where the residual iron, manganese, or combination thereof exceeds 1.0 mg/L.
2. Phosphate feed rates shall be determined by the product manufacturer and shall not exceed 10 mg/L.
3. Feed equipment shall be in accordance with the requirements of 12VAC5-590-860.
4. Stock phosphate solution shall be disinfected in accordance with manufacturer recommendations unless the phosphate solution is fed directly from the covered shipping container.
5. Sodium silicate or other silicate-based chemicals for the sequestration of iron and manganese shall be approved by the [ commissioner department ] on an individual basis. Operational data from actual full-scale facilities treating waters of similar quality or pilot tests may be required.
F. E. Sampling taps shall be provided for control purposes. Taps shall be located on each raw source water source, each treatment unit influent, and each treatment unit effluent.
G. Testing equipment shall be provided for all plants F. Iron and manganese testing equipment shall be provided. The Iron testing equipment shall have the capacity to accurately measure the iron content to a minimum of 0.1 milligrams per liter and to indicate manganese removal. be capable of accurately measuring iron concentration as low as 0.1 mg/L. Manganese testing equipment shall be capable of accurately measuring manganese concentration as low as 0.05 mg/L.
G. The [ commissioner department ] may approve proprietary treatment processes for the removal of iron and manganese on an individual basis. Operational data from actual full-scale facilities treating waters of similar quality or pilot tests may be required. The provisions of 12VAC5-590-290 may apply.
12VAC5-590-930. Fluoridation.
Where practicable and feasible, the board may require owners of waterworks to provide artificial fluoridation so as to bring the fluoride ion concentration to the optimum level as set forth in Article 1 of Part II.
A. Prior to the issuance of a permit for fluoridation, plans, specifications, operating procedures, and methods of supervision shall be submitted to the division. These shall be in conformity with requirements to be determined for each individual installation by the division. The board recommends that all community waterworks in Virginia be optimally fluoridated. Fluoridation feed systems shall be designed to deliver the optimum fluoride ion concentration as determined by the U.S. Department of Health and Human Services.
B. Fluoride compounds. Commercial sodium fluoride, sodium silicofluoride fluorosilicate (also called sodium silicofluoride), and fluorosilicic acid (also called hydrofluorosilicic acid) shall conform to the applicable AWWA standards or [ NSF/ANSI Standard 60-2017 NSF/ANSI/CAN Standard 60-2020 ], as appropriate. Use of other chemicals which may be made available must be approved by the division.
C. Fluoride compound storage. Fluoride chemicals shall be isolated from other chemicals to prevent cross contamination. Compounds shall be stored in covered or unopened shipping containers in a separate room (except sodium fluoride saturators) with the chemical feeder. The room must be provided with mechanical ventilation to the outside of the building.
D. Chemical feed installations.
1. Chemical feed installations shall conform to 12VAC5-590-860.
2. 1. Scales and loss of weight loss-of-weight recorders for dry chemical feeders and hydrofluorosilicic acid feeders shall be provided.
3. Feeders 2. Fluoride metering pumps shall have an accuracy so that the actual feed rate will be within 5.0% of the intended feed rate.
3. The point of application shall be located to provide adequate mixing.
4. The point of application of hydrofluorosilicic acid, if into a pipe, shall be so located as to provide adequate mixing.
5. 4. All fluoride feed lines shall be provided with adequate antisiphon anti-siphon devices.
5. Design of fluoride saturators shall consider:
a. The source water hardness. The water applied to the sodium fluoride saturator feeders shall be softened if the hardness exceeds 50 mg/L.
b. The fluoride source. Use only sodium fluoride in the saturators.
c. A flow restrictor with a maximum flow of 2.0 gpm on all upflow saturators.
6. The water applied to sodium fluoride saturator feeders shall be softened if hardness exceeds 75 milligrams per liter.
7. Unless otherwise approved, fluoride shall be applied to the raw water with the feeder paced by the raw water meter.
6. Adequate fluoride feed rate control and mixing shall be provided.
8. 7. Provisions shall be made for venting hydrofluorosilicic fluorosilicic acid carboys to the outside of the building when the carboys are in use.
E. Suitable protective equipment shall be provided which includes gloves, aprons, dust mask, and goggles.
F. Suitable equipment shall be provided for wetmopping wet mopping and hosing dust that might accumulate in the plant. Dry feeders shall be equipped with bag loading hoppers.
G. Equipment shall be provided for measuring the quantity of fluoride ion in the water. Testing equipment shall be colorimetric or electrode type as approved by the division [ commissioner department ].
12VAC5-590-940. Fluoride removal.
A. Fluoride removal may be accomplished by blending with a different quality water or by removal treatment. Where fluoride removal is required, the treatment units shall be designed to achieve a finished water fluoride concentration that is below the SMCL.
A. B. Blending. Blended water must shall result in all water delivered to the distribution system being of the same quality.
B. C. Treatment.
1. Chemical feed shall conform to 12VAC5-590-860.
2. 1. Treatment includes use of shall include ion exchange, activated alumina, bone char, reverse osmosis RO, or electrodialysis. Other processes may be utilized if they adequately defluoridate. The selected design is to shall be supported by pilot studies, unless at least two pilot studies, or two prototype plants, have demonstrated that the selected design is feasible. Such These studies or prototypes should shall be for waters having characteristics similar to the water that is to be treated.
3. Raw water 2. Water pH shall be adjustable to an optimum level to achieve the best fluoride removal.
4. 3. With any one unit out of service, the remaining unit or units must shall be capable of handling peak day flows treating the maximum plant flow rate.
5. 4. Filter clogging constituents such as iron having a concentration greater than 1.0 milligrams per liter should mg/L shall be removed prior to defluoridation before fluoride removal. If applicable, chlorination is to be applied after defluoridation.
6. 5. Test equipment must shall be provided and must be accurate to at least 0.1 milligrams per liter mg/L.
7. 6. An operation and maintenance (O & M) manual must shall be provided.
12VAC5-590-950. Stabilization Corrosion control or stabilization.
A. Water that is unstable due either to natural causes or to the treatment given applied to the water should shall be stabilized. Water treated with excess lime for softening or manganese removal shall be treated by carbon dioxide or acid.
A. Carbon dioxide addition.
1. The recarbonation chamber design should provide:
a. A detention time of three to 10 20 minutes;
b. A depth of about eight feet; and
c. A reaction tank with a detention time of 20 minutes.
2. Adequate precautions shall be taken to prevent the possibility of carbon monoxide entering the plant from the recarbonation and reaction chamber.
B. Sulfuric acid.
1. Feed equipment for sulfuric acid shall conform to 12VAC5-590-860.
2. Adequate precautions shall be taken for safety.
C. Removal of free carbon dioxide. Carbon dioxide may be removed by an alkali, following aeration. The addition of an alkali following aeration may not be necessary when the alkalinity of the aerated water is greater than 80 milligrams per liter.
D. B. Deposition of calcium carbonate film. The desired calcium carbonate film may be obtained by using either soda ash or caustic soda when the alkalinity of the water exceeds about 35 milligrams per liter mg/L. Soft waters should be treated with lime to provide the required calcium. Soft waters which that also have a low carbon dioxide content may need a mixture of lime and soda ash to provide both calcium and carbonate for the calcium carbonate film.
E. Polyphosphates. Polyphosphates are applicable for sequestering dissolved minerals.
1. Feed equipment shall conform to 12VAC5-590-860.
2. Phosphate chemicals shall be food grade.
3. Stock phosphate solution shall be kept covered and disinfected by carrying approximately 10 milligrams per liter chlorine residual.
4. Satisfactory chlorine residuals should be maintained in the distribution system when phosphates are used.
F. Under some conditions, softening plants can be designed using split treatment in which raw water is blended with softened water to partially stabilize the water. Treatment plants designed to utilize split treatment should, in most cases, also contain facilities for further stabilization by other means.
G. Water unstable due to biochemical action in the distribution system. Residual chlorine throughout the distribution systems may be used to prevent corrosion due to decomposition of organic matter (especially in dead-ended mains), the biochemical action within tubercles and the reduction of sulfates to sulfides.
C. Phosphates or other corrosion inhibitors may be used for corrosion control when applied in accordance with manufacturer recommendations and when they meet the requirements of 12VAC5-590-515. Stock phosphate solution shall be disinfected in accordance with manufacturer recommendations unless the phosphate solution is fed directly from the covered shipping container.
H. D. Cathodic protection may be used to prevent or minimize shall be acceptable for preventing or reducing corrosion of the inner surfaces of water storage tanks and standpipes and the outer surfaces surface of metal conduits pipe.
I. E. Laboratory equipment shall be provided for determining the effectiveness of stabilization treatment and the concentration of chemicals in the treated water.
12VAC5-590-960. Taste and odor control.
Tastes and odors found in water are primarily organic in nature. Since the presence of taste and odor problems in a water supply suggests to the consumer that the water may contain potentially toxic agents, expenditures are justified to improve the aesthetic quality of the water and maintain the consumers' confidence in the water utility.
A. Source treatment. Taste and odor problems in raw water sources are most frequently caused by the presence of plankton, or more specifically, algae. The treatment methods and dosages listed below have been found effective in some applications.
1. A. The continuous or periodic treatment of raw water source waters with copper sulfate and other copper compounds to kill algae or other growths shall be controlled to prevent a copper concentration in excess of 1.0 milligrams per liter mg/L, as copper, in the finished water leaving the treatment plant finished water.
2. The periodic treatment of the shallow areas of a reservoir with an activated carbon dosage of 0.2 to 0.5 pounds per 1,000 square feet of water surface has been found effective in some applications.
3. A potassium permanganate dosage from 0.4 to 4.0 milligrams per liter has been found effective in some applications.
4. Chlorine dosages that produce 0.2 to 1.0 milligrams per liter of free chlorine in the treated water have been found effective in some applications. Prior to treatment, this treatment method should be evaluated to determine that it will not cause any objectionable tastes or odors in the treated water.
B. Treatment methods. The waterworks shall be designed to produce high quality water regardless of any changes or emergencies that may arise with the raw water source. Provisions to handle taste and odor problems should be included in all designs regardless of the anticipated raw water quality.
1. Provisions shall be included in the design of the treatment plant to add chlorine or other approved oxidizing chemicals at the reservoir or at the head of the treatment plant. If breakpoint chlorination is proposed to treat taste and odor problems, extreme caution is warranted to insure that the actual breakpoint of the water is determined accurately. Dechlorination may be required if deemed necessary.
2. Chlorine dioxide can be utilized to treat any taste and odor problems susceptible to oxidation.
3. Potassium permanganate has oxidizing capabilities that can be utilized to treat taste and odor problems. It is normally fed to the raw water during the flash mix operation in a dosage such that the pink color formed during its solution travels only 1/2 to 2/3 of the length of the sedimentation basins.
4. Aeration has been used successfully to treat tastes and odors attributed to volatile organic matter but has shown limited success in treating tastes and odors associated with dissolved and suspended organic matter. Aeration facilities shall be designed in accordance with the provisions of 12VAC5-590-910.
5. When taste and odor problems are anticipated on an intermittent basis, treatment facilities shall be included in the water treatment plant design for the addition of powdered activated carbon. The dosage of powdered activated carbon required to treat taste and odor problems will vary with each individual raw water, and extensive lab work should be undertaken to ascertain that the carbon feed equipment is properly sized. The carbon feed equipment shall be capable of adding at least 40 milligrams per liter of powdered activated carbon regardless of the anticipated raw water quality. In the water treatment plant design, facilities should be provided to add powdered activated carbon to the flash mixer, to the flocculation basins, at the midpoint of sedimentation basins, and to the conduits leading to the filters.
The carbon can be added as a premixed slurry, or by means of a dry feed machine as long as it is assured that the carbon is properly wetted. All mechanisms for handling dry carbon should be tightly sealed and dust collection is required on all installations. The feed machine hopper wall should be on at least a 60 degree angle to the horizontal.
The carbon feed lines to the application points should be sized to handle the carbon suspension and should be equipped with flushing provisions.
B. Surface water aerators or diffused aeration systems shall be acceptable for de-stratifying reservoirs, reducing or eliminating seasonal turnover, and releasing compounds in the anaerobic or anoxic zones.
C. Addition of chemical oxidants at the source water intake, in the source water pump station discharge line, at the head of the treatment plant, or within the treatment train shall be acceptable for treating tastes and odors. Effective oxidants include chlorine, chlorine dioxide, potassium permanganate, and ozone. If breakpoint chlorination is proposed, then the actual breakpoint of the water shall be determined accurately. "Breakpoint chlorination" means the addition of chlorine to water until the chlorine demand has been satisfied, chlorine and ammonia nitrogen reactions are near completion, and further additions of chlorine result in a free chlorine residual that is directly proportional to the amount of chlorine added.
6. Granular activated carbon units may be used in place of filters described in 12VAC5-590-880 with appropriate pretreatment described in 12VAC5-590-870. Rates of flow shall be consistent with the type and intensity of the problem. The design of the facilities must be supported by the results of pilot plant studies
D. Powdered activated carbon (PAC). When taste and odor problems are anticipated on an intermittent basis, the addition of PAC shall be considered, and a pilot study shall be conducted to determine the optimum dosage. Multiple PAC feed locations shall be evaluated to provide maximum contact time, including the rapid mixer, the flocculation basins, and at the midpoint of the sedimentation basins.
1. PAC shall not be applied near the point of chlorine or other oxidant application.
2. Continuous agitation or resuspension equipment shall be required to keep the PAC from depositing in the slurry or storage tank.
3. All mechanisms for handling dry PAC shall be tightly sealed. Dust collection is required at all installations.
4. The PAC feed lines to the application points shall be sized to handle the PAC suspension and should be equipped with flushing provisions.
E. GAC media shall be acceptable in conventional gravity filters or in separate contactors to reduce taste and odor.
F. Ozonation shall be acceptable for taste and odor control.
12VAC5-590-970. Removal of volatile synthetic organic chemicals (VOCs). (Repealed.)
Appropriate processes or technologies (either specified as BAT in Appendix N or a division-approved alternative, such as other aeration techniques) that treat all the water in the waterworks shall be applied to achieve compliance. The selected design is to be supported by pilot studies unless at least two pilot studies, or two prototype plants, have demonstrated that the selected design is feasible. Such studies or prototypes shall be for waters having characteristics similar to the water that is to be treated.
A. Granular Activated Carbon (GAC). As in taste and odor control, GAC units may be used with appropriate pretreatment described in 12VAC5-590-870 B. The elements of a GAC system include carbon contactors, a carbon storage and transfer system, a regeneration system and a control system.
The selected GAC shall meet AWWA Standards. Multiple units shall be provided to process at least the peak day flow rate with one unit out of service. As carbon is corrosive, the use of noncorrosive piping and storage materials is mandatory.
B. Packed tower aeration. (Also see 12VAC5-590-910.)
1. Usually more efficient than other types of waterfall (natural) aeration.
2. With one unit out of service, the remaining unit(s) must be capable of handling peak day flows.
12VAC5-590-975. Removal of radionuclides.
A. Processes for the removal of radionuclides specified as BAT are identified in 40 CFR 141.66. The specific process and equipment proposed for removal of radionuclides shall to the satisfaction of the [ commissioner department ] have a demonstrated history of successful performance with similar water quality characteristics and performance requirements. Otherwise, the procedures of 12VAC5-590-290 shall apply.
B. When manganese greensand filter systems are utilized, the design shall meet the requirements of 12VAC5-590-920 B. In addition, a chemical contact tank with a minimum detention time of 30 minutes shall be provided. Laboratory or pilot studies may be required to demonstrate compliance with the radium standard when using a filtering treatment system for groundwater with total radium greater than 10 pCi/L.
C. Waste handling, disposal, and permitting shall be given special consideration early in the design process.
D. Occupational exposure shall be considered in the project design.
E. Provisions for operational control monitoring of the radionuclides requiring removal or of acceptable surrogates shall be included in the project design.
12VAC5-590-980. Microscreening. (Repealed.)
A microscreen is a mechanical supplement to treatment capable of removing suspended matter from water by straining. It shall not be used as a substitute for clarification or filtration.
A. The design of microscreening facilities shall give due consideration to:
1. A sanitary survey and chemical and biological evaluation;
2. The nature of suspended matter to be removed;
3. The corrosiveness of water;
4. The effect of chlorination when required as pretreatment; and
5. Control of the hydraulic capacity of the microscreen.
B. The design shall provide:
1. For durable, corrosion resistant screens;
2. A bypass and cleaning arrangement;
3. Duplicate units for continuous operation;
4. Protection against back siphonage when potable water is used for washing; and
5. Proper disposal of wash water.
12VAC5-590-985. GAC contactors.
A. Granular activated carbon (GAC) contactors may be used to adsorb natural organic compounds, taste and odor compounds, and SOCs. The most common applications of GAC contactors in drinking water treatment plants are (i) post-filtration adsorption and (ii) filtration-adsorption, in which some or all of the filter media in a granular media filter is replaced with GAC.
B. General requirements.
1. A demonstration study using bench-scale or pilot-scale tests shall be conducted to determine the GAC media effectiveness, adsorption efficiency, and regeneration frequency.
2. GAC contactors shall be sized for the optimum empty bed contact time.
3. A minimum of two contactor units shall be provided.
4. Bypassing the GAC facility may be permissible under certain circumstances to accommodate seasonal water quality fluctuations and allow for blending water.
C. Hydraulic configuration.
1. Pressure vessel installation may be configured in parallel or in series.
2. For pressure contactors, pre-filter and post-filter pressure gauges shall be installed at each individual contactor unit.
3. The rate of flow through the contactors shall be controlled either manually or automatically to ensure equal flow through each contactor.
D. Design details.
1. For pressure contactors, the maximum pressure loss through the vessels shall be as determined by the product manufacturer.
2. Sample taps, isolation valves, and bypass piping shall be provided before and after each individual contactor unit.
3. Pipes, tanks, and appurtenances shall be corrosion resistant.
4. The GAC facility shall provide the ability to filter-to-waste to prevent carbon fines in the effluent water.
5. Unless otherwise approved by the [ commissioner department ], disinfection shall be accomplished following the GAC contactors.
6. If backwashing of GAC specific units is required, then unchlorinated filtered water shall be used.
7. Turbidity monitoring of contactor effluent shall be considered.
8. The facility design shall include provisions for spent carbon disposal, GAC delivery, and storage.
12VAC5-590-990. Waterworks waste.
A. With the exception of sanitary sewage and flows recycled through the water treatment system, the wastes generated during the operation of water filtration plants constitute industrial wastes and are subject to the State Water Control Law (Chapter 3.1 (§ 62.1-44.2 et seq.) of Title 62.1 of the Code of Virginia).
Industrial wastes generated by water treatment facilities include, but are not limited to, the following:
1. Filter backwash water;
2. Coagulant sludges residuals;
3. Softening sludges residuals;
4. Microscreening sludges;
5. 4. Iron and manganese sludges residuals;
6. Sludges 5. Settled solids from presedimentation units; and
7. 6. Brine wastes.
B. After receipt and review of plans and specifications from the consulting engineer for the water treatment facilities, the division [ commissioner department ] will advise the State Water Control Board DEQ of any proposal to treat and discharge industrial wastes into state waters. The division commissioner department ] will submit to the State Water Control Board a letter or report to include DEQ that includes the following:
1. Capacity of the proposed treatment facilities;
2. Location of the proposed facilities;
3. Proposed final disposition of the treated waste effluent;
4. Name and address of the consulting engineer; and
5. Name and address of the owner.
C. Except for recycle flows as described in 12VAC5-590-420 K 12VAC5-590-395 C, the State Water Control Board owner will then deal directly with the consulting engineer in reference to need to satisfy DEQ's requirements for the final disposal of these wastes and.
D. The sanitary wastes from water treatment plants must receive treatment. Wastes from these facilities must shall be discharged either directly to a sanitary sewer system or to an approved individual waste disposal facility providing suitable treatment approved by the State Water Control Board.
12VAC5-590-1000. Disinfection.
A. Objective. To The objective of disinfection is to prevent the occurrence of waterborne diseases from the consumption of drinking water.
B. Methods. Disinfection shall be accomplished by the application of chlorine. The specific chlorine compound shall be selected on the basis of water flow rates, application rates, pH of the water, cost of equipment and chemicals, availability of disinfectant, and reliability of feed equipment. Alternate chemicals and methods for disinfection are to be handled as unconventional and the procedures of 12VAC5-590-300 apply.
C. Equipment.
1. Solution feed vacuum type gas chlorinators are generally preferred. The use of hypochlorite feeders of the positive displacement type may be considered for small installations.
2. Chlorinator capacities will vary, depending on the use and point of application of the chlorine and the raw water quality. Chlorination capacity shall be such that a minimum dosage of 15 milligrams per liter may be fed at all times.
3. Standby chlorination equipment shall be provided and chlorination capacities shall comply with 12VAC5-590-1000 C 2 with any unit out of operation for repairs. Spare parts shall be available for all chlorinators to replace parts which are subject to wear and breakage. All chlorinators shall be properly maintained and operated.
4. An ample supply of potable water shall be available for operating the chlorinator. Where a booster pump is required, duplicate equipment shall be provided, and, when necessary, standby power as well. Equipment for backflow prevention shall be provided. A pressure gauge shall be provided on each chlorinator water supply line.
5. Scales for weighing cylinders shall be provided at all waterworks using chlorine gas. At large waterworks, scales of the indicating and recording type are recommended. Scales shall be recessed unless they are of the low platform type.
6. Where manifolding of several cylinders is required to evaporate sufficient chlorine, consideration shall be given to the installation of gas evaporators.
7. A bottle of ammonia hydroxide solution shall be available for detecting chlorine gas leaks. Consideration shall also be given to the provision of caustic soda solution reaction tanks for absorbing the contents of leaking one-ton cylinders where such cylinders are in use. At large installations, consideration should be given to the installation of automatic gas detection and related alarm equipment. Emergency cylinder repair kits shall be provided.
8. Piping and connections for chlorine gas.
a. Piping arrangements should be as simple as possible. Pressure gauges shall be installed on the piping to each chlorinator. The number of screwed or flanged joints should be held to a minimum. Piping systems should be well supported and adequately sloped to allow drainage; low spots should be avoided. Suitable allowance should be provided for pipe expansion due to changes in temperature. Liquid chlorine has a high coefficient of thermal expansion. If liquid chlorine (containing no gas bubbles) is trapped between two valves, high pressure will develop upon increase in the temperature of the chlorine. This pressure may lead to hydrostatic rupture of the line. The effects of possible rupture should be considered in the design of any piping system. Where such rupture would present an undue hazard to personnel or equipment by allowing large quantities of chlorine to escape, protection of the system against hydrostatic pressure should be provided.
b. Condensation or reliquefaction of chlorine may occur in chlorine gas lines which pass through areas where the temperature is below the temperature pressure equilibrium indicated in the vapor pressure curve. Where adequate superheat is not provided by a vaporizer, condensation can be prevented by reducing the pressure with a pressure reducing valve.
c. It is recommended that joints in chlorine piping be flanged or welded. If threaded joints are used, extreme care should be taken to obtain clean, sharp threads. A lubricating pipe dope suitable for chlorine should be used. All threading oil must be thoroughly cleaned from the pipe. For permanent joints, linseed oil and graphite, glycerine or Teflon tape may be used. If Teflon tape is used, all remnants must be removed before joints are remade.
d. Fittings and appurtenances must be suitable for handling dry chlorine.
9. Chlorine solution is very corrosive to all of the common construction metals. At low pressures, chlorine solution can be handled in chemical stoneware, glass or porcelain equipment, and by certain alloys. Hard rubber, unplasticized polyvinylchloride, glassfiber reinforced polyester, polyvinylidene chloride, and fully halogenated fluorocarbon resins have been used successfully. Low molecular weight polyethylene, fiber reinforced rubber hose, and wrapped rubber hose have been used successfully for small capacity chlorinators. All of these materials must be selected with great care. For higher pressures, combinations using resistant lining materials (rubber, kynar, saran, Teflon, etc.) with the common metals for strength should be used.
Titanium may be used with chlorine solution, but must not be used with chlorine gas. Tantalum is inert to chlorine solution at temperatures up to 300°F. Hastelloy Alloy C® and Monel Alloy® are widely used. Platinum and silver find special applications. In general, operations involving chlorine solution require individual study.
Chlorine and equipment suppliers shall make recommendations only after careful survey of all factors involved.
10. Chlorine solution and hypochlorite solution piping shall be arranged such that prechlorination or postchlorination may be accomplished by any or all chlorinators.
D. Engineering design.
1. Any building to house chlorine equipment or containers should be designed and constructed to protect all elements of the chlorine system from fire hazards. If flammable materials are stored or processed in the same building, a fire wall should be erected to separate the two areas. Fire resistive construction is recommended.
If gas chlorination equipment and chlorine cylinders are to be in a building used for other purposes, a gas tight partition shall separate this room from any other portion of the building. Doors to this room shall open only to the outside of the building, and shall be equipped with panic hardware. Such rooms shall be at ground level, and should be separated from the feed area.
At least two means of exit should be considered from each separate room or building in which chlorine is stored, handled, or used. All exit doors shall open outward.
A clear glass, gas tight window shall be installed in an interior wall of the chlorinator room to permit the chlorinators to be viewed without entering the room.
Feed lines shall not carry chlorine gas beyond the chlorine feeder room unless the chlorine is under vacuum.
2. Chlorinator rooms shall be provided with a means of heating so that a temperature of at least 60°F can be maintained, but the room should be protected from excess heat. Cylinders shall be kept at essentially room temperature for at least 24 hours prior to use unless an evaporator is employed.
3. Forced, mechanical ventilation which will provide one complete air change per minute shall be installed in all chlorine feed rooms and rooms where chlorine cylinders are stored. The entrance to the air exhaust duct from the room shall be near the floor and the point of discharge shall be located so as not to contaminate the air inlet to any building or inhabited areas. Air inlets shall be located so as to provide cross ventilation with air and at such temperature that will not adversely affect the chlorination equipment. The vent hose shall run without traps from the chlorinator and shall discharge to the outside atmosphere above grade.
4. The electrical controls for the fans and lights shall be such that they will automatically operate when the door is opened and can be manually operated from the outside without opening the door.
E. Respiratory protection. The use of self-contained breathing apparatus (SCBA) in compliance with OSHA Respiratory Protection Standard 1910.134, "VIRGINIA OSHA STANDARDS" for General Industry, is required whenever anyone is dealing with an accidental release of chlorine. All waterworks that use chlorine gas at their treatment facility shall maintain a respiratory protection plan including emergency procedures, evacuation plans, designated SCBA personnel and any special site specific requirements. All respiratory protection devices shall be stored to protect against dust, sunlight, heat, extreme cold, excessive moisture or damaging chemicals; and in a location remote from the chlorine area.
F. Application of chlorine.
1. Provisions shall be made to ensure uniform mixing of the chlorine solution or hypochlorite solution with the water near the point of application.
2. Residual and contact time.
a. Waterworks with surface water sources shall provide a minimum residual (C) and contact time (T) as calculated in accordance with Appendix L. Appendix L contains information on CT calculations and methods, as well as information on contact tank baffling arrangements.
b. Waterworks with groundwater sources shall provide a minimum 30 minute hydraulic detention period (based on design flow) for chlorine contact.
G. Evaluation of effectiveness.
1. Sampling - see 12VAC5-590-770.
2. Equipment shall be provided for measuring chlorine residual employing any method listed in the most recent edition of "Standard Methods for the Examination of Water and Wastewater."
The equipment should enable residual chlorine measurement to the nearest 0.1 milligram per liter in the range below 0.5 milligram per liter, and to an accuracy of approximately 25% above 0.5 milligram per liter. The installation of continuous automatic chlorine residual analyzers recording and proportioning systems may be required on large installations.
B. Primary disinfection shall be provided for all surface water sources, all spring sources, all GUDI sources, and all well sources determined to be of questionable bacteriological quality as required by the [ commissioner department ]. Consideration shall be given to minimizing the formation of DBPs when designing a disinfection process. Waterworks with groundwater sources requiring disinfection under this section shall meet the requirement of 12VAC5-590-421 A 1 d.
C. All pipes, tanks, and equipment that convey, store, or treat potable water shall be disinfected with chlorine before being placed in service in accordance with the following AWWA standards where applicable: C651-14, [ C652-11 C652-19 ], and [ C653-13 C653-20 ].
D. All residual disinfectant determinations shall be made using methods identified in 12VAC5-590-440.
1. The project documents shall outline the procedures and include the disinfectant dosage, contact time, and method of testing the results of the procedure.
2. Methods of disinfection other than chlorination may be considered by the [ commissioner department ] on a individual basis.
12VAC5-590-1001. Chlorination.
A. General design requirements.
1. Chlorine feed capacity shall be capable of meeting the disinfection requirements under all operating conditions.
a. Chlorine feed systems for primary disinfection at a waterworks using a surface water source, a GUDI source, or both shall provide sufficient capacity to achieve the required microbial log inactivation specified in Table 500.1.
b. Chorine feed systems for primary disinfection at a waterworks using groundwater sources shall provide sufficient capacity to achieve 4-log virus inactivation and removal.
c. Chlorine feed systems for secondary disinfection at a waterworks shall provide sufficient capacity to achieve a minimum chlorine residual at the entry point of 0.2 mg/L for more than 4 hours.
2. Chlorine feed systems for disinfection at a waterworks using a surface water source, a GUDI source, or both shall be sized to deliver the required dose with the largest unit out of operation. Small hypochlorination installations for groundwater source waterworks shall have a spare metering pump, unless it can be demonstrated to the satisfaction of the [ commissioner department ] that spare equipment is readily available from a local supplier. Spare parts shall be available for all chlorinators to replace parts that are subject to wear and breakage.
3. Consideration shall be given to providing multiple chlorine feed points at all waterworks. For conventional filtration treatment plants, chlorine feed points shall be provided for the source water, applied water to the filters, and filter effluent.
4. The piping providing the water for preparing the chlorine solution shall be designed to prevent contamination of the "bulk treated" finished water.
a. At all facilities treating surface water, pre-filtration and post-filtration disinfection systems shall operate independently of each other to prevent possible siphoning of partially treated water into the clearwell.
b. The water piping to each ejector shall have a separate shutoff valve. A master shutoff valve is prohibited.
5. Provisions shall be made to ensure uniform mixing of the chlorine with the water near the point of application.
6. Residual and contact time.
a. The owner of a waterworks using a surface water source, a GUDI source, or both shall provide a minimum residual (C) and contact time (T) as calculated in accordance with 12VAC5-590-500.
b. The owner of a waterworks using a groundwater source that is required to disinfect shall provide a minimum residual (C) and contact time (T) to achieve 4-log virus inactivation and removal based on maximum design flow rate. Provisions shall be made to prevent short circuiting. The contact basin shall be designed utilizing the appropriate baffle factors referenced in Table 500.15 of 12VAC5-590-500.
7. Automatic proportioning chlorinators shall be provided where the rate of flow is not reasonably constant.
8. Equipment shall be provided for measuring the chlorine residual, employing any method specified in 12VAC5-590-440. The equipment shall be capable of a chlorine residual measurement to the nearest 0.1 mg/L.
9. Continuous chlorine residual analyzers shall be provided at all waterworks that are required to filter and that serve 3,300 or more persons or at any waterworks required by the [ commissioner department ]. Where a continuous chlorine residual analyzer is provided, the [ commissioner department ] may require that the design incorporate an operator-selected high or low chlorine residual alarm.
B. Gas chlorine feed systems.
1. Equipment.
a. An ample supply of potable water shall be available for operating the chlorinator. Where a booster pump is required, duplicate equipment shall be provided, and when necessary, standby power shall be provided as well. Equipment for backflow prevention shall be provided. A pressure gauge shall be provided on each chlorinator mixing water piping.
b. Scales for weighing cylinders shall be provided at all waterworks using chlorine gas. At large waterworks, scales of the indicating and recording type shall be considered. Scales shall be recessed unless they are of the low-platform type.
c. Where a manifold of several cylinders is required to evaporate sufficient chlorine, consideration shall be given to the installation of gas evaporators.
d. Automatic switch-over of chlorine cylinders shall be provided to assure continuous disinfection.
2. Chlorine gas leak detection.
a. Automatic chlorine gas leak detection with strategically located sensors and related alarm equipment shall be provided for all installations.
b. A bottle of ammonia hydroxide solution shall be provided for detecting chlorine gas leaks.
3. Emergency cylinder repair kits shall be provided.
4. Consideration shall be given to the provision of caustic soda solution reaction tanks for absorbing the contents of leaking one-ton cylinders where the cylinders are in use.
5. Piping and connections for chlorine gas.
a. Pressure gauges shall be installed on the piping to each chlorinator. Piping systems shall be well supported and adequately sloped to allow drainage. Suitable allowance shall be made for pipe expansion due to changes in temperature.
b. Fittings and appurtenances shall be suitable for handling dry chlorine.
6. Building design.
a. Any building to house chlorine equipment or containers shall be designed and constructed to protect all components of the chlorine system from fire hazards. See 12VAC5-590-720.
b. If gas chlorination equipment and chlorine cylinders are to be in a building used for other purposes, a gas-tight partition shall separate this room from any other portion of the building. Doors to this room shall open only to the outside of the building and shall be equipped with panic hardware. These rooms shall be at ground level and should be separated from the feed area.
c. At least two means of exit shall be considered from each separate room or building in which chlorine is stored, handled, or used. All exit doors shall open outward.
d. A clear glass, gas-tight window shall be installed in an interior wall of the chlorinator room to permit the chlorinators to be viewed without entering the room.
e. Feed lines shall not carry chlorine gas beyond the chlorine feeder room unless the chlorine is under vacuum.
f. Chlorinator rooms shall be provided with a means of heating so that a temperature of at least 60°F can be maintained, but the room should be protected from excess heat. Cylinders shall be kept at essentially room temperature for at least 24 hours before use unless an evaporator is employed.
g. Forced, mechanical ventilation that provides one complete air change per minute shall be installed in all chlorine feed rooms and rooms where chlorine cylinders are stored. The inlet to the air exhaust duct from the room shall be near the floor, and the point of discharge shall be located so as not to contaminate the air inlet to any building or inhabited areas. Air inlets shall be located so as to provide cross ventilation with air and at a temperature that will not adversely affect the chlorination equipment. The vent hose shall run without traps from the chlorinator and shall discharge to the outside atmosphere above grade.
h. The electrical controls for the fans and lights shall automatically operate when the door is opened and can be manually operated from the outside without opening the door.
C. Calcium hypochlorite and sodium hypochlorite feed systems.
1. Both calcium hypochlorite and sodium hypochlorite shall be acceptable for disinfection.
2. Hypochlorite solution feeders of the positive displacement type shall be provided.
3. Adequate mixing of the calcium hypochlorite or sodium hypochlorite solutions shall be provided.
4. Special design considerations for bulk delivery systems:
a. Bulk sodium hypochlorite storage tanks shall be constructed of corrosion-proof materials. Pumps, piping, materials, and appurtenances exposed to the sodium hypochlorite shall be suitable for such use.
b. Sodium hypochlorite storage facilities shall be designed to keep ambient temperature and lighting low. Sodium hypochlorite fumes are corrosive and tanks shall be vented to the outside. Tanks shall be designed for ease of filling, draining, and transfer of contents.
c. Piping, valves, pumps, and pipe accessories shall be designed and configured so as not to allow accumulation of gases that could cause air locking or loss of prime in chemical feed piping or pumps.
d. The design shall provide a system of local or general exhaust features to keep employee exposures below the airborne exposure limits, as described in the Safety Data Sheet for the chemical used, in accordance with federal occupational safety and health standards (29 CFR 1910.1200(g)). Local exhaust ventilation is generally preferred because it controls contaminant emissions at the source and thus, preventing dispersion into the general work area which could result in corrosion or exposure. Exhaust equipment and accessories shall be corrosion proof.
e. An eye wash fountain and quick-drench facilities in the immediate work area shall be provided.
12VAC5-590-1002. Chloramination.
A. Chloramines shall be acceptable for secondary disinfection. Chloramines are formed by the reaction of ammonia and chlorine. Multiple chemical species may be created; however, monochloramine is the desired form.
B. The process shall be controlled to minimize formation of dichloramine and nitrogen trichloride, which can create objectionable taste and odors. Control should be sufficient to limit free ammonia leaving the chloramination facility to no more than 0.1 mg/L as nitrogen.
C. pH adjustment facilities shall be provided to maintain pH in the range of 7 to 8.
D. When use of chloramines is proposed, the potential increase of lead leaching within the distribution system shall be considered. Additional distribution system monitoring may be required by the [ commissioner department ].
E. The owner shall inform the public before initiating any disinfection process involving chloramines, as directed by the [ commissioner department ].
12VAC5-590-1003. Chlorine dioxide addition.
A. Chlorine dioxide may be considered as a pre-oxidant to control tastes and odors, reduce color, oxidize iron and manganese, and reduce DBPPs. Chlorine dioxide may be used for primary disinfection. Where chlorine dioxide is used, consideration shall be given to the formation of the byproducts chlorite and chlorate.
B. Chlorine dioxide is generated onsite from sodium chlorite and either chlorine gas or hypochlorite solution. Chlorine dioxide generation equipment shall be factory assembled, pre-engineered units with a minimum efficiency of 95%. The excess free chlorine shall not exceed 3.0% of the theoretical stoichiometric concentration required.
C. The owner shall inform the public before using chlorine dioxide, as directed by the [ commissioner department ].
12VAC5-590-1004. Ozonation.
A. Ozone may be considered as a pre-oxidant to control tastes and odors, reduce color, oxidize iron and manganese, reduce DBPPs, and used for primary disinfection. Where ozone is used, consideration shall be given to the level of bromide and formation of brominated byproducts.
B. Ozone systems are typically comprised of four basic subsystems: ozone generation, feed gas preparation, ozone contactors, and off-gas disposal.
C. The PER shall evaluate water and gas flow rates, oxygen source, generator selection and sizing, contactor design, treatment process location, exhaust gas collection and destruction, and operator requirements.
D. Treatability studies using bench-scale or pilot-scale tests may be required as part of the PER to address the following:
1. Alternate points of ozone application;
2. Ozone demand tests, applied dose, transferred dose, and decay rates; and
3. Ozone byproducts, including bromide and bromate analyses.
E. Ozone systems shall be granted disinfection credit for Giardia lamblia, Cryptosporidium, and viruses, in accordance with 12VAC5-590-401 E 7 and 12VAC5-590-500, provided that they meet the requirements of this section.
1. Ozone residual levels shall be monitored continuously and recorded. For waterworks that claim inactivation credit for ozone, a minimum of two dedicated, online monitors per ozone contactor shall be provided. The location of the monitors shall be acceptable to the [ commissioner department ]. A portable ozone monitor shall be provided as a backup.
2. Ozone systems using multiple, consecutive contact chambers with gaseous ozone injected in the initial chambers, shall be designed to measure the ozone residual and compute log inactivation of Giardia and virus using the CeffluentT10 Method or the Log Integration CT10 Method, as described in the "Long Term 2 Enhanced Surface Water Treatment Rule Toolbox Guidance Manual," EPA Office of Water (4606), EPA 815-R-09-016, April 2010.
3. Sampling lines shall be designed to minimize the reaction time (typically less than 10 seconds conveyance time).
F. Alarms shall be provided for ozone process control safety. Automatic shutdown features shall be considered.
12VAC5-590-1005. Ultraviolet light (UV) disinfection.
A. All UV reactors shall conform to [ NSF/ANSI NSF/ANSI/CAN ] standards.
B. Each reactor train shall be equipped with an individual flow meter or a single flow meter in conjunction with differential pressure sensors in each treatment train. Reactors shall be sized to treat the design flow.
C. Hydraulic design shall ensure that lamps are submerged and that the entrance of air, negative pressure, or pressure surges in the reactors is prevented. Open channel flow reactors are prohibited.
D. A pressure gauge shall be provided upstream of each reactor. The design shall ensure that the reactor's maximum rated pressure cannot be exceeded.
E. Water quality parameters that may affect UV disinfection system performance shall be evaluated, including calcium, iron, manganese, hardness, and alkalinity. Pretreatment shall be considered for water quality parameters that may result in lamp sleeve fouling.
F. A building to enclose and protect all UV equipment shall be provided. Adequate space between control panels, power supply, and the reactor equipment shall be provided to allow for routine operation and maintenance, including removing lamp and wiper assemblies and for off-line chemical cleaning of reactor lamps.
G. An operation and maintenance manual shall be provided for all UV reactors.
H. UV systems may be used for primary disinfection and shall be granted log inactivation credit for Giardia lamblia, Cryptosporidium, and viruses in accordance with Table 401.7, provided that they meet the requirements of 12VAC5-590-401 E 7 c and this subsection.
1. Only UV reactors that have undergone independent, third-party oversight of the validation testing on a fully assembled system to determine the operating conditions under which the reactors deliver the required UV dose shall be considered for log inactivation credit.
2. The dose-monitoring strategy shall be either the UV intensity set point approach or the calculated dose approach as described in the "Ultraviolet Disinfection Guidance Manual For The Final Long Term 2 Enhanced Surface Water Treatment Rule," Office of Water (4601), EPA 815-R-06-007, November 2006. The dose-monitoring strategy shall be demonstrated through the UV reactor validation testing.
3. At least two reactors shall be provided. Reactors shall be sized to treat the design flow with the largest reactor out of service.
4. Continuous monitoring sensors shall be provided to measure UV intensity. A continuous sensor shall also be provided to measure ultraviolet transmittance (UVT) if the calculated dose approach is utilized.
a. The number of sensors provided shall be the same as that used in validation testing of the reactor.
b. Output from a continuous UVT analyzer shall be capable of being input directly into a control loop for each UV reactor, a SCADA system, or both. A bench-top spectrophotometer may be provided instead of a continuous UVT analyzer.
c. All signals from the sensors shall be displayed for operator response and for recordation.
d. At least one reference sensor for calibration of online UV intensity sensors shall be provided. Reference sensors shall be capable of calibration against a traceable standard.
e. Continuous recording equipment shall be provided with the monitoring sensors to store in memory or print one data point at least every four hours.
5. A means of flow distribution and control among multiple reactors shall be provided. The hydraulic flow profiles and piping configuration shall be identical to or more protective than that tested during equipment validation.
a. For onsite validation, the inlet and outlet piping configuration for the UV facility shall be designed according to manufacturer recommendations and to accommodate any site-specific constraints.
b. To avoid jetting flow and swirling flow, consideration shall be given to exclude expansions for at least 10 pipe diameters upstream of the reactor and to exclude out-of-plane 90-degree bends in series.
c. Each UV reactor shall be capable of being isolated and removed from service. Isolation valves upstream and downstream of each reactor, a drain, and sample taps for each reactor treatment train shall be provided. If the isolation valves are also used for flow control, then the flow control valve shall be located downstream of the UV reactor to limit the disturbance of the flow entering the UV reactor. Bypass piping shall not be allowed.
d. The lateral piping for each UV reactor train shall be sized and configured to provide approximately equal head loss through each UV reactor train over the validated range of flow rates.
6. The control system shall be capable of meeting the monitoring and reporting requirements in 12VAC5-590-401 and 12VAC5-590-570.
7. Automatic shutdown capability under critical alarm conditions shall be provided, including lamp or ballast failure, low liquid level, and high temperature. Alarms shall be provided for low UV validated dose, low UV intensity, low UV transmittance, high flow rate, and mechanical wiper failure.
8. Ground-fault circuit interrupters shall be provided for all lamps. Backup power shall be considered.
9. The owner shall develop a start-up plan and submit the plan to the department for approval. The plan shall include functional testing, determination of validated operating conditions and control settings, performance testing, development of an operation and maintenance manual, and inspection schedules.
I. UV systems not intended for primary disinfection may be used provided that they meet the requirements of this subsection.
1. Continuous sensors to measure UV intensity shall be considered.
2. Each UV reactor shall be capable of being isolated, removed from service, and be provided with bypass piping.
3. Automatic shutdown capabilities shall be provided in the event of lamp or ballast failure.
Article 4
Pumping Facilities
12VAC5-590-1010. General Basic pumping facility design criteria.
Pumping facilities shall be designed to maintain the sanitary quality of pumped water. Subsurface pits or pump rooms and inaccessible installations should be avoided. All pumps shall be accessible for servicing and repair.
12VAC5-590-1020. Location.
A. The pumping station shall be located so that the proposed site will meet the requirements of the sanitary protection of the water quality and the hydraulics of the system and be protected against interruption of service by fire, flood, or any other hazard to meet the hydraulic needs of the distribution system, preserve the quality of the water pumped, and shall consider the availability of a power or a fuel supply.
B. The station shall be:
1. Elevated to a minimum of one foot above the 100-year flood elevation or protected to such that elevation;
2. Accessible at all times unless permitted allowed to be out of service for a period of inaccessibility by the [ commissioner department ];
3. Graded around the station so as to lead surface drainage away from the station; and
4. Protected to prevent vandalism and entrance by animals or unauthorized persons,.
5. Located with respect to availability of a power or a fuel supply.
12VAC5-590-1030. Groundwater facilities. (Repealed.)
Where pumping facilities are used, wells and springs shall be vented by properly hooded and screened pipe extending at least 12 inches above the pump floor or ground surface. Where necessary, provisions shall be made for lubricating the pump from a point at least six inches above the top of the well cover by means which will prevent contamination of the water supply.
A. General well appurtenances.
The following well appurtenances are required:
1. A sanitary seal shall be provided on the top of the well casing;
2. A properly screened vent with the end elbowed downward shall be provided for the well casing;
3. A sampling tap shall be provided for raw water sampling which discharges in a downward direction and away from the well casing;
4. Adequate control switches, etc., for the pumping equipment shall be provided;
5. A water meter is required to determine water production for each well and the meter shall be located upstream of the well blow-off;
6. The well casing shall extend at least 12 inches above the concrete floor or apron surrounding the well;
7. Adequate support for the well pump and drop pipe shall be provided; and
8. Each well casing shall be equipped with a drawdown gauge, airline, and appurtenances for measuring the change in the elevation of the water level in the well.
B. Drilled wells with the prime mover mounted on the casing shall:
1. Have the casing extend 12 inches above the floor, and be equipped with a flange or suitable sanitary seal;
2. Have the casing firmly connected to the pump structure or have the casing inserted into a recess extending at least one inch into the base of the pump if a watertight connection is not provided;
3. Have the base of the pump not less than 12 inches above the pump room floor or apron; and
4. Have the pump foundation and base designed to prevent water from coming into contact with the joint between the casing and the prime mover.
C. Submersible pumps. Where a submersible pump is used, the top of the casing shall be effectively sealed against entrance of water under all conditions of vibration or movement of conductors or cables and shall have a gooseneck vent with a screen covered opening.
D. Discharge piping. The discharge piping shall be provided with separate means to pump (blowoff) water of unsatisfactory quality to a point away from the groundwater source but shall not be directly connected to a sewer. The discharge line shall:
1. Have control valves located above the pump floor;
2. Be protected against freezing;
3. Be valved to permit testing and control of each well;
4. Have watertight joints;
5. Have all exposed valves protected; and
6. Have erosion protection at the point of waste discharge.
E. General well pump house construction requirements.
1. The well pump house floor or apron surrounding the well shall:
a. Be of good quality concrete with adequate reinforcement;
b. Be a minimum of six inches in thickness;
c. Extend a minimum of three feet in all directions from the well; and
d. Slope at least ¼ inch per foot towards a screened four inch floor drain to atmosphere.
2. Well houses or well pump stations in pits are prohibited.
3. Well pump stations housing chlorination equipment shall meet the requirements of 12VAC5-590-1000.
12VAC5-590-1040. Pump stations.
A. Pump stations associated with surface water sources, treatment facilities, and finished water shall:
1. Have adequate space for the installation of additional units if needed and for the safe servicing of all equipment;
2. Be of durable construction, fire and weather resistant, and furnished with outward opening doors;
3. Have the floor elevation at least six inches above the finished grade, if possible;
4. Have the underground structure waterproofed;
5. Have all floors drained without impairing the quality of water being handled, and, if equipment is contained on the floor, the floor shall slope at least 1/8 inch in every foot to the point of discharge; and
6. Provide suitable outlet for drainage from pump glands without discharging onto the floor.
B. Suction wells. Suction wells shall:
1. Be watertight;
2. Have floors sloped to permit removal of water and entrained solids; and
3. Be covered or otherwise protected against contamination, including contamination by pump lubricants.
C. Equipment servicing in pump stations.
1. Craneways, hoist beams, eyebolts, or other adequate facilities for servicing or removal of pumps, motors, or other heavy equipment shall be provided.
2. Walkways shall be provided to lubrication points of equipment if these are located at intermediate points between floors.
3. Openings in floors, roofs, or wherever else needed for removal of heavy or bulky equipment shall be provided.
4. A convenient tool board or other facilities shall be provided as needed for proper maintenance of the equipment.
D. Stairways and ladders. Stairs are preferred in areas where there is frequent traffic or where supplies are transported by hand. They shall have risers not exceeding nine inches and treads wide enough for safety. Where ladders are used, intermediate landings should be provided if the vertical distance exceeds 10 feet. Stairways and ladders shall:
1. Be provided between all floors and in pits or compartments which must be entered and;
2. Have handrails on both sides and treads of nonslip material.
E. Heating. In pump houses not occupied by personnel, only enough heat need be provided to prevent freezing of equipment or treatment process. Provision shall be made for adequate heating for the comfort of the operator and the safe and efficient operation of the equipment.
F. Ventilation. Adequate ventilation shall be provided for all pumping stations. Forced draft ventiliation of at least six changes of air per hour (continuous operation) shall be provided for:
1. All rooms, compartments, pits and other enclosures below the grade floor; and
2. Any area where an unsafe atmosphere may develop or where excessive heat may build up.
G. Dehumidification. In areas where excess moisture could cause hazards to safety or damage to equipment, means for dehumidification shall be provided.
H. Lighting. Pump stations shall be adequately lighted throughout. All electrical work shall conform to the requirements of the state codes.
I. Pumps. At least two pumping units shall be provided. If only two units are provided, each shall be capable of delivering the peak demand. If more than two units are installed, they shall have sufficient capacity so that if any one pump is out of service, the remaining pumps are capable of carrying the peak demand. The pumping units shall:
1. Have ample capacity to supply the peak demand without overloading;
2. Be driven by a prime mover able to operate against the maximum head and air temperature which may be encountered; and
3. Have maintenance parts and tools readily available.
J. Suction lift. If suction lift is necessary, provision shall be made for priming the pumps. Suction lift should be less than 15 feet.
K. Priming. Prime water must not be of lesser sanitary quality than that of the water being pumped. Means shall be provided to prevent back siphonage. When an air operated ejector is used, the screened intake shall draw clean air from a point at least 10 feet above the ground or other source of contamination, unless the air is filtered by an apparatus approved by the Division. Vacuum priming may be used.
A. Enclosures.
1. The structure that houses a pump shall be of durable construction, fire and weather resistant, and furnished with lockable, outward opening doors. Underground structures shall be waterproofed.
2. Floors.
a. Pump house floors shall be of good quality concrete with adequate reinforcement and have a minimum thickness of six inches.
b. Pump house floors shall slope at least 1/8 inch per foot toward a screened four-inch-diameter floor drain to the atmosphere or other provisions for gravity drainage.
c. The pump house finished floor elevation should be at least six inches above the finished grade.
3. Openings in floors or roofs or elsewhere for removal of heavy or bulky equipment shall be provided.
a. Craneways, hoist beams, eyebolts, or other adequate facilities for servicing or removal of pumps, motors, or other heavy equipment shall be provided.
b. Adequate means of access shall be provided to lubrication points of equipment if these are located at intermediate points between floors.
4. Heat shall be provided for the safe and efficient operation of the equipment.
5. Adequate ventilation shall be provided for all pumping stations. Forced draft ventilation of at least six changes of air per hour (continuous operation) shall be provided for:
a. All rooms, compartments, pits, and other enclosures below grade; and
b. Any area where an unsafe atmosphere may develop or where excessive heat may build up.
6. In areas where excess moisture could cause hazards to safety or damage to equipment, means for dehumidification shall be provided.
7. Pump stations shall be adequately lighted throughout. All electrical work shall conform to the requirements of the applicable codes.
8. Stair design shall be in accordance with the USBC.
9. Pump stations shall have adequate space for the installation of additional units if needed and for the safe servicing of all equipment.
10. Pump stations shall be designed so that each pump has an individual suction line or the lines shall be so manifolded to ensure similar hydraulic and operational conditions.
B. Suction wells shall:
1. Be watertight;
2. Have floors sloped to allow removal of water and entrained solids;
3. Be covered or otherwise protected against contamination, including contamination by pump lubricants; and
4. Have two pumping compartments or other means to allow the suction well to be taken out of service for inspection, maintenance, or repair.
C. Groundwater well enclosures and aprons.
1. The floor at the well pump house shall meet the requirements of subdivision A 2 of this section.
2. Well pump aprons surrounding the well shall (i) be of quality reinforced concrete, (ii) extend a minimum of three feet in all directions from the well casing, (iii) be at least six inches thick, and (iv) be sloped 1/8 inch per foot away from the well.
3. Well houses or well pump stations in pits are prohibited.
D. Spring enclosures shall be vented by properly hooded and screened pipe extending at least 12 inches above the pump floor or ground surface.
12VAC5-590-1050. Booster pumps Pumps and controls.
A. General.
1. Pumps, pump motors, and all accessories shall be controlled in a manner that they will operate at their rated capacity. Where two or more pumps are installed, provision shall be made for proper alternation of the pumps. Alternation may be automatic or manual. Provision shall be made to prevent operation of the pump in the event of a backspin cycle.
2. All pumps shall be driven by motors designed to operate over the full range of operating conditions.
3. All pumps shall be served by control equipment that has overload protection for the air temperature encountered.
4. Electrical controls shall be protected to the 100-year flood elevation and should be located above grade.
5. If standby power is provided by onsite generators or engines, then the provisions for filling the fuel storage tank, the fuel tank itself, and the fuel line shall be designed to protect the waterworks and source water from contamination.
6. Pumps shall be lubricated with water of equal or better quality than the water being pumped or with food grade oil. Water seals shall not be supplied with water of a lesser sanitary quality than that of the water being pumped. Where pumps are sealed with potable water and are pumping water of lesser sanitary quality, the seal shall:
a. Have an air gap of at least two inches or two pipe diameters, whichever is greater, where a break-tank is provided; or
b. Be provided with an approved RPZ assembly.
7. When automatic pre-lubrication of pump bearings is necessary and an auxiliary power supply is provided, the pre-lubrication line shall be provided with a valved bypass around the automatic control.
8. A suitable outlet for drainage from pump glands shall be provided without discharging onto the floor.
A. B. Booster pumps,.
1. Booster pumps, except those connected to supply mains not containing service connections and except those taking suction directly from storage facilities, shall be located or controlled so that:
1. a. They will not produce negative gauge pressure in their suction line; and
2. b. The intake pressure shall be at least 20 psi when the pump is in normal operation;.
3. 2. An automatic pressure cutoff or a pressure regulating pressure-regulating valve shall be provided to prevent the suction line pressure from dropping to below 10 psi; and.
4. 3. Automatic or remote control devices shall have a sufficient range between the start and cutoff pressure, or another mechanism which that will prevent excessive cycling of the pumps.
B. Inline booster pumps. In addition to the other requirements of this section, inline booster pumps shall be accessible for servicing and repairs.
4. At least two pumping units shall be provided.
a. If only two units are provided, then each shall be capable of delivering the peak hour demand, taking into account storage contributions.
b. If more than two units are installed, then they shall have sufficient capacity so that if any one pump is out of service, the remaining pumps are capable of meeting the peak hour demand, taking into account storage contributions.
c. When using booster pumps to transfer water from atmospheric storage tanks to hydropneumatic tanks located upstream of an entry point into the distribution system, the combined capacity of the two pumps shall equal or exceed the peak hour demand. If fire flow is provided, then a pump separate from the transfer pumps shall be provided to deliver the required fire flow.
d. When booster pumping is required for small noncommunity systems, the reserve capacity requirements may be reduced in accordance with the type and size of system served.
5. Controls shall be provided to shut off pumps in the event that suction conditions may result in cavitation.
12VAC5-590-1060. Automatic and remote controlled stations. (Repealed.)
All automatic stations should be provided with an automatic signaling apparatus which will report to a facility manned 24 hours per day when the station is out of service. All remote controlled stations shall be electrically operated and controlled and shall have a signaling apparatus of proven performance. Installation of electrical equipment shall conform with the appropriate state codes.
12VAC5-590-1065. Piping, valves, and meters.
A. Piping shall:
1. Be adequately sized to minimize energy losses;
2. Not be subject to contamination;
3. Have watertight joints;
4. Be properly anchored to prevent movement;
5. Be protected against surge or water hammer;
6. Have proper labels to identify the contents of the pipes (12VAC5-590-720 C); and
7. Have all exposed piping, valves, and appurtenances protected against physical damage and freezing.
B. Pumps shall be adequately valved to allow satisfactory operation, maintenance, and repair.
1. If foot valves are necessary, then they shall have a net valve area of at least 2-1/2 times the area of the suction pipe and they shall be screened.
2. Each pump shall have shutoff valves on both suction and discharge sides of the pump.
3. Each pump shall have a positive-acting check valve on the discharge side between the pump and shutoff valve or suitable control features to prevent flow reversal.
4. Surge relief valves or slow-acting check valves shall be designed to minimize hydraulic transients.
5. Discharge control valves and appurtenances shall be located above the pump floor when an above-ground discharge is provided.
6. Pumps shall be equipped with an air release or vacuum relief valve located upstream from the check valve, with exhaust or relief piping terminating in a down-turned position at least 18 inches above the floor and covered with a corrosion-resistant screen.
C. Gauges. Each pump shall have a standard pressure gauge on its discharge line capable of displaying the maximum allowable pressure of the pump and shall have a standard pressure gauge or a compound gauge when appropriate on its suction line.
D. Meters.
1. All booster pump stations located within the distribution system should be fitted with a flow rate indicating and totalizing meter with recording capabilities.
2. A totalizing water meter to measure water production shall be provided for each well and shall be located upstream of the well blowoff.
E. Additional requirements for well discharge piping.
1. Valves shall be provided to allow testing and control of each well.
2. A nonthreaded sampling tap shall be provided for water sampling that discharges in a downward direction and away from the well casing.
3. A standard pressure gauge shall be provided to indicate well discharge pressure. The gauge shall be capable of displaying pressure under all operating conditions.
4. Blowoff.
a. A separate means to pump (i.e., blowoff) water of unsatisfactory quality to a point away from the groundwater source shall be provided. Blowoff discharge shall not create a cross-connection.
b. Systems shall be equipped with a watertight cap or a screened discharge.
c. Erosion protection at the point of waste discharge shall be provided.
12VAC5-590-1070. Appurtenances. (Repealed.)
A. Valves.
Pumps shall be adequately valved to permit satisfactory operation, maintenance, and repair of the equipment. If foot valves are necessary, they shall have a net valve area of at least two and one half times the area of the suction pipe and they shall be screened. Each pump shall have a positive acting check valve on the discharge side between the pump and shutoff valve.
B. Piping, in general, shall:
1. Be designed so that the friction head will be low;
2. Not be subject to contamination;
3. Be sloped in one direction to drains;
4. Have adequate cleanouts;
5. Have watertight joints;
6. Be protected against surge or water hammer;
7. Be such that each pump has an individual suction line or the lines shall be so manifolded that they will insure similar hydraulic and operational conditions; and
8. Have proper legends to identify the contents of the pipes (see 12VAC5-590-720 L).
C. Gauges and meters.
The station should have indicating, totalizing, and recording metering of the total water pumped. Each pump shall:
1. Have a standard pressure gauge on its discharge line;
2. Have a compound gauge on its suction line; and
3. Have recording gauges in the larger stations as required by the division.
D. Water seals.
Water seals shall not be supplied with water of a lesser sanitary quality than that of the water being pumped. Where pumps are sealed with potable water and are pumping water of lesser sanitary quality, the seal shall:
1. Be provided with a break tank open to atmospheric pressure; and
2. Have an air gap between feeder line and spill line of the tank, at least two inches or two pipe diameters, whichever is greater.
E. Controls.
Pumps, their prime movers, and all accessories shall be controlled in such a manner that they will operate at their rated capacity without overloading. Where two or more pumps are installed, provision shall be made for proper alternation. Alternation may be automatic or manual. Provision shall be made to prevent operation of the pump during the backspin cycle. Electrical controls should be located above grade.
F. Power.
When power failure would result in cessation of the minimum essential service, the power supply shall be provided from at least two independent sources or an auxiliary source shall be provided.
G. Auxiliary power supply.
When automatic prelubrication of pump bearings is necessary and an auxiliary power supply is provided, the prelubrication line shall be provided with a valved by-pass around the automatic control.
Article 5
Finished Water Storage Structures
12VAC5-590-1080. General Basic finished water storage structure design criteria.
A. The materials and designs used for finished water storage structures, including associated pipe and valves, shall provide stability and durability as well as protect the quality of the stored water. Steel structures shall follow the current available American Water Works Association standards concerning steel tanks, standpipes, reservoirs, and elevated tanks wherever they are applicable. Other materials of construction are acceptable when properly designed to meet the requirements of this section. Steel, concrete, composite, and plastic storage structures shall be designed, constructed, cleaned, disinfected, and tested in accordance with the following AWWA standards, where applicable: D100-11, [ D103-09 D103-19 ], D107-16, [ D108-10 D108-19 ], D110-13, [ D115-06 D115-20 ], [ D120-09 D120-19 ], D121-12, and [ C652-11 C652-19 ].
B. Safety cages, rest platforms, roof-ladder handrails, and other safety devices shall be provided as required by VOSH laws and regulations.
A. C. Location of finished water storage structures facilities.
1. The bottom of ground level ground-level reservoirs, storage tanks, and standpipes should be placed at the normal ground surface above finished grade to ensure positive drainage away from the structure.
2. Where the bottom must be below normal ground surface, it shall be placed above the groundwater table. Sewers, drains, standing water, and similar sources of contamination shall be kept at least 50 feet from the reservoir finished water storage structure. AWWA approved water pipe Pipe conforming to water distribution pipe standards of 12VAC5-590-1110, pressure tested in place without leakage, shall be used for gravity sewers at lesser separations.
3. The top of all storage facilities shall not be less than two feet above the normal ground surface and shall be above the 100-year flood level elevation. Clearwells Any clearwell constructed under filters may be excepted exempted from this requirement when the total design gives the same protection.
B. All new finished water storage structures shall have suitable watertight roofs or covers which exclude birds, animals, insects, and dust.
C. No drain on a water storage structure shall have a direct connection to a sewer or storm drain.
All finished water storage structures shall be equipped with separate drains discharging to the atmosphere. Drainage of finished water storage structures to the distribution system through inlet and outlet piping shall not be allowed.
D. The overflow pipe of a finished water storage structure shall be brought down near the ground surface where any discharge will be visible and into a drainage inlet structure or a splash plate which will divert the overflow away from the storage structure. No overflow may be connected directly to a sewer or storm drain.
1. When an internal overflow pipe is used it shall be located in the access tube.
2. The overflow of a ground level finished water storage structure shall be high enough above normal or graded ground surface to prevent the entrance of surface water.
3. All nonpressure type finished water storage structures shall be provided with a downward discharging screened overflow.
E. Finished water storage structures shall be designed with convenient access to the interior for cleaning and maintenance. Manholes or scuttles above the waterline shall be:
1. Framed at least four inches, preferably six inches, above the surface of the roof at the opening; on ground level structures, manholes should be elevated 24 to 36 inches above the top or covering sod;
2. Fitted with a solid watertight cover which overlaps the framed opening and extends vertically down around the frame at leas two inches (shoebox type);
3. Hinged at one side; and
4. Fitted with a locking device.
F. Finished water storage structures shall be vented by separate vent structures. Open construction between the side wall and roof is not permissable.
1. Vents shall prevent the entrance of surface water.
2. Vents shall exclude birds and animals.
3. Vents shall exclude insects and dust, as much as this function can be compatible with effective venting, for elevated tanks and standpipes, four-mesh noncorrodible screen may be used.
4. Vents on ground level structures shall terminate in an inverted U construction the opening of which is 24 to 36 inches above the roof or sod and is covered with noncorrodible screen cloth to exclude insects.
G. The roof and sidewalls of all structures must be watertight with no openings except properly constructed vents, manholes, overflows, risers, drains, pump mountings, control ports, or piping for inflow and outflow.
1. Any pipes running through the roof or sidewall of a finished water storage structure must be welded or properly gasketed in metal tanks or should be connected to standard wall castings which were poured in place during the forming of a concrete structure; these wall castings shall have flanges imbedded in the concrete.
2. Openings in a storage structure roof or top designed to accommodate control apparatus or pump columns shall be curbed and sleeved with proper additional shielding and shoebox type cover to prevent the access of surface water into the structure.
3. Valves and controls shall be located outside the storage structure so that valve stems and similar projections will not pass through the roof or top of the structure.
H. The roof or cover of the storage structure should be well drained, but downspout pipes shall not enter or pass through the reservoir.
I. The safety of employees shall be considered in the design of the storage structure. As a minimum, such matters shall conform to pertinent building codes, laws, and regulations of the area where the reservoir is constructed.
1. Ladders, ladder guards, balcony railings, and safe location of entrance hatches shall be provided.
2. Elevated tanks with riser pipes over eight inches in diameter shall have protective bars over the riser opening inside the tank.
J. All finished water storage structures and their appurtenances, especially the riser pipes, overflows, and vents, shall be designed to prevent freezing which will interfere with proper functioning.
K. Every catwalk over finished water in a storage structure shall have a solid floor with raised edges so designed that shoe scrapings and dirt will not fall into the water.
L. The area surrounding a ground level structure should be graded in a manner that will prevent surface water from standing within 50 feet of the structure.
M. Proper protection should be given to metal surfaces by paints or other protective coatings, by cathodic protective devices, or both. Paint systems consistent with the most current available American Water Works Association standards and otherwise acceptable to the division shall be used. Cathodic protection should be designed and installed by competent technical personnel.
N. All finished water storage facilities shall be cleaned to remove all dirt and loose materials prior to disinfection of the structure. Only potable water shall be used to clean and rinse the water storage facilities. All equipment including brooms, brushes, spray equipment and workmen's boots shall be disinfected before they are used to clean the storage facilities.
O. All finished water storage facilities shall be satisfactorily disinfected prior to being placed in operation. The disinfection of the storage facilities shall be repeated until it is determined, by bacteriological testing, that the water is free of coliform bacteria.
1. One of the following disinfection methods shall be used. Other methods of disinfection may be approved on a case-by-case basis by the division.
a. The tank shall be filled to the overflow level with potable water to which enough chlorine has been added to produce an initial chlorine concentration of 50 mg/L in the full tank. The full tank should stand for 24 hours; however, in no case shall it stand less than six hours. At the end of the holding period, the chlorinated water shall be drained to waste, the tank refilled with potable water, and tested for satisfactory bacteriological quality before placing the tank in service.
b. All interior surfaces of the tank shall have applied a chlorine solution containing at least 200 mg/L of free available chlorine. The chlorine solution shall be applied with either spray equipment or brushes. Any equipment used to apply the chlorine solution shall either be new or previously used only for disinfection purposes. The chlorine solution shall remain in contact with the tank surfaces for at least 30 minutes. The tank shall then be filled with potable water to the overflow level and tested for satisfactory bacteriological quality before placing the tank in service; or
c. Potable water containing a free chlorine residual of 50 mg/L shall be placed in the tank to such a depth that when the tank is filled, the resulting chlorine concentration in the water will be at least two mg/L. The water containing 50 mg/L of chlorine shall stand in the tank for 24 hours. The tank shall then be filled with potable water and allowed to stand for 24 additional hours. At the end of the second 24 hour period, the chlorine residual shall be at least two mg/L. After analyses of the water for satisfactory bacteriological quality, the tank may be placed in service without draining the water used to disinfect it.
2. Testing of the water following disinfection shall be in accordance with 12VAC5-590-800 C.
D. Pressure variation. The maximum variation between normal operational high and low water levels in finished water storage structures which float on a distribution system shall not exceed 30 feet.
E. Level controls.
1. Adequate controls shall be provided to enable sufficient tank turnover, water quality maintenance, avoidance of overflows, and efficient operations.
2. A telemetery system with recording capability shall be considered to transmit the operating levels in distribution system storage facilities to a location where qualified personnel may access the data at all times.
3. Altitude valves or equivalent controls shall be provided.
4. For tanks with a monitoring system, warnings or alarms indicating overflow, low level, and pump malfunction shall be provided.
12VAC5-590-1081. Atmospheric tank storage.
A. Protection.
1. All finished water storage structures shall have suitable watertight roofs or covers that exclude birds, animals, and insects.
2. All finished water storage structures shall be designed to prevent vandalism and entrance by animals or unauthorized persons.
B. Finished water storage structures shall be designed to facilitate turnover of water. Consideration shall be given to locating inlet and outlet pipes at different elevations and locations, tank mixers, and other acceptable means to avoid stagnation. Excessive storage capacity shall be avoided to prevent water quality deterioration. See 12VAC5-590-640 B 3.
C. Drains.
1. No drain on a finished water storage structure shall create a cross-connection hazard.
2. All finished water storage structures shall be equipped with separate drains discharging to the atmosphere. Drainage of finished water storage structures to the distribution system through inlet and outlet piping is prohibited.
D. Overflows.
1. Finished water storage structures shall be provided with a downward-discharging, screened overflow pipe. The discharge pipe shall be brought down near the ground surface and into a drainage inlet structure or a splash plate that will divert the overflow away from the storage structure. The overflow pipe discharge shall be high enough above normal or graded ground surface to prevent the entrance of surface water.
2. Overflow pipe screens shall be installed so as to withstand the force of overflows. Properly designed flapper valves or rubber flex-type valves may be used instead of screens if approved by the [ commissioner department ].
E. Inlet and discharge pipes.
1. Elevated tanks with riser pipes over eight inches in diameter shall have protective bars over the riser opening inside the tank.
2. Inlet and outlet pipes from water storage facilities shall be located in a manner that will prevent the flow of sediment into the distribution system.
F. Finished water storage structures shall be designed with convenient access to the interior for cleaning and maintenance. Ladders, ladder guards, balcony railings, and safely located entrance hatches shall be provided where applicable. Hatches, manholes, or scuttles above the waterline shall be:
1. Framed at least four inches, preferably six inches, above the surface of the roof at the opening; on ground-level structures, manholes should be elevated 24 to 36 inches above finished grade;
2. Fitted with a solid watertight cover that overlaps the framed opening and extends vertically down around the frame at least two inches (shoebox type);
3. Hinged at one side; and
4. Fitted with a locking device.
G. Finished water storage structures shall be vented by separate vent structures. Open construction between the side wall and roof is prohibited.
1. Vents shall prevent the entrance of surface water.
2. Vents shall exclude birds, animals, and insects and be constructed of noncorrodible material. Screens shall be designed to be frost-free or capable of relieving pressure or vacuum in the event of frosting or clogging.
3. Vents on ground-level structures shall terminate in an inverted U construction, with the vent terminating 24 to 36 inches above roof or finished grade.
H. Penetrations. The roof and sidewalls of all structures shall be watertight with no openings except properly constructed vents, manholes, overflows, risers, drains, pump mountings, control ports, or piping for inflow and outflow.
1. All pipes running through the roof or sidewall of a finished water storage structure shall be welded or properly gasketed in metal tanks or should be connected to standard wall castings that were placed during the forming of a concrete structure; these wall castings shall have flanges imbedded in the concrete.
2. Valves and controls shall be located outside the finished water storage structure so that valve stems and similar projections will not pass through the roof or top of the structure.
3. Downspout pipes for roof drainage shall not enter or pass through the structure.
I. All finished water storage structures and their appurtenances, especially the riser pipes, overflows, and vents shall be designed to prevent freezing that will interfere with proper functioning.
J. Every catwalk over finished water in a storage structure shall have a solid floor with raised edges designed so that shoe scrapings and dirt will not fall into the water.
K. The area surrounding a ground-level structure shall be graded in a manner that will prevent surface water from standing within 50 feet of the structure.
L. Proper protection shall be given to metal surfaces by paints or other protective coatings, by cathodic protective devices, or both, in accordance with the [ NSF/ANSI Standard 61-2016NSF/ANSI/CAN Standard 61-2020 ], AWWA Standards [ D102-14 D102-17 ], [ D104-11 D104-17 ], and [ D106-16 D106-20 ], or an approved equivalent, where applicable.
M. All finished water storage facilities shall be cleaned to remove all dirt and loose materials before disinfection of the structure. Only potable water shall be used to clean and rinse the water storage facilities. All equipment including brooms, brushes, spray equipment, and worker's boots shall be disinfected before they are used to clean the storage facilities.
N. Disinfection. All finished water storage facilities shall be satisfactorily disinfected in accordance with AWWA Standard [ C652-11 C652-19 ] before being placed in operation. The disinfection of the storage facilities shall be repeated until it is determined, by bacteriological testing, that the water is free of coliform bacteria.
12VAC5-590-1082. Pressure tank storage.
[ A. ] When hydropneumatic tanks are used, they shall comply with the requirements of state and local laws and regulations for the construction and installation of unfired pressure vessels.
[ 1. B. ] Pressure tanks shall be located above the normal ground surface with the operating end of the tank containing the inlet pipe, the pressure gauge, and other appurtenances projecting into a building with climate controls to prevent freezing. Alternatively, it may be completely housed, if adequate access is provided for inspection, removal, and replacement.
[ 2. C. ] Pressure tanks shall have bypass piping to permit operation of the system while the tank is being cleaned, repaired, or painted.
[ 3. D. ] Pressure tanks shall have an access manway, a drain, and control equipment consisting of a pressure gauge, water sight glass, automatic or manual air blowoff, pressure and vacuum relief valves, and mechanical means for adding air. Pressure tanks smaller than than 120 gallons and bladder tanks are not required to have an access manway, sight glass, or vacuum relief valve.
[ 4. E. ] Pressure tanks and pumps shall be designed to minimize pump cycling and to operate within manufacturer recommendations.
12VAC5-590-1090. Plant storage.
The applicable design standards of 12VAC5-590-1080 shall be followed for plant storage.
A. Washwater Backwash water storage tanks shall be sized in conjunction with available pump units and finished water storage to give provide the filter backwash water required. Consideration must shall be given to the possibility of having to wash more than one filter at a time or several filters in succession.
B. Clearwell storage should shall be sized, in conjunction with distribution system storage, to relieve the filters from having to follow fluctuations in water use or meet peak demands, including filter backwash water. When finished water storage is used to provide proper contact time for chlorine disinfection, special attention must shall be given to size, drawdown, and baffling. Plant clearwells shall be equipped with a raised viewing port having a clear glass or plastic viewing window and a submerged waterproof, waterproofed electric light.
C. Finished water shall not be stored or conveyed in a compartment adjacent to unsafe nonpotable water when the two compartments are separated by a single wall.
D. Receiving basins and pump wet wells for finished water shall be designed as finished water storage structures.
E. Hydropneumatic (pressure) tanks may be acceptable in small water systems. When used, they shall comply with the requirements of state and local laws and regulations for the construction and installation of unfired pressure vessels.
1. The tank shall be located above the normal ground surface with the tank end containing the inlet pipe, the pressure gauge and other appurtenances projecting into an operating house to prevent freezing or be completely housed.
2. The tank shall have bypass piping to permit operation of the system while the tank is being cleaned, repaired, or painted.
3. Pressure or level-pressure operated start-stop controls shall be installed on the discharge piping to permit operation of the water supply system.
4. Each tank shall have an access manhole, a drain, and control equipment consisting of pressure gauge, water sight glass, automatic or manual air blowoff, pressure and vacuum relief valves and mechanical means for adding air. Appurtenances to small capacity tanks shall be determined by the division on a case-by-case basis.
5. Tanks and pumps shall be designed to minimize pump cycling and shall have at least the following capacity:
a. When the hydropneumatic tank is fed directly by a well or wells, the effective storage volume is one-third of the hydropneumatic tank's gross volume;
b. When the hydropneumatic tank is fed directly from ground storage, the effective storage volume is the effective volume of the ground storage tank plus the effective volume of the hydropneumatic tank; and
c. At least two booster or transfer pumps are required which have a combined capacity to meet the requirements of 12VAC5-590-690 C.
12VAC5-590-1100. Distribution storage. (Repealed.)
The applicable design standards of 12VAC5-590-1080 shall be followed for distribution storage.
A. The maximum variation between high and low water levels in finished water storage structures which float on a distribution system should not exceed 30 feet. Large diameter, shallow-depth reservoirs are preferable over small diameter, deep-depth reservoirs.
B. Adequate controls shall be provided to maintain levels in distribution system storage structures at all times.
C. Pressure tanks. (Also see 12VAC5-590-1090 E.)
1. A telemetering system and recording equipment should be provided, to a location where qualified personnel are available at all times, for the transmission and recording of storage levels in the distribution system.
2. Altitude valves or equivalent controls may be required for subsequent structures on the system.
3. Overflow, low level, and pump malfunction warnings or alarms should be transmitted to a location where qualified personnel are available for surveillance on a 24-hour basis.
Article 6
Water Distribution Systems
12VAC5-590-1110. Materials Distribution system materials.
A. The pipe selected shall have been manufactured in conformity with the current available standards issued by the American Water Works Association if such standards exist or be approved by the National Sanitation Foundation for water distribution piping.
B. In the absence of such standards, pipe meeting applicable commercial standards and acceptable to the division may be considered.
C. Used water mains that meet these standards may be used again after the pipe has been thoroughly cleaned and restored.
D. Packing and joint materials used in the joints of pipe shall meet the standards of the American Water Works Association or the National Sanitation Foundation.
E. Mechanical joints or slip joints with resilient gaskets are preferred.
Pipe, fittings, joints, valves, hydrants, and coatings shall conform to AWWA standards.
12VAC5-590-1120. Minimum pipe size.
A. The minimum size pipe for water distribution systems mains shall be four inches in diameter. Pipes of lesser diameter may be used in the following instances:
1. When the run is less than 300 feet, two-inch diameter pipe may be used; and.
2. When the run is less than 600 feet but more than 300 feet, three-inch diameter pipe may be used.
3. Any departure in sizing shall be justified by hydraulic analysis and future water demands.
B. The minimum size of pipe where fire protection is to be provided or required shall be six inches in diameter. Fire hydrants shall not be connected to water mains that are not designed to carry fire flows. Connection of a fire hydrant to a pipe of less than six inches in diameter is prohibited.
C. The standard grading schedule of the Insurance Services Office and other related organizations shall be followed in other cases.
D. Any departure in sizing shall be justified by hydraulic analysis and future water use and can be considered only in special circumstances.
E. Water mains not sized to carry fire flows shall not be connected to fire hydrants. C. Where a noncommunity waterworks serves a single building, the plumbing shall be in accordance with the USBC. Where a noncommunity waterworks serves two or more buildings, the pipe shall be of sufficient size to provide adequate flow and pressure in order to meet the system demands.
12VAC5-590-1130. System Distribution system design.
A. Dead-ends should be minimized by the looping of all water mains.
B. Where dead-end lines water mains occur, they shall be provided with a fire hydrant, flushing hydrant, or blowoff for flushing purposes a means of effective flushing shall be provided.
C. No flushing device shall be directly connected to any sewer.
12VAC5-590-1140. Installation and testing of water mains.
A. Adequate supports and restraints shall be provided for all pipes.
B. A continuous and uniform bedding shall be provided in the trench for all buried pipe.
C. Stones and rocks found in the trench shall be removed for to a depth of at least six inches below the bottom of the pipe and selected fill bedding provided.
D. The specifications for installation shall include:
1. Pressure testing on installed pipe;
2. Allowable leakage of installed pipe; and
3. Reference to applicable American Water Works Association standards or manufacturers' recommended installation procedures D. Installed pipe shall be pressure-tested and meet allowable leakage as specified in accordance with AWWA Standards [ C600-10 C600-17 ], [ C604-11 C604-17 ], and C605-13, where applicable.
E. Any plastic or other nonmetallic pressurized conduit pipe installed underground shall have affixed thereto be provided with a material conductive of electricity or some other means of locating the conduit while it is underground buried pipe.
12VAC5-590-1150. Separation of water mains and sanitary sewers.
A. The following factors shall be considered in providing adequate separation of water mains and sanitary sewers:
1. Materials and types of joints for water and sanitary sewer mains;
2. Soil conditions;
3. Service branch connections into the water main and sanitary sewer mains;
4. Compensating variations in the horizontal and vertical separations;
5. Space for repairs and alterations of water and sanitary sewer mains;
6. Offsetting of pipes around manholes; and
7. Identification of the physical restraints preventing normal separation.
B. Parallel installation of water mains and sanitary sewers.
1. Under normal conditions, water mains shall be laid at least 10 feet horizontally from a sanitary sewer or sewer manhole. The distance shall be measured edge-to-edge.
2. Under unusual conditions situations when local conditions prevent a horizontal separation of 10 feet, the water main may be laid closer to a sanitary sewer or sewer manhole provided that:
a. The bottom (invert) of the water main shall be at least 18 inches above the top (crown) of the sanitary sewer;
b. Where this vertical separation cannot be obtained, the sanitary sewer shall be constructed of, AWWA approved water pipe water distribution pipe and pressure tested in place without leakage prior to backfilling; and in accordance with 12VAC5-590-1110 and 12VAC5-590-1140;
c. The [ commissioner department ] may approve concrete encasement of the water main or other physical barrier;
d. The sewer manhole shall be of watertight construction and tested in place; and
e. No water pipes shall pass through or come into contact with any part of a sewer manhole.
C. Crossing of water mains and sanitary sewers.
1. Under normal conditions, water lines mains crossing sanitary sewers shall be laid to provide a separation of at least 18 inches between the bottom of the water line main and the top of the sanitary sewer whenever possible.
2. Under unusual conditions situations when local conditions prevent a vertical separation described in subdivision C 1 of this section, the following construction shall be used:
a. Sewers Sanitary sewers passing over or under water mains shall be constructed of the materials described in subdivision B 2 b subsection B of this section and shall be constructed to a point 10 feet beyond and on each side of the crossing; and
b. Water lines mains passing under sanitary sewers shall, in addition, be protected by providing:
(1) A vertical separation of at least 18 inches between the bottom of the sanitary sewer and the top of the water line main;
(2) Adequate structural support for the sanitary sewers to prevent excessive deflection of the joints and the settling on and breaking of the waterline water main; and
(3) That the length of the water line main be centered at the point of the crossing so that joints shall be equidistant and as far as possible from the sanitary sewer.
D. No water pipes shall pass through or come in contact with any part of a sewer manhole. The minimum horizontal separation distance between water mains and septic tanks and drainfields, measured edge-to-edge, shall be 10 feet. Greater separation distances shall be provided wherever practical.
E. Water mains shall be located a safe horizontal distance from sources of contamination not already mentioned in this section, such as sewage treatment works and industrial complexes. The owner's engineer shall contact the department to determine the safe separation distances.
12VAC5-590-1160. Valve, air relief, meter, and blowoff chambers.
A. Air and sediment accumulations may be removed through a standard fire hydrant; compressed air and pumping may be used for dewatering mains through hydrants. Standard fire hydrants or blowoffs shall be considered to enable removal of sediment and air accumulations.
B. Chambers Drains in chambers or pits containing that contain valves, blowoffs, meters, or other such appurtenances to a distribution system shall not be connected directly to any storm drain or sanitary sewer, nor shall blowoffs or air relief valves be connected directly to any sanitary sewer.
C. Such chambers Chambers or pits shall be drained to the surface of the ground where they are not subject to flooding by surface water or to absorption pits located above the seasonal groundwater table elevation. The backfill material for the water main may serve as an absorption pit if granular embedment material is laid from the pipe bedding up through the final backfill layer for the entire length of pipe in the chamber. Sump pumps may be used where other means are not practicable.
D. Chambers or pits shall be designed to facilitate air-valve inspection and servicing.
E. Air relief and blowoff piping.
D. 1. The open end of an air relief pipe shall be extended from the manhole or enclosing chamber to a point at least one foot above ground and provided with a screened, downward facing elbow. The exposed pipe and appurtenances shall be protected from vandalism and other damage.
2. When an aboveground extension is not practical or desired, the open end of the air relief pipe or blowoff shall be extended.
a. Where the pit or chamber is provided with proper drainage and is not otherwise subject to high groundwater levels, surface flooding, ponding, and contaminant or pollutant spills, the open end may be provided with a screened, downward facing elbow. The valve chamber or pit shall be vented to provide sufficient air flow to allow proper operation of the air valve. Air valves fitted with a smooth vent port and screened hood are allowable under these conditions.
b. Where the pit or chamber is not properly drained or is otherwise subject to high groundwater levels, surface flooding, ponding, and contaminant or pollutant spills, a manually operated valve or blowoff shall be used and the open end shall be fitted with a watertight cap or other means to prevent contamination from entering the pipe and valve.
c. The installation and testing specifications shall require field verification by the owner's engineer of the groundwater elevation and surface water drainage [ prior to, as needed in circumstances or situations where this is of potential concern, before ] placement of the pit or chamber.
12VAC5-590-1170. Hydrants.
A. [ Where hydrant drains are not plugged, they shall be drained to the ground surface or to dry wells provided exclusively for this purpose in a manner that will avoid contamination of the hydrant or water main from high groundwater, surface flooding and ponding, and contaminant or pollutant spills Fire hydrants.
1. To avoid cross-connection and contamination, dry barrel fire hydrants:
a. Should be located in areas that are not subject to high groundwater, flooding, surface water ponding, and contaminant or pollutant spills. When this is not practical, consideration shall be given to:
(1) Piping the drain port to daylight with screening on the end of the pipe; or
(2) Plugging the drain port and marking the hydrant for seasonal dewatering.
b. Shall comply with the ANSI/AWWA C502-18 standard, to include drain ports that are physically isolated from the drinking water system by the hydrant stem valve; and
c. Shall be drained to the ground surface or to a dry well provided exclusively for this purpose. Fire hydrant drains shall not be connected to sanitary sewers or storm drains. ]
[ B. Hydrant drains shall not be connected to sanitary sewers or storm drains.
C. 2. ] Fire hydrants shall be connected only to water systems mains adequately designed for fire flows in addition to domestic flow in accordance with the requirements of 12VAC5-590-1120 B.
[ B. Yard hydrants.
1. Shall have a hose connection vacuum breaker, meeting ASSE 1011-2017 or ASSE 1052-2016, if the hydrant has hose threads and is not already protected with an integral vacuum breaker.
2. To avoid cross-connection and contamination, yard hydrants installed in areas subject to high groundwater, flooding, contaminant, or pollutant spills or in areas where surface water ponds shall:
a. Meet ASSE 1057-2012, Performance Requirements for Freeze Resistant Sanitary Yard Hydrants with Backflow Protection; or
b. Have hydrant drain ports that are piped to daylight with screening on the end of the pipe; or
c. Be contained from the rest of the distribution system by a backflow prevention assembly suitable for a high hazard.
3. Frost-proof yard hydrants with weep holes draining below grade are allowed provided they are not installed in areas subject to high groundwater, to flooding, or to contaminant or pollutant spills or in areas where surface water ponds.
C. Hydrants and flushing devices not designed for fire protection may be connected to pipe of less than six inches in diameter, consistent with 12VAC5-590-1120 A. ]
12VAC5-590-1180. Surface water crossings.
A. Surface water crossings, both over and under water, present special problems and should challenges and shall be discussed with the division department before final plans project documents are prepared.
A. Above B. Aerial water crossings. The pipe above water crossings shall be:
1. Adequately supported;
2. Protected from freeze damage;
3. Accessible for repair or replacement; and
4. Above the 100-year flood level elevation.
B. C. Under water crossings.
1. The pipe shall be of special construction, suitable to the method of installation and having flexible watertight joints.
2. Valves Where rigid pipe is used, valves and taps shall be provided at both ends of the water crossing so that the section can be isolated for tests or repair; the valves and taps shall be easily accessible and not subject to flooding.
3. Sample taps shall be available at each end of the crossing and at a reasonable distance from each side of the crossing and not subject to flooding.
4. Permanent taps shall be made for testing and locating leaks.
12VAC5-590-1190. Water services and plumbing. (Repealed.)
Water services and plumbing shall conform to the Uniform Statewide Building Code.
12VAC5-590-1200. Water pressure in systems. (Repealed.)
The system shall be designed to maintain a minimum pressure of 20 psi in the distribution system at the design flow (see 12VAC5-590-690 C). Where the pressure at the service tap exceeds 80 psi, the provisions of the Uniform Statewide Building Code shall apply.
12VAC5-590-1210. Disinfection and testing of water mains.
A. All water mains shall be disinfected prior to in accordance with AWWA Standard C651-14 before being placed in operation. The disinfection of the mains shall be repeated until it is determined by bacteriological testing that the water is free of coliform bacteria.
B. Prior to disinfection all water mains shall be flushed unless the tablet method of disinfection is used. All valves and hydrants shall be operated during this operation. Flushing velocities should not be less than 2.5 feet per second.
C. Methods of chlorine application.
1. Continuous feed method - Potable water shall be introduced into the pipe main at a constant flow rate. Chlorine shall be added at a constant rate to this flow so that the chlorine concentration in the water in the pipe is at least 50 mg/L. The chlorinated water shall remain in the main at least 24 hours, after which, the chlorine concentration in the water shall be at least 10 mg/L. All valves and appurtenances shall be operated while the chlorinated water remains in the main;
2. Slug method - Potable water shall be introduced into the main at a constant flow rate. This water shall receive a chlorine dosage which will result in a chlorine concentration of 100 mg/L in a "slug" of the water. The chlorine shall be added long enough to insure that all portions of the main are exposed to the 100 mg/L chlorine solution for at least three hours. The chlorine residual shall be checked at regular intervals not to exceed 2,000 feet to insure that adequate residual is maintained. As the chlorinated water passes valves and appurtenances, they shall be operated to insure disinfection of these appurtenances; or
3. Tablet method - Tablets shall be placed in each section and in all appurtenances. Enough tablets shall be used to insure that a chlorine concentration of 25 mg/L is provided in the water. They shall be attached by an adhesive to the top of the pipe sections and crushed or rubbed in all appurtenances. The adhesive shall be acceptable to the division. The velocity of the potable water in the main shall be less than 1 foot per second. The water shall then remain in contact with the pipe for 24 hours. All valves and appurtenances shall be operated while the chlorinated water is in the main.
This method shall not be used if nonpotable water or foreign materials have entered the mains or if the water temperature is below 5°C (41°F).
D. Final flushing. After the required retention period, the chlorinated water shall be flushed from the main using potable water.
E. Testing. After the mains have been flushed, the water mains shall be tested in accordance with 12VAC5-590-800 C. Samples shall be collected at regular intervals, not exceeding 2,000 feet, throughout the length of main.
F. Repairs. Cleaning, disinfecting, flushing, testing, or similar operational actions shall be in accordance with the current standard issued by AWWA (AWWA C-601). B. Project documents shall provide the details of the procedure and include the disinfectant application technique, dosage, contact time, method of testing the results of the procedure, and use or disposal of the disinfecting water.
12VAC5-590-1220. Cover Pipe cover.
All distribution mains buried distribution pipe shall be provided with sufficient earth or other suitable cover or encasement to prevent from freezing and provide protection from damage by external forces.
12VAC5-590-1230. Metering. Service connection metering.
Each service connection should A. All new service connections in community waterworks shall be metered.
B. Water pipe and appurtenances between the water main and the service connection shall conform to all applicable codes.
12VAC5-590-1235. Water loading stations.
A. The station and its piping and valving arrangement shall be designed to prevent unauthorized use, tampering, and vandalism.
B. An air gap or RPZ assembly shall be provided on the potable water fill connection to prevent backflow into the waterworks.
C. The piping and valving arrangement shall prevent contaminants from being transferred from a hauling tank or vessel to others subsequently using the water loading station.
D. Hoses used to fill potable water tanks and vessels shall be approved for potable water contact.
E. Hoses shall not come into contact with the ground or other contaminated surface and shall otherwise be handled, maintained, and stored in a manner to prevent contamination.
12VAC5-590-1240. General. (Repealed.)
Part IV. Exceptions for Noncommunity Waterworks to Specific Sections of the Manual of Practice (Part III)
Noncommunity waterworks design shall conform to Part III of this chapter. Due to the types of service provided and size of some noncommunity waterworks, certain exceptions to the design requirement specified in Part III may be allowed. Each of the following subsections will refer to exceptions in corresponding sections of Part III.
12VAC5-590-1250. Exceptions to Article 1 of Part III. (Repealed.)
A. The evaluation of source requirements shall consider the type and use of the noncommunity system. Minimum storage for noncommunity waterworks, in conjunction with the source, must provide system peak hour demand.
B. A minimum laboratory facility of a sink and workbench shall be provided.
12VAC5-590-1260. Exceptions to Article 2 of Part III. (Repealed.)
A. Exceptions to the minimum size well lot may be made for noncommunity waterworks, based upon site availability and other factors.
B. When the source requirements for a noncommunity system are determined to be three gallons per minute or less the 48-hour minimum drawdown test may be reduced to no less than eight hours. The drawdown test, approved by the division and based upon system demands and geological conditions, shall be performed to determine well yield.
12VAC5-590-1270. Exceptions to Article 5 of Part III. (Repealed.)
When booster pumping is required for small noncommunity systems, the duplicity and capacity requirements may be reduced in accordance with the type and size of system served.
12VAC5-590-1280. Exceptions to Article 6 of Part III. (Repealed.)
In the instance where a noncommunity water system serves a single building, the water line plumbing (including size) shall be in accordance with the most recent edition of the Uniform Statewide Building Code.
When a noncommunity water system serves two or more buildings, the water line shall be of sufficient size to provide adequate flow and pressure in order to meet the system demands.
EDITOR'S NOTE: Text stricken in Appendices A through E, G, I, and L through P in the proposed regulation has not been further amended, therefore it is not published. See proposed stricken text at 36:6 VA.R. 475-845 November 11, 2019.
NOTICE: The following forms used in administering the regulation have been filed by the agency. Amended or added forms are reflected in the listing and are published following the listing. Online users of this issue of the Virginia Register of Regulations may also click on the name to access a form. The forms are also available from the agency contact or may be viewed at the Office of Registrar of Regulations, 900 East Main Street, 11th Floor, Richmond, Virginia 23219.
FORMS (12VAC5-590)
Uniform Water Well Completion Report, Form GW-2 (rev. 7/2016 & 8/2016)
Waterworks Level 1 Assessment, Form ODW-4 (eff. 4/2016)
Waterworks Level 2 Assessment, Form ODW-5 (eff. 4/2016)
Application for Monitoring Waivers (rev. 3/2019)
Waterworks Permit Application, ODW-001 (filed 10/2019)
Operational Evaluation Reporting Form (filed 10/2019)
Waterworks Level 1 Assessment (rev. 9/2017)
Waterworks Level 2 Assessment (rev. 9/2017)
Well Yield and Recovery Report Form, ODW-002 (filed 10/2020)
DOCUMENTS INCORPORATED BY REFERENCE (12VAC5-590)
"Maximum Permissible Body Burdens and Maximum Permissible Concentration of Radionuclides in Air or Water for Occupational Exposure," National Bureau of Standards Handbook 69.
Standard Methods for the Examination of Water and Wastewater, 18th edition, American Public Health Association, American Waterworks Association, and Water Pollution Control Federation, 1992.
ANSI/NSF Standard for Drinking Water Treatment System Components, ANSI/NSF 61, American National Standard Institute, November, 1994.
AWWA Standard for American National Standard for Cement-Mortar Lining for Ductile-Iron Pipe and Fittings for Water, C-104, American Waterworks Association.
AWWA Standard for American National Standard for Polyethylene Encasement for Ductile-Iron Pipe and Fittings for Water, C-105, American Waterworks Association.
AWWA Standard for American National Standard for Ductile-Iron and Gray-Iron Fittings 3 Inch Through 48 Inch for Water, C-110, American Waterworks Association.
AWWA Standard for American National Standard for Rubber-Gasket Joints for Ductile-Iron Pressure Pipe and Fittings, C-111, American Waterworks Association.
AWWA Standard for American National Standard for Flanged Ductile-Iron Pipe with Threaded Flanges, C-115, American Waterworks Association.
AWWA Standard for American National Standard for the Thickness Design of Ductile-Iron Pipe, C-150, American Waterworks Association.
AWWA Standard for American National Standard for Ductile-Iron Pipe, Centrifugally Cast, for Water or Other Liquids, C-151, American Waterworks Association.
AWWA Standard for American National Standard for Ductile-Iron Pipe, Compact Fittings, 3 Inch Through 16 Inch, for Water and Other Liquids, C-153, American Waterworks Association.
AWWA Standard for Steel Water Pipe, 6 Inch and Larger, C-200, American Waterworks Association.
AWWA Standard for Coal-Tar Protective Coatings and Linings for Steel Water Pipelines- Enamel and Tape-Hot Applied, C-203, American Waterworks Association.
AWWA Standard for Cement-Mortar Protective Lining and Coating for Steel Water Pipe-4 Inch and Larger-Shop Applied, C-205, American Waterworks Association.
AWWA Standard for Field Welding of Steel Water Pipe, C-206, American Waterworks Association.
AWWA Standard for Steel Pipe Flanges for Waterworks Service-4 Inch and Larger-Shop Applied, C-207, American Waterworks Association.
AWWA Standard for Dimensions for Fabricated Steel Water Pipe Fittings, C-208, American Waterworks Association.
AWWA Standards for Cold-Applied Coatings for the Exterior of Special Sections, Connections, and Fittings for Steel Water Pipelines, C-209, American Waterworks Association.
AWWA Standard for Liquid-Epoxy Coating Systems for the Interior and Exterior of Steel Water Pipelines, C-210, American Waterworks Association.
AWWA Standard for Fusion-Bonded Epoxy Coating for the Interior and Exterior of Steel Water Pipelines, C-213, American Waterworks Association.
AWWA Standards for Tape Coating Systems for the Exterior of Steel Water Pipelines, C-214, American Waterworks Association.
AWWA Standard for Extruded Polyolefin Coatings for the Exterior of Steel Water Pipelines, C-215, American Waterworks Association.
AWWA Standard for Cross-Linked Polyolefin Coatings for the Exterior of Special Sections, Connections, and Fittings for Buried Steel Water Pipelines, C-216, American Waterworks Association.
AWWA Standard for Cold-Applied Petrolatum Tape and Petroleum Wax Tape Coatings for the Exterior of Special Sections, Connections, and Fittings for Buried Steel Water Pipelines, C-217, American Waterworks Association.
AWWA Standard for Coating the Exterior of Aboveground Steel Water Pipelines and Fittings, C-218, American Waterworks Association.
AWWA Standard for Bolted, Sleeve-Type Couplings for Plain-End Pipe, C-219, American Waterworks Association.
AWWA Standard for Stainless Steel Pipe, 4 Inch and Larger, C-220, American Waterworks Association.
AWWA Standard for Reinforced Concrete Pressure Pipe, Steel-Cylinder Type, for Water and Other Liquids, C-300, American Waterworks Association.
AWWA Standard for Prestressed Concrete Pressure Pipe, Steel-Cylinder Type, for Water and Other Liquids, C-301, American Waterworks Association.
AWWA Standard for Reinforced Concrete Pressure Pipe, Noncylinder Type, for Water and Other Liquids, C-302, American Waterworks Association.
AWWA Standard for Reinforced Concrete Pressure Pipe, Noncylinder Type, Pretensioned, for Water and Other Liquids, C-303, American Waterworks Association.
AWWA Standard for Design of Prestressed Concrete Cylinder Pipe, C-304, American Waterworks Association.
AWWA Standard for the Selection of Asbestos-Cement Transmission and Feeder Main Pipe, C-403, American Waterworks Association.
AWWA Standard for Cement-Mortar Lining of Water Pipelines-4 Inch (1000 mm) and Larger-In Place, C-602, American Waterworks Association.
AWWA Standard for Underground Service Line Valves and Fittings, C-800, American Waterworks Association.
AWWA Standard for Polyvinyl Chloride Pressure Pipe, 4 Inch Through 12 Inch for Water Distribution, C-900, American Waterworks Association.
AWWA Standard for Polybutylene Pressure Pipe and Tubings, 1/2 Inch Through 3 Inch, for Water Service, C-902, American Waterworks Association.
AWWA Standard for Polyethylene Pressure Pipe and Fittings, 4 Inch Through 63 Inch, for Water Distribution, C-906, American Waterworks Association.
AWWA Standard for Polyethylene Pressure Pipe and Tubing, 1/2 Inch Through 3 Inch, for Water Service, C-901, American Waterworks Association.
AWWA Standard for Polyvinyl Chloride Water Transmission Pipe, Nominal Diameters 14 Inch Through 36 Inch, C-905, American Waterworks Association.
AWWA Standard for Polyvinyl Chloride Pressure Fittings, 4 Inch Through 8 Inch, C-907, American Waterworks Association.
AWWA Standard for Fiberglass Pressure Pipe, C-950. American Waterworks Association.
AWWA Standard for Asbestos-Cement Pressure Pipe, 4 Inch Through 16 Inch, for Water Distribution Systems, C-400, American Waterworks Association.
AWWA Standard for Selection of Asbestos-Cement Pressure Pipe, 4 Inch Through 16 Inch, for Water Distribution Systems, C-401, American Waterworks Association.
AWWA Standard for Asbestos-Cement Transmission Pipe, 18 Inch Through 42 Inch, for Potable Water and Other Liquids, C-402, American Waterworks Association.
AWWA Standard for Installation of Ductile-Iron Pipe and Their Appurtenances, C-600, American Waterworks Association.
AWWA Standard for Installation of Asbestos-Cement Pressure Pipe, C-603, American Waterworks Association.
AWWA Standard for Grooved and Shouldered Joints, C-606, American Waterworks Association.
AWWA Standard for Disinfecting Water Mains, C-651, American Waterworks Association.
Control of Communicable Diseases in Man, 15 edition, American Public Health Association, 1990.
U.S. Department of Commerce (https:/www.commerce.gov/):
Maximum Permissible Body Burdens and Maximum Permissible Concentrations of Radionuclides in Air and in Water for Occupational Exposure, NBS Handbook 69 issued June 5, 1959 and amended August 1963, U.S. Department of Commerce
U.S. Environmental Protection Agency (https:/www.epa.gov/):
Ultraviolet Disinfection Guidance Manual for the Final Long Term 2 Enhanced Surface Water Treatment Rule, [ Office of Water, ] EPA 815-R-06-007, [ Office of Water, ] November 2006
[ Enhanced Coagulation and Enhanced Precipitative Softening Guidance Manual, EPA 815-R-99-012, Office of Water, May 1999 ]
Consensus Method for Determining Groundwaters [ under Under ] the Direct Influence of Surface Water Using Microscopic Particulate Analysis (MPA), EPA [ 910/992029 910/9-92-029 ], Environmental Services Division, October 1992
[ The ] Stage 2 Disinfectants and Disinfection Byproducts Rule (Stage 2 DBPR) Implementation Guidance, [ Office of Water, ] EPA 816-R-07-007, [ Office of Water, ] August 2007
Long Term 2 Enhanced Surface Water Treatment Rule Toolbox Guidance Manual, [ Office of Water, ] EPA 815-R-09-016, [ Office of Water, ] April 2010
NSF International, P.O. Box 130140, 789 N. Dixboro Road, Ann Arbor, MI 48105 (http://www.nsf.org/):
[ NSF/ANSI Standard 60-2017 NSF/ANSI/CAN Standard 60-2020 ] , Drinking Water Treatment Chemicals - Health Effects, [ April 23, 2017 2020 ]
[ NSF/ANSI Standard 61-2017 NSF/ANSI/CAN Standard 61-2020 ] , Drinking Water System Components - Health Effects, [ March 13, 2017 2020 ]
[ ASSE International.18927 Hickory Creek Drive, Suite 220, Mokena, IL 60448 (https://www.asse-plumbing.org/): ]
[ ASSE Standard #1011-2017, Performance Requirements For Hose Connection Vacuum Breakers, 2017 ]
[ ASSE Standard #1052-2016, Performance Requirements For Hose Connection Backflow Preventers, 2016 ]
[ ASSE Standard #1057-2012, Performance Requirements For Freeze Resistant Sanitary Yard Hydrant with Backflow Protection, 2012 ]
ASTM International, 100 Barr Harbor Drive, P.O. Box C700, West Conshohocken, PA 19428-2959 (https://www.astm.org/):
ASTM F480-14, Standard Specification for Thermoplastic Well Casing Pipe and Couplings Made in Standard Dimension Ratios (SDR), SCH 40 and SCH 80, March 1, 2014
American Water Works Association, 666 W. Quincy Avenue, Denver, CO 80235 (https://www.awwa.org/):
AWWA Standard, ANSI/AWWA [ A100-15, A100-20, ] Water Wells, [ December 1, 2015 eff. 7/1/2020 ]
AWWA Standard, ANSI/AWWA B114-16, Reverse Osmosis and Nanofiltration Systems for Water Treatment, [ May 1, 2016 eff. 5/1/2016 ]
[ AWWA Standard, ANSI/AWWA C502-18, Dry-Barrel Fire Hydrants, eff. 1/1/2019 ]
AWWA Standard, ANSI/AWWA C600-17, Installation of Ductile-Iron Mains and Their Appurtenances, [ July 1, 2017 eff. 7/1/2017 ]
AWWA Standard, ANSI/AWWA C604-17, Installation of Buried Steel Water Pipe - 4 In. (100 mm) and Larger, [ August 1, 2017 eff. 8/1/2017 ]
AWWA Standard, ANSI/AWWA C605-13, Underground Installation of Polyvinyl Chloride (PVC) and Molecularly Oriented Polyvinyl Chloride (PVCO) Pressure Pipe and Fittings, [ February 1, 2014eff. 2/1/2014 ]
AWWA Standard, ANSI/AWWA C651-14, Disinfecting Water Mains, [ February 1, 2015 eff. 2/1/2015 ]
AWWA Standard, ANSI/AWWA [ C652-11, C652-19, ] Disinfection of Water-Storage Facilities, [ October 1, 2011 eff. 4/1/2020 ]
AWWA Standard, ANSI/AWWA [ C653-13, C653-20, ] Disinfection of Water Treatment Plants, [ December 1, 2013 eff.9/1/2020 ]
AWWA Standard, ANSI/AWWA C654-13, Disinfection of Wells, [ July 1,2013 eff. 7/1/2013 ]
AWWA Standard, ANSI/AWWA D100-11, Welded Carbon Steel Tanks for Water Storage, [ July 1, 2011 eff. 7/1/2011 ]
AWWA Standard, ANSI/AWWA D102-17, Coating Steel Water-Storage Tanks, [ December 1, 2017 eff. 12/1/2017 ]
AWWA Standard, ANSI/AWWA [ D103-09, D103-19, ] Factory-Coated Bolted Carbon Steel Tanks for Water Storage, [ November 1, 2009 eff. 1/1/2020 ]
AWWA Standard, ANSI/AWWA D104-17, Automatically Controlled, Impressed-Current Cathodic Protection for the Interior Submerged Surfaces of Steel Water Storage Tanks, [ December 1, 2017 eff. 12/1/2017 ]
AWWA Standard, ANSI/AWWA [ D106-16, D106-20, ] Sacrificial Anode Cathodic Protection Systems for the Interior Submerged Surfaces of Steel Water Storage Tanks, [ June 1, 2016 eff. 8/1/2020 ]
AWWA Standard, ANSI/AWWA D107-16, Composite Elevated Tanks for Water Storage, [ January 1, 2017 eff. 1/1/2017 ]
AWWA Standard, ANSI/AWWA [ D108-10, D108-19, ] Aluminum Dome Roofs for Water Storage Facilities, [ June 1, 2010 eff.11/1/2019 ]
AWWA Standard, ANSI/AWWA D110-13 (R-18), Wire- and Strand-Wound, Circular, Prestressed Concrete Water Tanks, [ August1, 2018 eff. 8/1/2018 ]
AWWA Standard, ANSI/AWWA [ D115-17, D115-20, ] Tendon-Prestressed Concrete Water Tanks, [ July 1,2017 eff. 7/1/2020 ]
AWWA Standard, ANSI/AWWA [ D120-09, D120-19, ] Thermosetting Fiberglass-Reinforced Plastic Tanks, [ October 1, 2009 eff. 10/1/2019 ]
AWWA Standard, ANSI/AWWA D121-12, Bolted Aboveground Thermosetting Fiberglass-Reinforced Plastic Panel-Type Tanks for Water Storage, [ June 1, 2012 eff. 6/1/2012 ]
Tendon-Prestressed Concrete Water Tanks (eff. 7/1/2020)
AWWA Permission Letter-2-9-2021
Dry-Barrel Fire Hydrants (eff. 1/1/2019)
Performance Requirements For Hose Connection Vacuum Breakers (eff. 11/2017)
Performance Requirements For Hose Connection Backflow Preventers (eff. 5/3/2016)
Performance Requirements For Freeze Resistant Sanitary Yard Hydrant with Backflow Protection (eff. 7/2012)
Drinking Water Treatment Chemicals - Health Effects (eff. 2020)
Drinking Water System Components - Health Effects (eff. 2020)
Water Wells (eff. 7/1/2020)
Disinfection of Water-Storage Facilities (eff. 4/1/2020)
Disinfection of Water Treatment Plants (eff. 9/1/2020)
Factory-Coated Bolted Carbon Steel Tanks for Water Storage (eff. 1/1/2020)
Sacrificial Anode Cathodic Protection Systems for the Interior Submerged Surfaces of Steel Water Storage Tanks (eff. 8/1/2020)
Aluminum Dome Roofs for Water Storage Facilities (eff. 11/1/2019)
Thermosetting Fiberglass-Reinforced Plastic Tanks (eff. 10/1/2019)
VA.R. Doc. No. R18-5204; Filed April 28, 2021